THROUGH THE WALL UNIT
23
2.2.4.2 Conditions of compressor working
:
a. Compressor starts: RT
≤
ST+1
℃;
b. Compressor stops: RT
>
ST+3
℃;
c. +1
℃<
ST-RT
≤
+3
℃,
compressor maintains the original state.
2.2.4.3 The first time the unit is turned on, there will be a 3 minute delay for compressor
protection before temperature starts to rise.
2.2.4.4 Operation of four-way valve
:
In heating mode, the four-way valve remains open
(except when defrosting). When heating mode is selected or unit is turned on, the four-way
valve will open 5 minutes before compressor starts. When mode is changed from heating
mode or unit is turned off, four-way valve will close after compressor has stopped for 2
minutes.
2.2.4.5 Operation of outdoor motor: Starts and stops at the same time as the compressor
(Except when system goes into the defrost function or over heat protection).
2.2.4.6 Indoor auto fan speed selection.
2.2.4.7 Pre-heat control: After selecting heating mode, when IPT
≥
38
℃
, indoor fan motor will
run according to the setting. When IPT
<
38
℃
, indoor fan motor will delay starting until
compressor runs for 60 seconds.
In heating mode, when the unit has been heating for 30 minutes or more and the compressor
is continuously running for 5 minutes, the outdoor coil temperature sensor starts detecting the
outdoor coil temperature. When the sensor detects <-5 degree for 1 minute, and above 2
conditions are met, the unit will begin to defrost.
When defrosting, if the compressor has run for 5 minutes and OPT rises to 15
℃
, defrosting
will stop automatically and normal heating will resume.
Содержание PTTW-10-EC Series
Страница 1: ...ENGINEERING MANUAL PTTW 10 EC SERIES THROUGH THE WALL AIR CONDITIONERS 2010 EU V 1 1 ...
Страница 7: ...THROUGH THE WALL UNIT 6 Noise Level Indoor Fan Mode ...
Страница 8: ...THROUGH THE WALL UNIT 7 Noise Level Indoor Cooling Mode ...
Страница 9: ...THROUGH THE WALL UNIT 8 Noise Level Outdoor Cooling Mode ...
Страница 10: ...THROUGH THE WALL UNIT 9 OPERATION TEST PTTW 10 Cooling test ...
Страница 11: ...THROUGH THE WALL UNIT 10 PTTW 10 Heating test ...
Страница 12: ...THROUGH THE WALL UNIT 11 PTTW 10 Heating test ...
Страница 13: ...THROUGH THE WALL UNIT 12 PTTW 10 Heating test ...
Страница 14: ...THROUGH THE WALL UNIT 13 EXPLODED DRAWING ...
Страница 19: ...THROUGH THE WALL UNIT 18 ELECTRIC WIRING DIAGRAM For PTTW 10 ...
Страница 34: ...THROUGH THE WALL UNIT 33 THIS IS THE END ...