HYDRONIC CASSETTE
57
For unit with wall pad only
Error message can be found in both LED lights on unit body (please refer to table 1) and wall pad error indication.
(Please refer to page 49 Error Indication)
Note: If the address of slave unit is not set (refer to appendix I) LED lights and Wall pad of the master unit will not
show the status of the defective slave unit.
Without Master-Slave connection
For unit with handset only
For all units Red LED light on the unit
High speed
Red LED On
Medial speed
Yellow LED On
Low speed
Green LED On
For all units Green LED light on the unit
Electrical heater failure
Blink 1times, stop 3 sec
Return air sensor failure
Blink 3 times, stop 3 sec
Indoor coil sensor 1 failure
Blink 4 times, stop 3 sec
Indoor coil low temperature protection Blink 5 times, stop 3 sec
Indoor coil over heat protection
Blink 6 times, stop 3 sec
For unit with wall pad only
Error message can be found in both LED lights on the unit body (please refer to table 2) and on the wall
pad error indication. (Please refer to page 49 Error Indication)
Table 2
Содержание PCG-06
Страница 31: ...HYDRONIC CASSETTE 31 5th STEP change the fan speed wiring according to below wiring diagram ...
Страница 39: ...HYDRONIC CASSETTE 39 DIMENSIONAL DRAWINGS PCG 06 08 PS ...
Страница 40: ...HYDRONIC CASSETTE 40 PCG 09 PS ...
Страница 41: ...HYDRONIC CASSETTE 41 PCG 12 16 PS ...
Страница 42: ...HYDRONIC CASSETTE 42 VALVE INFORMATION ...
Страница 43: ...HYDRONIC CASSETTE 43 ...
Страница 44: ...HYDRONIC CASSETTE 44 REMOTE CONTROL HANDSET WIRELESS LCD HANDSET DISPLAY ...
Страница 60: ...HYDRONIC CASSETTE 60 CONTROL AND POWER SUPPLY WIRING DIAGRAMS ...
Страница 61: ...HYDRONIC CASSETTE 61 MASTER SLAVE CONTROL WIRING DIAGRAM ...
Страница 66: ...HYDRONIC CASSETTE 66 ...