WALL PAD OPERATION
1) Clock display and setting
System has an accurate internal real time clock used for time indication and timer ON/OFF function.
Real time clock display area indicates internal time clock which can be set by
TIME
or
TIME
button.
2) Day display and setting
The wall pad has day display function which is used for day indication and timer ON/OFF function.
Day display icon indicates current day. Press
DAY
button to set day.
3) Timer ON/OFF setting
If master unit is in global control mode and on/off timer setting is reached, master unit will command
the whole network to be on or off. Otherwise timer on/off is effective to the local unit only. The system
supports 7 days on/off timer setting.
a) Press
TIMER
button once,
and
ON
symbol blinking indicates on timer programming mode,
day display area indicates the day for setting timer on. If on timer for this day is null, timer
display area shows
, otherwise the on timer setting will be shown. Press
TIME
or
TIME
button to change the on timer setting. Press
CANCEL
key to cancel the current on timer selected
and the timer display area will show
. Press
DAY
button to change the day the on
timer is to be programmed.
b) Press
TIMER
button again,
and
OFF
symbol blinking indicates off timer programming
mode. The setting method is the same as on timer setting above.
c) Press
TIMER
button again, to exit timer on/off setting function.
d) Should there be any on or off timer being programmed,
will light up. Should there be any
unexecuted on or off timer for the current day, its corresponding
ON
or
OFF
icon will light up.
e) Hold
down
CANCEL
button for 3 seconds to cancel all timer settings.
Timer set by master unit is as follows:-
1. Press
NET
button to enter into networking control mode. Unit area blinking indicates the
slave unit under control. Press
TIME
or
TIME
to select the desired slave unit. Units that are off
will be skipped automatically.
2. Press
TIMER
button once to enter into on timer programming mode. Press
DAY
button to
select the required day of the week. Master unit will then retrieve the setting from the
selected slave unit and timer display area will show “rEAd”. The on timer setting will be
shown upon reading the data successfully. Press
TIME
or
TIME
button to change the on timer
setting.
Содержание PCG-06
Страница 31: ...HYDRONIC CASSETTE 31 5th STEP change the fan speed wiring according to below wiring diagram ...
Страница 39: ...HYDRONIC CASSETTE 39 DIMENSIONAL DRAWINGS PCG 06 08 PS ...
Страница 40: ...HYDRONIC CASSETTE 40 PCG 09 PS ...
Страница 41: ...HYDRONIC CASSETTE 41 PCG 12 16 PS ...
Страница 42: ...HYDRONIC CASSETTE 42 VALVE INFORMATION ...
Страница 43: ...HYDRONIC CASSETTE 43 ...
Страница 44: ...HYDRONIC CASSETTE 44 REMOTE CONTROL HANDSET WIRELESS LCD HANDSET DISPLAY ...
Страница 60: ...HYDRONIC CASSETTE 60 CONTROL AND POWER SUPPLY WIRING DIAGRAMS ...
Страница 61: ...HYDRONIC CASSETTE 61 MASTER SLAVE CONTROL WIRING DIAGRAM ...
Страница 66: ...HYDRONIC CASSETTE 66 ...