2. Compressor checking
Measure the resistance value of each winding by using the tester.
Position
Resistance Value
ASK89D53UEZ
ASN108D22UEZ
DA130M1C-31FZ
DA150S1C-20FZ
Blue - Red
2.45Ω
(20
℃
)
1.5Ω
(20
℃
)
1.77Ω
(20
℃
)
0.95Ω
(20
℃
)
Blue -
Black
Red - Blue
3.IPM continuity check
Turn off the power, let the large capacity electrolytic capacitors discharge completely, and dismount the IPM. Use a
digital tester to measure the resistance between P and UVWN; UVW and N.
Digital tester
Normal resistance value
(+)Red
(-)Black
∞
(Several MΩ)
P
N
U
V
W
Digital tester
Normal resistance value
(+)Red
(-)Black
∞
(Several MΩ)
U
N
V
W
4.Indoor AC Fan Motor
Measure the resistance value of each winding by using the tester.
Содержание FSAI-SU-120AE2
Страница 8: ...8 3 Dimension 3 1 Indoor Unit W D H Model W D H FSAI SU 90AE2 715 188 250 FSAI SU 120AE2 800 188 275 ...
Страница 12: ...12 4 2 Wiring Diagram Indoor unit FSAI SU 90AE2 FSAI SU 120AE2 Outdoor unit FSOAI SU 90AE2 ...
Страница 13: ...13 Outdoor unit FSOAI SU 120AE2 ...
Страница 25: ...25 Use torque wrench to tighten the service port cap to a torque of 18N m Be sure to check for gas leakage ...
Страница 41: ...41 8 2 2 Indoor unit and outdoor unit communication protection error diagnosis and solution E1 ...
Страница 45: ...45 8 2 6 Refrigerant Leakage Detection diagnosis and solution EC ...
Страница 46: ...46 8 2 7 IPM malfunction or IGBT over strong current protection diagnosis and solution P0 ...
Страница 47: ...47 8 2 8 Over voltage or too low voltage protection diagnosis and solution P1 ...
Страница 48: ...48 8 2 9 High temperature protection of compressor top diagnosis and solution P2 ...
Страница 49: ...49 8 2 10 Inverter compressor drive error diagnosis and solution P4 ...