5.4 Installation for the first time
Air and moisture in the refrigerant system have undesirable effects as below:
●
Pressure in the system rises.
●
Operating current rises.
●
Cooling or heating efficiency drops.
●
Moisture in the refrigerant circuit may freeze and block capillary tubing.
●
Water may lead to corrosion of parts in the refrigerant system.
Therefore, the indoor units and the pipes between indoor and outdoor units must be leak tested
and evacuated to remove gas and moisture from the system.
Gas leak check (Soap water method):
Apply soap water or a liquid neutral detergent on the indoor unit connections or outdoor unit
connections by a soft brush to check for leakage of the connecting points of the piping. If bubbles
come out, the pipes have leakage.
1. Air purging with vacuum pump
(Indoor unit)
(Liquid side)
(Gas side)
Vacuum
pump
Vacuum
pump
Lo
Hi
Handle Hi
Two-way valve
Close
Manifold valve
Compound meter
Pressure
gauge
-0.1MPa
Handle Lo
Charge hose
Charge hose
(Outdoor unit)
Close
Three-way valve
Содержание FSAI-SU-120AE2
Страница 8: ...8 3 Dimension 3 1 Indoor Unit W D H Model W D H FSAI SU 90AE2 715 188 250 FSAI SU 120AE2 800 188 275 ...
Страница 12: ...12 4 2 Wiring Diagram Indoor unit FSAI SU 90AE2 FSAI SU 120AE2 Outdoor unit FSOAI SU 90AE2 ...
Страница 13: ...13 Outdoor unit FSOAI SU 120AE2 ...
Страница 25: ...25 Use torque wrench to tighten the service port cap to a torque of 18N m Be sure to check for gas leakage ...
Страница 41: ...41 8 2 2 Indoor unit and outdoor unit communication protection error diagnosis and solution E1 ...
Страница 45: ...45 8 2 6 Refrigerant Leakage Detection diagnosis and solution EC ...
Страница 46: ...46 8 2 7 IPM malfunction or IGBT over strong current protection diagnosis and solution P0 ...
Страница 47: ...47 8 2 8 Over voltage or too low voltage protection diagnosis and solution P1 ...
Страница 48: ...48 8 2 9 High temperature protection of compressor top diagnosis and solution P2 ...
Страница 49: ...49 8 2 10 Inverter compressor drive error diagnosis and solution P4 ...