Index2:
1. Outdoor DC fan motor(control chip is inside fan motor)
Power on and when the unit is in standby, measure the voltage of pin1-pin3, pin4-pin3 in fan motor
connector. If the value of the voltage is not in the range showing in below table, the PCB must have
problems and need to be replaced.
For other models:
DC motor voltage input and output
NO.
Color
Signal
Voltage
1
Red
Vs/Vm
140V~380V
2
---
---
---
3
Black
GND
0V
4
White
Vcc
13.5-16.5V
5
Yellow
Vsp
0~6.5V
6
Blue
FG
15V
Содержание FS2MIF-140AE2
Страница 5: ...4 3 Dimensions FS2MIF 140AE2 FS2MIF 180AE2 FS3MIF 210AE2 ...
Страница 6: ...5 FS3MIF 270AE2 FS4MIF 280AE2 ...
Страница 7: ...6 FS4MIF 360AE2 FS5MIF 360AE2 ...
Страница 8: ...7 4 Wiring Diagram FS2MIF 140AE2 FS2MIF 180AE2 ...
Страница 9: ...8 FS3MIF 210AE2 FS3MIF 270AE2 FS4MIF 280AE2 ...
Страница 10: ...9 FS4MIF 360AE2 FS5MIF 360AE2 ...
Страница 35: ...34 9 3 Trouble shooting 9 3 1 For the indoor unit 9 3 1 1 Indoor EEPROM malfunction ...
Страница 36: ...35 9 3 1 2 Indoor outdoor units communication error ...
Страница 44: ...43 9 3 2 For the outdoor unit 9 3 2 1 Outdoor EEPROM malfunction ODU E0 ...
Страница 46: ...45 9 3 2 3 Voltage protection ODU E5 ...
Страница 47: ...46 9 3 2 4 PFC module protection ODU E6 For FS4MIF 280AE2 FS4MIF 360AE2 FS5MIF 360AE2 ...
Страница 51: ...50 9 3 2 7 Low pressure protection ODU P2 For FS4MIF 280AE2 FS4MIF 360AE2 FS5MIF 360AE2 ...
Страница 52: ...51 9 3 2 8 Current protection of compressor ODU P3 ...