39
For other models:
NO.
Color
1
Red
2
---
3
Black
4
White
5
Yellow
6
Blue
For console:
5
4
6
3
2
1
NO.
Color
1
Red
2
---
3
White
4
Blue
5
Yellow
6
Black
Index2:
1: Indoor AC fan motor
Power on and set the unit running in fan mode at high fan speed. After running for 15 seconds, measure the
voltage of pin1 and pin2. If the value of the voltage is less than 100V(208~240V power supply)or 50V(115V
power supply), the PCB must have problems and need to be replaced.
Содержание FS2MIF-140AE2
Страница 5: ...4 3 Dimensions FS2MIF 140AE2 FS2MIF 180AE2 FS3MIF 210AE2 ...
Страница 6: ...5 FS3MIF 270AE2 FS4MIF 280AE2 ...
Страница 7: ...6 FS4MIF 360AE2 FS5MIF 360AE2 ...
Страница 8: ...7 4 Wiring Diagram FS2MIF 140AE2 FS2MIF 180AE2 ...
Страница 9: ...8 FS3MIF 210AE2 FS3MIF 270AE2 FS4MIF 280AE2 ...
Страница 10: ...9 FS4MIF 360AE2 FS5MIF 360AE2 ...
Страница 35: ...34 9 3 Trouble shooting 9 3 1 For the indoor unit 9 3 1 1 Indoor EEPROM malfunction ...
Страница 36: ...35 9 3 1 2 Indoor outdoor units communication error ...
Страница 44: ...43 9 3 2 For the outdoor unit 9 3 2 1 Outdoor EEPROM malfunction ODU E0 ...
Страница 46: ...45 9 3 2 3 Voltage protection ODU E5 ...
Страница 47: ...46 9 3 2 4 PFC module protection ODU E6 For FS4MIF 280AE2 FS4MIF 360AE2 FS5MIF 360AE2 ...
Страница 51: ...50 9 3 2 7 Low pressure protection ODU P2 For FS4MIF 280AE2 FS4MIF 360AE2 FS5MIF 360AE2 ...
Страница 52: ...51 9 3 2 8 Current protection of compressor ODU P3 ...