HEAT_F8
IHEATLMT4
HEAT_F7
IHEATLMT3
HEAT_F6
IHEATLMT2
HEAT_F5
IHEATLMT1
If the current frequency is lower than HEAT_F4, the frequency will not be limited.
After 10s of the compressor start, if the current>IHEAT, the AC will display the failure for 30 seconds and stop. The AC
will restart 3 minutes later.
8.5.5 Indoor / outdoor units communication protection
If the indoor units can not receive the feedback signal from the outdoor units for 2 minutes, the AC will stop
and display the failure.
8.5.6 High condenser coil temp. protection.
When T3>65°C for 3 seconds, the compressor will stop while the indoor fan and outdoor fan will continue.
When T3<52°C the protection will release and the compressor will restart after 3 minutes.
8.5.7 Outdoor unit anti-freezing protection
When T2B<0°C for 250 seconds, the indoor unit capacity demand will be zero and resume to normal when
T2B>10°C
8.5.8 Oil return
Running rules:
1. If the compressor frequency keeps lower than RET_OIL_FREQ1_ADD for RET_OIL_TIME1_ADD, the
AC will rise the frequency to RET_OIL_FREQ2_ADD for RET_OIL_TIME2_ADD and then resume to
former frequency.
2. The EXV will keep 300p while the indoor units will keep the current running mode.
If the outdoor ambient is higher than TempT4HeatLimit_ADD during the oil return, the AC quit oil return.
Содержание FS2MIF-140AE2
Страница 5: ...4 3 Dimensions FS2MIF 140AE2 FS2MIF 180AE2 FS3MIF 210AE2 ...
Страница 6: ...5 FS3MIF 270AE2 FS4MIF 280AE2 ...
Страница 7: ...6 FS4MIF 360AE2 FS5MIF 360AE2 ...
Страница 8: ...7 4 Wiring Diagram FS2MIF 140AE2 FS2MIF 180AE2 ...
Страница 9: ...8 FS3MIF 210AE2 FS3MIF 270AE2 FS4MIF 280AE2 ...
Страница 10: ...9 FS4MIF 360AE2 FS5MIF 360AE2 ...
Страница 35: ...34 9 3 Trouble shooting 9 3 1 For the indoor unit 9 3 1 1 Indoor EEPROM malfunction ...
Страница 36: ...35 9 3 1 2 Indoor outdoor units communication error ...
Страница 44: ...43 9 3 2 For the outdoor unit 9 3 2 1 Outdoor EEPROM malfunction ODU E0 ...
Страница 46: ...45 9 3 2 3 Voltage protection ODU E5 ...
Страница 47: ...46 9 3 2 4 PFC module protection ODU E6 For FS4MIF 280AE2 FS4MIF 360AE2 FS5MIF 360AE2 ...
Страница 51: ...50 9 3 2 7 Low pressure protection ODU P2 For FS4MIF 280AE2 FS4MIF 360AE2 FS5MIF 360AE2 ...
Страница 52: ...51 9 3 2 8 Current protection of compressor ODU P3 ...