Instruction Manual
D104331X012
easy-Drive 200L
December 2018
25
Table 3. easy-Drive 200L Modbus Map (cont.)
Type
Name
MB Register
Default
R/W
Values
Notes
unit16
Deadband
(10=1.0%)
40053
5
R/W
0-250
Minimum percentage signal change to elicit a
movement response based upon end position of last
movement. For example, if the previous command
resulted in the actuator moving to 31.2% of travel and
deadband is set to 100 (10.0%), setpoint must
command valve to 21.2% or 41.2% before valve will
move to new position. Default is set set to minimize
signal dithering.
unit16
Low travel cutoff position
(100=10.0%)
40054
50
R/W
0-999
Analog input command, in percent with one implied
decimal (50=5.0%), below this value will result in the
valve plug moving to the closed position. Active in
both local and Modbus control modes.
unit16
Analog on/off close position
(100=10.0%)
40055
400
R/W
0-999
When the valve is in 4-20 mA on/off mode, this value is
the point at which the valve will close. It must be set to
a smaller value than the analog on/off open position.
Percentage position value with one implied decimal
(400=40.0%).
unit16
Analog on/off open position
(100-10.0%)
40056
500
R/W
1-1000
When the valve is in 4-20 mA on/off mode, this value is
the point at which the valve will open. It must be set to
a larger value than the analog on/off close position.
Percentage position value with one implied decimal
(500=50.0%).
unit16
Analog Close Value
40057
40
R
31 - 220
The analog value, in mA with one implied decimal
(40=4.0 mA), that defines the closed position
unit16
Analog Open Value
40058
200
R
31 - 220
The analog value , in mA with one implied decimal
(200=20.0 mA), that defines the open position
unit16
Number of retries
40059
2
R/W
0-4
When the valve plug encounters an obstruction, how
many attempts will it make to move past that point,
assuming no change in the command signal within the
deadband range
unit16
RESERVED
40060
unit16
RESERVED
40061
unit16
RESERVED
40062
unit16
RESERVED
40063
unit16
RESERVED
40064
unit16
RESERVED
40065
unit16
RESERVED
40066
unit16
Control Source
40067
0
R/W
0-5
0=Dual Contact On/Off 1=Single Contact On/Off,
2=Modbus On/Off, 3=Modbus Positioning,
4=4-20 Positioning, 5=4-20 Level
unit16
Valve Type
40068
1
R/W
1-10
1=D3, 2=D4, 3=easy-Drive Actuator 0.62",
4=easy-Drive Actuator 0.75", 5 = easy-Drive Actuator
Stop-to-Stop, 6 = easy-Drive Actuator 0.50"
unit16
RESERVED
40069
unit16
RESERVED
40070
unit16
RESERVED
40071
unit16
RESERVED
40072
unit16
RESERVED
40073
-continued-