BA_EN_DS13
4.4 Switch point setting
1
2
Switch point setting
1.2 x 8
Fig. 10:
Switch point setting
1. Remove the plugs (1) and the seals (2) in the hood and/or open the bayonet
ring enclosure.
2. The required switch points can be set on the reference scale guide with a
screwdriver. The achievable accuracy is 5 %.
3. Replace the plug and/or the bayonet ring after completing the settings.
4.5 Function test
Remove both plugs in the hood for testing. Carry out the test for both mi-
croswitches. After the test, the switch points need to be reset.
Checking the switch points when the system is depressurized.
• No measurement is shown and the measurement display points to zero.
• Turn the switch point setting button toward the zero-point until the micro-
switch is activated.
• Check whether the signal is available on the terminals.
Test when the system is operational
• A measurement is shown.
• Turn the switch point setting button toward the measurement until the micro-
switch is activated.
• Check whether the signal is available on the terminals.
After the successful test, commission the device again otherwise contact our re-
pair department.