
position (maximum rate of inner + outer crown); push in and hold the dial until the flame has been lit (fig. 2.4).
The sparks produced by the electrode situated inside the relative burner will light the flame.
In the event that the local gas supply conditions makes it difficult to light the burner in position
, try again with the dial in position
.
2. Wait for about ten seconds after the gas burner has been lit before letting go the dial (safety device activation
delay).
3. Adjust the gas valve to the desired position.
If there is no mains electrical supply, the burners can be used with
no restriction. In that case, in order to light the burner, you must:
1. Bring a lighted match close to the burner (as per side
figure) and keep it in place until the burner has been
ignited.
2. Push and turn the dial in a counter-clockwise direction up
to the
position (maximum rate of inner + outer crown); push in
and hold the dial until the flame has been lit (fig. 2.4).
In the event that the local gas supply conditions makes it
difficult to light the burner in position
, try again with the dial in position
.
3. Wait for about ten seconds after the gas burner has been
lit before letting go the dial (safety device activation delay).
4. Adjust the gas valve to the desired position.
If the burner flame should go out for some reason, the safety valve will automatically stop the gas flow.
To re-light the burner, return the dial to the closed
OFF
position, wait for at least 1 minute and then repeat the lighting
procedure.
If your local gas supply makes it difficult to light the burner with the dial set to maximum, set the dial to minimum and
repeat the operation.
Updated: Thu, 11 Nov 2021 19:59:30 GMT
Powered by
7