4 | Commissioning
FISCHER Mess- und Regeltechnik GmbH
16 / 32
BA_EN_DE49_0
MA
ME
Input variable
Output / display [%]
100
0
0.0
100.0
Value pair 2
p-02
i-02
Illustration 10:
Table function
4.3.8 Password
The parameter
pass
serves to define a password.
A value between 0 and 999 can be selected for the password. The value 0 can-
cels the password function.
If a password has been issued, the unit configuration is protected by this pass-
word. You can use the key
û
to switch to the configuration mode, however as
soon as you select a parameter, a password request appears
-p-
. You can set
this with the arrow keys
þ
ÿ
and confirm with
û
. This unlocks the unit and it
can be configured again.
NOTICE
Forgotten password
If the password is forgotten, it can only be deleted again by the manufacturer.
4.3.9 Reset
The function
rst
allows all settings to be reset to default values. The default
value for this parameter is 0.
Enter the value 1 to carry out a RESET. As soon as the configuration mode is
quitted via the parameter
ESc
, a RESET is carried out and all parameters are
reset to the saved default values.
4.3.10 Parameter menu
After switching on the device, it will briefly indicate the software version number
and before entering the normal operating mode. By using the middle û key on
the membrane keypad you can access the parameter menu. The reading now
shows the text
ESc
. By using the right
þ
key, you can choose the parameters
from the following list one by one.