
4 | Commissioning
FISCHER Mess- und Regeltechnik GmbH
12 / 32
BA_EN_DE49_0
4 Commissioning
4.1 Generalities
WARNING
Operation in areas at risk of explosion
If operated in explosive areas, the electrical data of the unit and the valid local
regulations and guidelines for the installation and operation of electrical systems
in explosive areas must be observed (e.g. DIN EN 60079-14)
A prerequisite for commissioning is correct installation of all electrical supply
lines and the pressure lines. All connections are arranged so that there are no
mechanical forces acting on the device.
4.2 Control elements
Measured value display
Measuring unit
Tastatur
Measuring range overstepping
Illustration 8:
Display and keypad
The LCD display shows the current pressure value in normal mode. The unit is
shown to the right of the measured value.
It is operated via a 3-key film keypad
ÿ
Page down menu
Decrease value
û
Call up menu
Save value
OK
þ
Page up menu
Increase value
4.3 Parameters
After being activated, the device briefly displays the software version number
and carries out a display test. Then the transmitter goes into normal mode.
When setting the parameters, the display either shows the respective menu
item or the associated parameter value. The device continues to function whilst
the parameters are being set; the changes come into effect instantly.
Please note that the transmitter will switch to the operating mode again, if no
key is pressed for more than 1 minute.
Proceed as follows to set a parameter:
• Press the enter key
û
to switch to the menu.
ESc
will appear on the dis-
play.
• Use the arrow keys
þ
to select the first parameter.
• If a password has been entered,
-p-
appears in the display. Enter the pass-
word to unlock the menu.
• Use the arrow keys
ÿ
þ
to scroll through the menu.
• Press the enter key
û
to call up the parameter.
• Use the arrow keys
ÿ
þ
to set the required value.
• Press the enter key
û
to save the value.
Содержание DE49 # 0 series
Страница 29: ...FISCHER Mess und Regeltechnik GmbH Attachments 8 BA_EN_DE49_0 29 32 Illustration 15 CE_DE_DE49 0_Page_2...
Страница 31: ...FISCHER Mess und Regeltechnik GmbH Attachments 8 BA_EN_DE49_0 31 32 Illustration 17 IBExU09ATEX1164 2 _EN_Part2...
Страница 32: ...8 Attachments FISCHER Mess und Regeltechnik GmbH 32 32 BA_EN_DE49_0 Illustration 18 IBExU09ATEX1164 2 _EN_Part3...