General operation
Seite/Page 22 - Kaptitel/Chapter 2: General operation
10.5.17
2.7.2 Fischer Panda Art. No. 21.02.02.015P, 24 V-version
Fig. 2.7.2-1: Panel 21.02.02.047P with master-slave adapter 21.02.02.015P
With the Master-Slave-Adapter RE0706 two Generator Control Panels P6+ RE0703 can be connected to a Master-
Slave-Combination. In addition on each Generator Control Panel P6+ an Master-Slave-Adapter RE0706 is installed.
The Generator Control Panel P6+ is interconnected by the 14pole connecting terminals on the Master-Slave-
Adapters 1:1. The Master-Panel is hereby defined when the generator is connected to the main connector. Thus, the
main connector of the Slave-Panel should not be occupied (unconnected).
The solder jumpers on the Master-Panel have to be coded in the same manner as for a Master-Panel without a
Slave-Panel as in normal operation. The solder jumpers on the Slave-Panel are coded as for slave operation (please
see the appropriate adjustment pages for the Generator Control Panel P6+ RE0703).
The Master-Panel and Slave-Panel are identical, and only differs as a result of the coding. Both Master-Slave-
Panels are also identical.
2.7.3 Terminal connections:
X2: (14polig, 21 - 34) master Slave connection (1:1 wire)
X3: (2polig, 35 - 36) 35: Panel on signal of the Generator Control Panel P6+ RE0703
36: Error signal of the Generator Control Panel P6+ RE0703
The Panel-ON-Signal is active when the panel is switched on.
The error signal is so long active, as the panel recognizes an error, which must lead to switching the generator off.
The output voltage corresponds to the operating voltage of the Generator Control Panel P6+ less 0,7 V - 1,4 V. Each
output has a free wheeling diode which short circuits externals voltage supplies under 0 V and a decoupling diode
which decouples the circuitry from external power feeding.
2.7.4 Fuse:
A 0,8AT fuse must be installed on the Master-Panel.
01
02
01. Main terminals
02. Master-slave adapter 21.02.02.015P