11. General maintenance.
The following service table is for guidance only, as the frequency will depend on the
conditions of each installation.
ACTION
FREQUENCY
Cleaning the filters
According to the dehumidifier's
instructions.
Inspection of the wet air fan impeller (reactivation) Every 2000 hours of operation
Inspection of the dry air fan impeller (process)
Every 2000 hours of operation
Internal inspection (desiccant rotor surfaces,
tension belt, presence of foreign bodies, etc.)
Every 8900 hours of operation.
Desiccant rotor inspection
Every 1500 hours of operation.
Electrical connections check
Every 2 months
Heat recovery module inspection (plates)
Every 2000 hours of operation.
Belt inspection/replacement, if applicable
Every 2000 hours of operation.
Rotor seals inspection/replacement, if applicable
Every 2000 hours of operation.