Calculation of the flow using the differential suction pressure of the fan
Calculating the flow, having configured the control mode pressure, and whenever the fan
is a Plug-fan type, can be done with the following equation:
𝑄 = 𝑘 ∗ √
1.2
𝜌
∗ ∆𝑃
Where:
-
Q stands for the air flow in m
3
/h
-
𝜌
is the density of the air through the fan, in kg/m
3
-
∆𝑃
is the differential pressure in Pa measured between the suction
plenum of the fan and its inlet ring.
-
𝑘
is an intrinsic constant of each fan.
The
k
values for each DFRA model are the following:
DFRA
model
100
130
160
175
200 230 300
400
500
650
900
k value
95
121