FA147C Installation Instructions

3Ð2

Wiring Run Chart For Devices* Drawing Aux Power From The Control (12V+ & 12VÐ)

TOTAL CURRENT DRAWN BY ALL DEVICES CONNECTED TO A SINGLE WIRE RUN

 ÊÊ

Wire Size

 

50mA or less

100mA 

300mA

500mA

#22

Ê 500 ft (152m)

  250 ft (76m)

Ê80 ft (24m)

ÊÊÊ50 ft (15m)

#20

Ê 750 ft (228.6m)

  380 ft (116m)

130 ft (39.6m)

ÊÊÊ80 ft (24m)

#18

 1300 ft (396m)

  650 ft (198m)

220 ft (67m)

Ê130 ft (39.6m)

#16

 1500 ft (457m)

1000 ft (305m)

330 ft (100.5m)

Ê200 ft (70m)

*

 

Includes Keypads, RF Receivers, Expansion/ Relay Units, or the FA4285 Phone Module.

The length of all wire runs must not exceed 1500 feet (457m) when unshielded quad conductor
cable is used (750 feet if shielded cable is used). This restriction is due to the capacitive effect 

on

the data lines 

when quad cable is used.

 KEYPADS

BLACK

RED

GREEN

YELLOW

4

5

6

7

CONTROL
TERMINALS

KEYPAD CONNECTOR CABLE
             

¯

Figure 3–1.  Keypad Connections  To The Control Board

Mounting the Keypads

1.

Make sure keypads

 are set to non-addressable mode (address 31), which is the factory

default setting. Refer to the instructions provided with the keypad for address setting
procedure.

2.

Mount the keypads

 at a height that is convenient for the user. Refer to the instructions

provided with the keypad for mounting procedure.
You can either surface mount or flush mount keypads (using an appropriate Trim Ring Kit:
FA550TRK (except FA210KP, FA245KP). Refer to the mounting instructions and template
included with the keypad and/or trim ring kit for specific information.

Using a Supplementary Power Supply to Power Additional Keypads

The control provides 500mA for powering keypads (up to a maximum of 4) and other devices
from the auxiliary power output. The backup battery will supply power to these keypads in the
event that AC power is lost.

When the controlÕs auxiliary power load for all devices exceeds 500mA, you can power
additional keypads from a regulated, 12VDC power supply (e.g., 487-12  supplies 12V, 250mA;
488-12 supplies 12V, 500mA). Use a UL  Listed, battery-backed supply for UL installations.

The 487-12/488-12 power supplies have a backup battery which can power these keypads in the
event of AC power loss.

Keypads powered from supplies which do not have a backup battery 

will not function

 when AC

power is lost. Therefore, be sure to power at least one keypad from the Control's auxiliary power
output.

Содержание FA147C

Страница 1: ...K3211 3 98 INSTALLATION INSTRUCTIONS FA147C Security System...

Страница 2: ...alarm in the hallway outside may not wake up the sleeper if the door is closed Install a smoke detector inside bedrooms where electrical appliances such as portable heaters air conditioners or humidif...

Страница 3: ...n Characteristics For Zones 1 6 4 1 Wiring Burglary and Panic Devices to Zones 1 6 4 1 Wiring 4 Wire Smoke Combustion Detectors 4 1 Compatible 4 Wire Smoke Combustion Detectors 4 2 Programming Hard Wi...

Страница 4: ...me By Zone 7 10 Section 8 FA4285 Phone Module 8 1 Mounting the FA4285 Phone Module 8 1 General Information 8 1 Phone Module Wiring 8 2 Caller ID Units 8 2 Programming The Control For Phone Access 8 4...

Страница 5: ...Master Code 17 1 Changing the Master Code 17 1 User Codes 17 1 Duress Code 17 2 Keypad Functions 17 2 General Information 17 2 Arming Disarming Functions etc 17 3 Panic Keys 17 3 FA4285 Phone Module i...

Страница 6: ...Detector Connections 4 2 Figure 5 1 Wiring Connections 4219 and 4229 5 1 Figure 6 1 5881 and 5882 Wireless Receivers cover removed 6 3 Figure 7 1 4204 Connections To Control 7 2 Figure 7 2 4229 Conne...

Страница 7: ...ding Wireless zones adding an FA4285 Phone Module etc Without an understanding of the programming method for this system you will not be able to successfully perform the required programming Before an...

Страница 8: ...not observed could seriously affect the operation of the system or could cause damage to the system Please read each warning carefully This symbol also denotes warnings about physical harm to the ins...

Страница 9: ...ones up to 30 total wired and wireless zones Wired Expansion Supports up to 8 additional wired zones using a 4219 expansion module or 4229 expansion relay module Zones will have the following characte...

Страница 10: ...mmed for your system a pager will respond to certain conditions as they occur in your system and display code numbers on the pager indicating the type of condition that has occurred Quick Arm Feature...

Страница 11: ...Bell Supervision Red jumper on control board when cut will provide supervision of bell wiring when bell is wired with EOL resistor as indicated in the instructions Auxiliary Power Output Provides 12V...

Страница 12: ...FA147C Installation Instructions 1 4...

Страница 13: ...ge and or block RF transmissions from wireless transmitters Do not locate the cabinet in an area of high RF interference revealed by frequent or pro longed lighting of the LED in the receiver after it...

Страница 14: ...be used on the circuit board even when the RF receiver is mounted above it Installing the 4204 4219 or 4229 Module in the Cabinet See Figure 2 2 Any one of these units can be mounted in the cabinet wi...

Страница 15: ...ee Detail B in Fig 2 3 4 Insert the top of the control s board into the slot in the clips and position two long red clips at the lower edge of the board see Detail C 5 Swing this board into place and...

Страница 16: ...onnect Cord TERMINALS ON CONTROL EARTH GROUND PREMISES PHONES Handset Incoming Telco Line TIP RING BROWN TIP GRAY RING GREEN TIP RED RING RJ31X JACK PLUG DIRECT CONNECT CORD TIP RING GROUND INCOMING T...

Страница 17: ...til you are instructed to do so later in the manual Earth Ground Connections This product has been designed and laboratory tested to ensure its resistance to damage from generally expected levels of l...

Страница 18: ...FA147C Installation Instructions 2 6...

Страница 19: ...o The Keypads 1 Determine wire gauge by referring to the wiring length gauge chart below For devices Keypads RF Receivers Expansion Relay units etc connected to a single 4 wire run determine the curre...

Страница 20: ...address setting procedure 2 Mount the keypads at a height that is convenient for the user Refer to the instructions provided with the keypad for mounting procedure You can either surface mount or flus...

Отзывы: