ÊÊSection 2. Installing the Control

2Ð5

Installing The Back-Up Battery

1. Place the 12-volt back-up battery in the control cabinet. To calculate the correct battery size

for an installation, refer temporarily to ÒCalculating the Battery Size NeededÓ in the 

Final

Power Up

 section.

U

U

U

ULLLL

Use a 4AH battery or larger for  UL  installations.

2. Attach Red and Black wires on the battery connector cable to the control board as follows:

a.

Red to the positive (

+

) battery tab 

on the control board

 

 

(see Summary of Connections

Diagram for location, if necessary)

.

b.

Black to the negative (

Ð

) battery tab 

on the control board

 

.

Ê 

These wires may have already been connected to the battery tabs on the control board. If so,

disregard steps a. and b.

Do not attach the connector cable to the terminals on the battery until you are instructed to do
so later in the manual.

Earth Ground Connections

This product has been designed and laboratory-tested to ensure its resistance to damage from
generally expected levels of lightning and electrical discharge, and does not normally require
an earth ground. If an earth ground is desired for additional protection in areas of severe
electrical activity, 

terminal 21 

on the control board, or the cabinet, may be used as the ground

connection point. The following are examples of good earth grounds available at most
installations:

Metal Cold Water Pipe:

Use a non-corrosive metal strap (copper is recommended) firmly secured to the pipe to which
the ground lead is electrically connected and secured.

AC Power Outlet Ground:

Available from 3-prong, 120VAC, power outlets only. To test the integrity of the ground
terminal, use a three-wire circuit tester with neon lamp indicators, such as the  UL -Listed Ideal
Model 61Ð035, or equivalent, available at most electrical supply stores.

Содержание FA147C

Страница 1: ...K3211 3 98 INSTALLATION INSTRUCTIONS FA147C Security System...

Страница 2: ...alarm in the hallway outside may not wake up the sleeper if the door is closed Install a smoke detector inside bedrooms where electrical appliances such as portable heaters air conditioners or humidif...

Страница 3: ...n Characteristics For Zones 1 6 4 1 Wiring Burglary and Panic Devices to Zones 1 6 4 1 Wiring 4 Wire Smoke Combustion Detectors 4 1 Compatible 4 Wire Smoke Combustion Detectors 4 2 Programming Hard Wi...

Страница 4: ...me By Zone 7 10 Section 8 FA4285 Phone Module 8 1 Mounting the FA4285 Phone Module 8 1 General Information 8 1 Phone Module Wiring 8 2 Caller ID Units 8 2 Programming The Control For Phone Access 8 4...

Страница 5: ...Master Code 17 1 Changing the Master Code 17 1 User Codes 17 1 Duress Code 17 2 Keypad Functions 17 2 General Information 17 2 Arming Disarming Functions etc 17 3 Panic Keys 17 3 FA4285 Phone Module i...

Страница 6: ...Detector Connections 4 2 Figure 5 1 Wiring Connections 4219 and 4229 5 1 Figure 6 1 5881 and 5882 Wireless Receivers cover removed 6 3 Figure 7 1 4204 Connections To Control 7 2 Figure 7 2 4229 Conne...

Страница 7: ...ding Wireless zones adding an FA4285 Phone Module etc Without an understanding of the programming method for this system you will not be able to successfully perform the required programming Before an...

Страница 8: ...not observed could seriously affect the operation of the system or could cause damage to the system Please read each warning carefully This symbol also denotes warnings about physical harm to the ins...

Страница 9: ...ones up to 30 total wired and wireless zones Wired Expansion Supports up to 8 additional wired zones using a 4219 expansion module or 4229 expansion relay module Zones will have the following characte...

Страница 10: ...mmed for your system a pager will respond to certain conditions as they occur in your system and display code numbers on the pager indicating the type of condition that has occurred Quick Arm Feature...

Страница 11: ...Bell Supervision Red jumper on control board when cut will provide supervision of bell wiring when bell is wired with EOL resistor as indicated in the instructions Auxiliary Power Output Provides 12V...

Страница 12: ...FA147C Installation Instructions 1 4...

Страница 13: ...ge and or block RF transmissions from wireless transmitters Do not locate the cabinet in an area of high RF interference revealed by frequent or pro longed lighting of the LED in the receiver after it...

Страница 14: ...be used on the circuit board even when the RF receiver is mounted above it Installing the 4204 4219 or 4229 Module in the Cabinet See Figure 2 2 Any one of these units can be mounted in the cabinet wi...

Страница 15: ...ee Detail B in Fig 2 3 4 Insert the top of the control s board into the slot in the clips and position two long red clips at the lower edge of the board see Detail C 5 Swing this board into place and...

Страница 16: ...onnect Cord TERMINALS ON CONTROL EARTH GROUND PREMISES PHONES Handset Incoming Telco Line TIP RING BROWN TIP GRAY RING GREEN TIP RED RING RJ31X JACK PLUG DIRECT CONNECT CORD TIP RING GROUND INCOMING T...

Страница 17: ...til you are instructed to do so later in the manual Earth Ground Connections This product has been designed and laboratory tested to ensure its resistance to damage from generally expected levels of l...

Страница 18: ...FA147C Installation Instructions 2 6...

Страница 19: ...o The Keypads 1 Determine wire gauge by referring to the wiring length gauge chart below For devices Keypads RF Receivers Expansion Relay units etc connected to a single 4 wire run determine the curre...

Страница 20: ...address setting procedure 2 Mount the keypads at a height that is convenient for the user Refer to the instructions provided with the keypad for mounting procedure You can either surface mount or flus...

Отзывы: