Firman The Ultimate 4550 Скачать руководство пользователя страница 24

English                                                                                                                             

Page 21

                    

6XSSRUWVXSSRUW#DUFDXJXVWDFRP

4. Fully open the LPG

 

cylinder knob

.

5. Turn the fuel selector switch to “

LPG

” position.

3. Connect the regulator to both LPG cylinder and

generator.

NOTE:

 When the fuel selector switch is turned 

to  the  “

LPG”

  position,  the  indicator  light  will 

become 

RED

 up to 

4 minutes

(before goes off).

Starting  the  engine  successfully  during  these 

4 minutes

 will turn the indicator light 

GREEN

.

6. Disconnect all electrical loads from the 

    generator. Never start or stop the generator 

    with electrical devices plugged in or turned 

    on.

7. Move choke lever located on engine to “

START

” 

position.

NOTE

Do

 

not

 

place

 

the

 

LPG

 

cylinder

 

in

 

the

 

path

 

of

 

muffler

 

outlet

.

9.Move the choke lever to the “

RUN

” position.

11. Allow generator to run at no load for few

minutes upon each initial start-up to permit 

engine and generator to stablize.

8. 

PULL TO-PRIME:

-

Pull the starter cord 1-2 times. Pull slowly until 

resistance if felt and then pull rapidly.

10. 

PULL TO RUN:

-

-

Pull the starter cord slowly until resistance if felt 

and pull rapidly to run the unit. 

If the engine fails to start in 1-2 pulls with choke in the 

RUN

” position, then move choke lever to “

START

” 

position and repeat the “

PULL-TO-PRIME

” step.

REMINDER: 

MUST HAVE 

SOLID RED INDICATOR 

LIGHT

 TO BE ABLE TO START THE GENERATOR. 

THE GENERATOR CANNOT BE STARTED DURING 

BATTERY  POWER  SAVING  MODE

  UNLESS 

1-2 Times

Page 22

Содержание The Ultimate 4550

Страница 1: ...carefully before operating equipment Ensure engine is stopped and level before performing any maintenance or service IMPORTANT Serial Number MODEL NUMBER R P03615 Rev Level 00 DO NOT RETURN TO STORE C...

Страница 2: ......

Страница 3: ...ces tools and motor loads and is not intended for any other purpose It is important that you read and understand these instructions thoroughly before attempting to start or operate this equipment Save...

Страница 4: ...duct downwind and point the engine exhaust away from occupied spaces If you start to feel sick dizzy or weak while using this product shut it off and get to fresh air RIGHT AWAY See a doctor You may h...

Страница 5: ...de and downwind far away from windows doors and vents Direct exhaust away from occupied spaces INCORRECT USAGE Do not operate in any of the following locations Near any door window or vent Garage Base...

Страница 6: ...and and arm toward engine faster than you can let go which could cause broken bones fractures bruises or sprains resulting in serious injury When starting engine pull cord slowly until resistance is f...

Страница 7: ...loads OFF and disconnect from generator before stopping generator DO NOT use generator with electrical cords which are worn frayed bare or otherwise damaged DO NOT operate generator in the rain or we...

Страница 8: ...ppliances NEVER use this product to power medical devices or medical appliances Inform your electricity provider immediately if you or anyone in your household depends on electrical equipment to live...

Страница 9: ...es to remove the attached engine support brackets red under the engine Engine Support Brackets red color Remove these 4 nuts bolts as indicated English Customer Service 1 844 FIRMAN1 2 If included rem...

Страница 10: ...embly prior to usage If problem arise when assembling the generator call 1 844 347 6261 H K 1 Before adding wheels tip the generator on its side 2 Slide the axle pin A through the wheel B 3 Slide the...

Страница 11: ...ed boot is securely tightened to the positive battery post Make sure boot is over battery post 2 Remove bolt M5X10 and M5 nut from black cable ring 3 Remove vinyl cap from the negative battery post Lo...

Страница 12: ...Cap 12 Easy Oil Drain 17 Remote Holder Includes Remote English Customer Service 1 844 FIRMAN1 We are always working to improve our products Therefore the enclosed product may differ slightly from the...

Страница 13: ...pt to start When the engine starts release the switch to the RUN l position 1 Control Panel A Digital display B AC voltage indicator C Frequency indicator D Hour indicator E Low oil indicator F Select...

Страница 14: ...er Service 1 844 FIRMAN1 16 Your remote control is already programmed in factory for your convenience You might need programming when using new remote control 17 Tethered Adapter TT 30P 30A 120V to L5...

Страница 15: ...P 5 Push and release the START button The indicator light will flash once to program the remote START 6 Push and hold the program button approximately 3 seconds until the indicator light turn off The...

Страница 16: ...lockwise Facing P T O Float Brushed Polyurethane Type Yes 4550 FIRMAN Rated Fequency 60Hz Oil Type See Add Engine Oil Section Grounding System AN IMPORTANT MESSAGE ABOUT TEMPERATURE When operated abov...

Страница 17: ...warning device or stop the engine If generator shuts off and the oil level is within specifications check to see if generator is sitting at an angle that forces oil to shift Place on an even surface t...

Страница 18: ...cap remove cap 2 Slowly add unleaded fuel to fuel tank Be careful not to fill above the red fuel level indicator This allows adequate space for fuel expansion 3 Install fuel cap and let any spilled fu...

Страница 19: ...nder so the connection between the valve and the regulator won t cause bends or kinks in the hose Spray a soapy water solution one part liquid detergent and one part water to check all connections for...

Страница 20: ...result due to the increased enrichment of the air fuel ratio Other high altitude issues can include hard starting increased fuel consumption and spark plug fouling To alleviate high altitude issues ot...

Страница 21: ...ound fault circuit interrupter GFCI in any damp or highly conductive area such as metal decking or steel work DO NOT touch bare wires or receptacles DO NOT use generator with electrical cords which ar...

Страница 22: ...Keep exhaust pipe clear of foreign objects Keep generator away from open flame Keep generator on a stable and level surface WARNING Surge Protection Voltage fluctuation may impair the proper functioni...

Страница 23: ...t no load for few minutes upon each initial start up to permit engine and generator to stablize StartingtheGenerator RecoilStart LPG 1 Before starting the generator check for loose or missing parts an...

Страница 24: ...ngine to START position NOTE Do not place the LPG cylinder in the path of muffler outlet 9 Move the choke lever to the RUN position 11 Allow generator to run at no load for few minutes upon each initi...

Страница 25: ...switch is turned to the GAS position the indicator light will become RED up to 4 minutes before goes off Starting the engine successfully during these 4 minutes will turn the indicator light GREEN 5 D...

Страница 26: ...ANNOT BE STARTED DURING BATTERY POWER SAVING MODE UNLESS THE FUEL SELECTOR SWITCH IS TURNED TO THE OFF POSITION AND THEN TURNED BACK TO THE LPG POSITION 9 Move the choke lever to the RUN position 4 Fu...

Страница 27: ...nerator when using one or more receptacles Also do not exceed the amperage rating of any one receptacle Do not apply heavy electrical load during break in period the first five hours of operations wor...

Страница 28: ...TED DURING BATTERY POWER SAVING MODE UNLESS THE FUEL SELECTOR SWITCH IS TURNED TO THE OFF POSITION AND THEN TURNED BACK TO THE GAS OR LPG POSITION Unwanted Shutdown The generator cannot be started dur...

Страница 29: ...cient fuel flow to the engine This is not an indication of a problem with the generator but only a problem with the flow of gas from the LPG cylinder If generator performance seems to be deteriorating...

Страница 30: ...endations Regular maintenance will improve the performance and extend the life of the generator See any authorized dealer for service The generator s warranty does not cover items that have been subje...

Страница 31: ...o cause skin cancer in certain laboratory animals Thoroughly wash exposed areas with soap and water a Drain oil by removing the drain plug and the oil filler cap while the engine is warm Change engine...

Страница 32: ...replacement parts Exhaust heat gases could ignite combustibles structures or damage fuel tank causing a fire resulting in death or serious injury and or property Contact with muffler area could cause...

Страница 33: ...and attach with the screws Spark arrester screen Flange Screw Battery Replacement 1 Remove the spark plug wire from spark plug 2 Remove the nut and bolt from the negative and positive posts 3 Loosen...

Страница 34: ...il it stops from lack of gasoline This will dry out all remaining gasoline in tank fuel lines and carburetor 5 Turn fuel selector switch to OFF position Fully close the LPG cylinder knob if it is open...

Страница 35: ...tic battery charging circuit The battery will receive charging voltage when the engine is running The battery will maintain a proper charge if the unit is used on a regular basis about once every two...

Страница 36: ...er level Place generator on level surface 2 Fill fuel tank with gasoline 3 Replace spark plug 4 Connect wire to spark plug 5 Clean or replace the fuel filter 6 Charge or replace battery 7 Adjust the c...

Страница 37: ...PARTS DIAGRAM AND PART LIST P03615 PARTS DIAGRAM English Page 35 Customer Service 1 844 FIRMAN1 136...

Страница 38: ...208cc ENGINE PARTS DIAGRAM English Page 36 Customer Service 1 844 FIRMAN1...

Страница 39: ...d Cover Cap Ground Wire 2 Terminal Block Bolt washer Assemblies Carbon Brush Holder Carbon Brush Assembly Air Cleaner Bracket Flange Bolt M6 8 Muffler Fixed Plate A small Muffler Fixed Plate B big Flg...

Страница 40: ...ning 1 2 1 8 1 2 1 1 1 1 1 1 1 2 6 1 2 1 1 1 1 1 2 1 1 1 7 4 2 2 1 2 1 1 1 2 2 2 1 2 1 1 1 2 2 2 1 2 1 2 1 1 1 1 2 3 1 1 4 1 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85...

Страница 41: ...9 1 i V 7i iV i i V V i V i i V i V v i i iVi i i i Vi v i v V i i i i V v i iviV i i i L 7 i i Li i i i v i V i 7 9 7 i i U U i Failures due to improper maintenance or oil levels i v i V v L i i i v...

Страница 42: ...gine is Designed built and equipped so as to conform with all applicable regulations adopted by the Air Resources Board and US EPA and Free from defects in materials and workmanship that cause the fai...

Страница 43: ...ust manifold Catalytic converter Muffler gasket pulse valve 4 Air induction system including Intake pipe manifold Air cleaner 5 Crankcase breather assembly including Breather connection tube 6 Fuel ta...

Страница 44: ...P N 336745464 Rev 02 Firman Power Equipment Inc Peoria AZ 85381 www firmanpowerequipment com 8716 West Ludlow Dr Suite 6...

Отзывы: