background image

1

DESCRIPTION

The FIREYE YZ300 (YZ320) Interlock Annunciator Module provides increased interlock 
supervision capability of the BurnerLogix

 

System. The Interlock Annunciator Module connects 

to any YB110 (YB230) or ZB110 (ZB230) BurnerLogix chassis/amplifier by means of a cable, (
P/N ED580-2, ED580-4, ED580-8).

By wiring any of twenty interlock switches into the Interlock Annunciator Module, the BurnerLogix
display automatically acts as a “first-out” annunciator for these interlocks. In addition, a fuel selec-
tion circuit providing full annunciation even if two fuels are fired simultaneously is standard. The
YZ300 (YZ320) is shipped with default messages associated with each set of terminals. The user has
the ability to modify these lockout messages in one of two ways:

1.

Use the BLV512 or BLL510 display module to select a lockout alarm message for the individual
terminals of the YZ300 (YZ320) from a library of available messages. Refer to Bulletins 
BL-1001 and/or BLZ-1001 for information regarding the operation of these controls.

2.

Program a customized message (up to 40 characters in length) for the individual terminals of the
YZ300 (YZ320) using a compatible PC with the Windows based YZ300P Programming soft-
ware, available from Fireye and the appropriate hardware. Note: The YZ300 (YZ320) Interlock
Annunciator does not need to be connected to a BurnerLogix system to be custom programmed.

Note: 

Proper operation of the YZ300 (YZ320) requires a BurnerLogix YB110 (YB230) with an 

Engineering code of 3 or later or any ZB110 (ZB230) chassis/amplifier (Engineering codes 
are found after the date code, e.g. 0636-03).

The Interlock Annunciator Module does not interfere with the normal operation of the BurnerLogix
System. It expands the message and diagnostic capability.

The wiring bases for the YZ300 (YZ320) measure 4 in. wide by 7 in. tall, consuming a minimum
amount of cabinet space. The wiring bases contain a 24 position terminal block, each position clearly
numbered and each terminal utilizing a clamping mechanism to assure a good mechanical connec-
tion. 

The YZ300 (YZ320) Interlock Annunciator module provides operational information and reduces
troubleshooting time and expense. It expands the standard display messages of the BurnerLogix to
identify the specific limit in the operating control circuit (L1-3) or running interlock circuit (3-P)
which caused the burner shutdown or lockout. For a detailed description of the BurnerLogix System,
see Bulletins BL-1001 or BLZ-1001.

FIREYE

®

YZ300 and YZ320

INTERLOCK

ANNUNCIATOR

For use with the Fireye

BurnerLogix™ Control

YZEM-3001

June 2, 2017

APPROVED

Содержание YZ300

Страница 1: ...rogramming soft ware available from Fireye and the appropriate hardware Note The YZ300 YZ320 Interlock Annunciator does not need to be connected to a BurnerLogix system to be custom programmed Note Pr...

Страница 2: ...C EMC Directive 89 336 EEC GASTEC 0063BT1754 EN298 2003 EN230 2005 Table 1 Agency Approvals SPECIFICATIONS Supply Voltage YZ300 120VAC 10 15 50 60 Hz YZ320 230VAC 10 15 50 60 Hz Power Consumption 10 V...

Страница 3: ...LOCKOUT 3 P INTLK OPEN to one which will individually identify the sixteen 16 interlocks now being monitored by the YZ300 YZ320 such as LOCKOUT LOW OIL TEM PERATURE or the appropriate modified messag...

Страница 4: ...the BurnerLogix control to respond with the proper message Interlock contacts that temporarily open for shorter time periods will be ignored Refer to Figure 2 on page 8 for DEFAULT MESSAGES SPECIAL NO...

Страница 5: ...owered and gas is an active fuel blinks if any gas interlock is open NON RECYCLING illuminates steady when all interlocks between terminals 54 and P are closed and powered blinks if any interlock is o...

Страница 6: ...et 1000 meters for RS 485 A good ground system should be provided to minimize the effects of AC quality problems A prop erly designed ground system meeting all the safety requirements will ensure that...

Страница 7: ...on the underside of the BurnerLogix control Plug end of ED580 cable with ferrite core into EXP port of the BurnerLogix control Plug the other end of the ED580 cable into the EXP port located on the u...

Страница 8: ...wn will be undisturbed when the YZ300 YZ320 is installed Remove all power from the BurnerLogix control and the YZ300 YZ320 before wiring Note Terminals 44 45 49 50 and 53 54 are internally connected F...

Страница 9: ...es associated with the above terminals can be modified via either the BLL510 or BLV512 displays The selection of available messages are dependent on each group For example the message Low Oil Pressure...

Страница 10: ...ning Windows A copy of YZ300P software provided by Fireye An RS232 to RS485 converter serial port required P N EC485 or IC485 includes necessary power supply or USB to RS485 converter P N UC485 An ED5...

Страница 11: ...be powered and if not connected to the BurnerLogix the default address is set to 1 and the baud rate is 9600 N 8 1 RUNNING THE YZ300P SOFTWARE 1 Run the YZ300P software on the PC After the introductor...

Страница 12: ...ted messages will not be displayed on the YZ300P Write the YZ300P will upload or write all messages to the YZ300 YZ320 If the message displayed on the YZ300P screen is a default message then no writin...

Страница 13: ...alled CUSTOMIZING OR ERASING A MESSAGE To customize or erase a message on the YZ300P screen click on the particular message and the fol lowing dialog box will appear The current message pertaining to...

Страница 14: ...defective in material or workmanship or which otherwise fails to conform to the description of the prod uct on the face of its sales order THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES AND FIREYE...

Отзывы: