YZ300 (YZ320) MESSAGE SELECT

The sub-menu "YZEM MSG SELECT" will allow the user to modify the recycle and non-recycle
messages associated with the operation of the YZ300 (YZ320) Interlock Annunciator Module and
BurnerLogix. The use of the default messages requires the system to be wired as shown in the wiring
diagram. For example, the low water cutoff had to be wired between terminals 43 and 44 of the
YZ300 (YZ320). The YZEM MSG SELECT option now allows the user to select from a library of
messages and program each interlock terminal as required. The messages associated with the YZ300
(YZ320) are divided into four (4) groups: 

Recycle, Non-recycle, Gas Select, and Oil Select.

The 

Recycl

e group pertains to the limits that are connected between terminals L1 and 3 of the Burn-

erLogix. These are terminals L1-40, 40-41, 41-42, and 42-3.

The 

Non-Recycle

 group pertains to the limits that are connected between terminals 3 and P of the

BurnerLogix. These are terminals 3-43, 43-44, 54-55, 55-56, 56-57, 57-58, 58-59, 59-60 and 60-P.

The 

Gas Select

 group pertains to the terminals associated with the gas interlocks of the YZ300

(YZ320). These are terminals 50-51, 51-52, and 52-53.

The 

Oil Select

 group pertains to the terminals associated with the oil interlocks of the YZ300

(YZ320). These are terminals 45-46, 46-47, 47-48, and 48-49.

The lockout messages associated with the above terminals can be modified via either the BLL510 or
BLV512 displays.

The selection of available messages are dependent on each group. For example, the message "Low
Oil Pressure" is a selection only for the Oil Select group. The default message for a particular inter-
lock is the standard message for those terminals. For example, the default message for terminals 40-
41 is "L1-3 AUX #1 OPEN."

TO MODIFY THE YZ300 (YZ320) MESSAGES

All four keys: NEXT, BACK, MODE, and RESET/MDFY are used to used to enter or exit the sub-
menu associated with the YZ300 (YZ320) messages. The NEXT or BACK keys are used to scroll
through the various terminals and selectable messages. The RESET/MDFY key is used to modify
and save a new message for each of the YZ300 (YZ320) Interlock Annunciator terminals.

To modify the YZ300 (YZ320) messages: 

Press the NEXT or BACK key until the BLL510 or BLV512 displays:

YZEM MSG SELECT>

Press the MODE key to enter the sub-menu and the screen displays:

TRM #40-41

MDFY

L1-3 AUX#1 OPEN 

or previously selected message.

Press the NEXT key and the screen displays:

TRM #41-42

MDFY

L1-3 AUX#2 OPEN 

or previously selected message.

To change the message, press and hold the RESET/MDFY key for one (1) second. When the
RESET/MDFY key is released, the screen displays:

TRM #41-42

SAVE

L1-3 AUX#2 OPEN

Press the NEXT or BACK key to display the available messages for the particular group being mod-
ified. See attached List of available messages for each group.

Library messages cannot override custom programmed messages.

Содержание YZ300

Страница 1: ...rogramming soft ware available from Fireye and the appropriate hardware Note The YZ300 YZ320 Interlock Annunciator does not need to be connected to a BurnerLogix system to be custom programmed Note Pr...

Страница 2: ...C EMC Directive 89 336 EEC GASTEC 0063BT1754 EN298 2003 EN230 2005 Table 1 Agency Approvals SPECIFICATIONS Supply Voltage YZ300 120VAC 10 15 50 60 Hz YZ320 230VAC 10 15 50 60 Hz Power Consumption 10 V...

Страница 3: ...LOCKOUT 3 P INTLK OPEN to one which will individually identify the sixteen 16 interlocks now being monitored by the YZ300 YZ320 such as LOCKOUT LOW OIL TEM PERATURE or the appropriate modified messag...

Страница 4: ...the BurnerLogix control to respond with the proper message Interlock contacts that temporarily open for shorter time periods will be ignored Refer to Figure 2 on page 8 for DEFAULT MESSAGES SPECIAL NO...

Страница 5: ...owered and gas is an active fuel blinks if any gas interlock is open NON RECYCLING illuminates steady when all interlocks between terminals 54 and P are closed and powered blinks if any interlock is o...

Страница 6: ...et 1000 meters for RS 485 A good ground system should be provided to minimize the effects of AC quality problems A prop erly designed ground system meeting all the safety requirements will ensure that...

Страница 7: ...on the underside of the BurnerLogix control Plug end of ED580 cable with ferrite core into EXP port of the BurnerLogix control Plug the other end of the ED580 cable into the EXP port located on the u...

Страница 8: ...wn will be undisturbed when the YZ300 YZ320 is installed Remove all power from the BurnerLogix control and the YZ300 YZ320 before wiring Note Terminals 44 45 49 50 and 53 54 are internally connected F...

Страница 9: ...es associated with the above terminals can be modified via either the BLL510 or BLV512 displays The selection of available messages are dependent on each group For example the message Low Oil Pressure...

Страница 10: ...ning Windows A copy of YZ300P software provided by Fireye An RS232 to RS485 converter serial port required P N EC485 or IC485 includes necessary power supply or USB to RS485 converter P N UC485 An ED5...

Страница 11: ...be powered and if not connected to the BurnerLogix the default address is set to 1 and the baud rate is 9600 N 8 1 RUNNING THE YZ300P SOFTWARE 1 Run the YZ300P software on the PC After the introductor...

Страница 12: ...ted messages will not be displayed on the YZ300P Write the YZ300P will upload or write all messages to the YZ300 YZ320 If the message displayed on the YZ300P screen is a default message then no writin...

Страница 13: ...alled CUSTOMIZING OR ERASING A MESSAGE To customize or erase a message on the YZ300P screen click on the particular message and the fol lowing dialog box will appear The current message pertaining to...

Страница 14: ...defective in material or workmanship or which otherwise fails to conform to the description of the prod uct on the face of its sales order THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES AND FIREYE...

Отзывы: