Fireye PPC6000 Series Скачать руководство пользователя страница 22

  

22 

 

Stage
no.

Stage name 

Description

15.

Moving to low fire 

Once the AUTO signal is received the fuel and air motors are moved 
from their ignition positions to their low fire positions. These positions 
may or may not be the same as the ignition positions. The ‘ignition 
prove’ terminal PE7 (low-fire-switch) is switched off. 

If the fuel/profile select input is removed (PE9, 10, 11 or 12), the 
control will immediately move to status 1. 

Once the drives have reached their low fire positions, and an AUTO 
signal is received (PA10 - PA11), the control will advance to status 
16.

IF Option 23.0 (warming limit) is enabled, drive will remain at low fire 
until time set by Option 23.0 expires. 

NOTE : terminal PE7 will always be OFF during status 15.

16.

Modulation

 (EK33) 

Once the fuel and air motors reach their low fire positions, they are 
modulated according to the demand placed on the burner. 

In this burner status the ‘high-fire-switch’ and ‘low-fire-switch’ outputs 
(PE8 & PE7) will come on at high and low fire respectively and may 
be used for indication purposes. 

If a ‘HIGH’ input is provided by closing PA9 – PA11, this control will 
move to status 17. 

If the ‘AUTO’ input is removed by opening PA10 – PA11, this control 
will modulate down to low fire then jump to status 15. Note : Terminal 
PE7 will not be energised in this case. This may be used to provide a 
low fire post purge, or a low fire hold function. 

If the fuel/profile select input is removed (PE9, 10, 11 or 12), the 
control will immediately move to status 1. 

If this control wishes to turn the burner off (there is no call for heat, for 
example), it will open the ‘controlled shutdown’ relay, removing power 
from PE3. It will remain in modulation status however, until one of the 
conditions above is met.

17.

Move to post-
purge

The selected motor(s) are moved to their purge positions all others 
are moved to their closed positions. When the drives have all 
stopped, the control will move to status 18.

18.

Post-purge

The controller confirms all required drives are at their purge positions, 
and gives a ‘purge proved’ signal by providing (line voltage) to 
terminal PE8 (high-fire-switch). 

The control will remain in this status until the burner controller signals 
the end of pre-purge by breaking PA9 – PA11 (‘HIGH’ input), or the 
fuel/profile select input is removed (PE9, 10, 11 or 12). In either case, 
the control will immediately move to status 1.

Содержание PPC6000 Series

Страница 1: ...__________________________________2 3 Password _______________________________________________________2 4 Adjusting Cut IN and Cut OUT_____________________________________3 5 Manual Modulation _______...

Страница 2: ...value and press the ENTER COM key 3 Password The only password an operator should require is the site Passcode This can be set as a number from 0 999 The factory default number is 154 The site Passcod...

Страница 3: ...alue Meaning 0 No limits The burner will run until another method is used to switch it off 1 Absolute limit The values entered in option parameters 21 6 22 6 and 21 7 22 7 are the actual limit values...

Страница 4: ...own on the display This function can be disabled via option parameter 1 1 To do so requires the suppliers highest passcode 6 Resetting the Control To reset the Nexus the MUTE RESET key will have to be...

Страница 5: ...free to modulate 1 Measured value below warming limit burner held at low fire if the control is in auto or sequencing mode EK18 Boiler status 0 Burner will not fire because the temperature pressure me...

Страница 6: ...essage since power up This should be zero unless there has been a problem EK26 Commission status Current commissioning mode where 0 Normal run mode 1 Adjust ratio mode 2 Commission ratio mode EK27 Com...

Страница 7: ...nearest to the current modulation position EK37 Voltage reference error V The error between the measured voltage reference and the calibrated value 0 12 is the limit The displayed value shows volts NO...

Страница 8: ...ut or trim not selected via serial comms 4 O2 setpoints or flow values incorrect 8 Option 30 6 not 0 16 Not modulating 32 In commission mode 64 Probe faulty see EK45 EK47 Oxygen setpoint Current oxyge...

Страница 9: ...al Output 7 ON Daughterboard PZ15 PZ16 LOW VOLTAGE AND CURRENT ONLY 128 Digital Output 8 ON Daughterboard PZ17 PZ17 LOW VOLTAGE AND CURRENT ONLY EK61 Analog Input 1 Main Unit Terminal PB9 also boiler...

Страница 10: ...task time The current longest internal software task time This is provided for manufacturers diagnostics only and may be removed in future versions EK76 Longest task number The current longest interna...

Страница 11: ...xed by a letter This letter describes the status of the fault F This means that a fault e g PSU calibration fault has occurred and is still present The fault may be internal or external to the unit L...

Страница 12: ...at least four setpoints commissioned x Use commission ratio mode to enter more setpoints Subset fuel code F19 Circuit board voltage reference fault The circuit board has an incorrect on board referen...

Страница 13: ...than five degrees 3 During pre purge ignition or post purge when a drive moves from its setpoint 4 During modulation when a drive is not at its correct setpoint as defined by the commissioned fuel ai...

Страница 14: ...to the control x This could be due to high levels of electrical interference getting into the product Check all cables are correctly screened and screens are terminated correctly Ensure the mains supp...

Страница 15: ...5 and re commission or restore with option parameter 45 2 x This could be due to high levels of electrical interference getting into the product Check all cables are correctly screened and screens are...

Страница 16: ...en level exceeded 15 0 during auto trim commissioning The burner is shutdown Subset Last auto trim commission setpoint 32 if adding air L58 Flue temperature low alarm value exceeded The measured flue...

Страница 17: ...he engineer to ensure the new servo is mechanically fixed the same way as the original one Subset Invalid profile 100 101 to 104 3 The selected profile has been uploaded from a PC but has not been ver...

Страница 18: ...st steam boilers When using only a proportional control the system rarely achieves set point as the burner firing rate is lowered as the pressure comes up At some point the input meets the actual dema...

Страница 19: ...4 for set point 1 PID1 and 22 2 22 3 and 22 4 for set point 2 PID2 These values are adjustable using the Site Passcode 154 11 The Startup Shutdown Stages The startup shutdown stages are as follows Sta...

Страница 20: ...The fuel and air motors are moved down until they are stopped by the closed position micro switches in the servos The final positions are compared with the closed positions stored in memory and must...

Страница 21: ...fuel profile select input is removed PE9 10 11 or 12 the control will immediately move to status 1 10 Ignition The controller confirms all required drives are at their ignition positions and gives an...

Страница 22: ...sing PA9 PA11 this control will move to status 17 If the AUTO input is removed by opening PA10 PA11 this control will modulate down to low fire then jump to status 15 Note Terminal PE7 will not be ene...

Страница 23: ...23...

Страница 24: ...ch is found defective in material or workmanship or which otherwise fails to conform to the description of the product on the face of its sales order THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES A...

Отзывы: