9
No.
Name
Description
EK59
Digital (relay) outputs on.
Represents which drives are currently at their
setpoints, where:
0 – All drives are at their setpoints and are not
moving.
Non- zero – One or more drives are not at their
setpoint.
EK60
Spare
The combination of digital outputs currently
switched on.
+1 : Digital Output 1 ON. Display, PR6(COM),
PR7(NO), PR8(NC). Low voltage or line voltage.
+2 : Digital Output 2 ON. Display, PR6(COM),
PR4(NO), PR5(NC). Low voltage or line voltage.
+4 : Digital Output 3 ON. Display, PR1(COM),
PR2(NO), PR3(NC). Low voltage or line voltage.
+8 : Digital Output 4 ON. Main Unit, PE4 (line
voltage out).
+16 : Digital Output 5 ON. Not implemented.
+32 : Digital Output 6 ON. Not implemented.
+64 : Digital Output 7 ON. Daughterboard, PZ15
– PZ16. LOW VOLTAGE AND CURRENT
ONLY.
+128 : Digital Output 8 ON. Daughterboard,
PZ17 – PZ17. LOW VOLTAGE AND CURRENT
ONLY.
EK61
Analog Input 1.
Main Unit Terminal PB9 (also boiler
measured value).
The raw ADC counts from analog input 1.
0 to 1023 for 0 to 5.00 volts.
EK62
Analog Input 2.
Main Unit Terminal PA12 (also remote
setpoint).
The raw ADC counts from analog input 2.
0 to 1023 for 0 to 5.00 volts.
EK67
Analog input 7.
Daughterboard terminal PZ12(-)
PZ13(+). Also VFD1.
The raw ADC counts from analog input 7.
0 to 1023 for 0 to 5.00 volts.
EK68
Analog input 8.
Daughterboard terminal PZ13(-)
PZ14(+). Also VFD2.
The raw ADC counts from analog input 8.
0 to 1023 for 0 to 5.00 volts.
EK69
Daughter board Frequency input 1
(PZ7). 0 to 12 volts.
Gives the measured frequency in Hz on this
input. If the input is not changing, this value will
be 0 for OFF (open circuit) and 1 for ON.