DESCRIPTION

The MBCE-110/230UV modules provide visual indication and electrical outputs that 
signal the user regarding flame presence in a combustion chamber. The module uses 
Fireye UV scanners to sense flame presence independently or as components in a 
burner management system. Many operational characteristics are provided including:

 

CE certified 

 

Self-contained: 110 VAC, 50/60 Hz: MBCE-110UV-1, MBCE-110UV-2

MBCE-110UV-3, MBCE-110UV-4
230 VAC, 50/60 Hz: MBCE-230UV-1, MBCE-230UV-3

 

UV scanner compatible*

 

Flame ON/OFF LED indicator

 

4-20mA output permits direct reading of flame signal strength

 

Uses CE certified 11-pin relay base 

 

Panel surface or DIN-rail mounting 

 

Flame pull-in threshold adjustment

The module provides a cost effective method of monitoring flames  using UV sensing. 

The MBCE-UV is intended for non-permanent operation (burner must be recycled at 
least once every 24 hours). The MBCE-UV is ideally suited for flame detection in nat-
ural gas applications; however, it can be used for flame detection in propane and light 
fuel oil applications. 

Check with Fireye for more details by contacting your local distributor or by check-
ing the Fireye home page at: www.fireye.com.

NOTE: 

When the MBCE-110/230UV modules are used, additional means must be furnished to provide 

those functions usually provided by flame safeguard control systems to meet local regulations (i.e.: 
safe start check, valve closure, starting and running interlocks, safety timings, etc.).
The MBCE-UV shall be powered continuously from a separate source other than the Burner control 
per EN 298. 

* see ordering information

NOTICE: When Fireye products are combined with equipment manufactured by others and/

or integrated into systems designed or manufactured by others, the Fireye warranty, as stated

 

in its General Terms and Conditions of Sale, pertains only to the Fireye products and not to any 
other equipment or to the combined system or its overall performance.

MBCE-110/230UV

Flame Sensor 

Module

MBCE-1002

FEBRUARY 3, 2017

Содержание MBCE-110UV Series

Страница 1: ...UV is ideally suited for flame detection in nat ural gas applications however it can be used for flame detection in propane and light fuel oil applications Check with Fireye for more details by conta...

Страница 2: ...ngle channel module 110 VAC 50 60 Hz use with UV scanner 3 sec FFRT MBCE 1002 MBCE 110UV 4 Single channel module 110 VAC 50 60 Hz use with UV scanner 4 sec FFRT MBCE 1002 MBCE 230UV 1 Single channel m...

Страница 3: ...CE 110 230UV to socket use retaining kit P N 60 2886 NOTICE The MBCE UV is designed to be used with a compatible UV scanner in order to sense the flame activity in a combustion chamber The MBCE UV is...

Страница 4: ...ed 60 302 for UV1AL The sight pipe must permit an unobstructed view of the pilot and or main flame Both pilot and main flames must completely cover the scanner field of view FIGURE 1 AIMING YOUR SCANN...

Страница 5: ...estos insulated wire should be avoided c Multiconductor cable is not recommended without prior factory approval 2 High voltage ignition wiring should not be installed in the same conduit with flame de...

Страница 6: ...he flame signal strength must be greater than the threshold before the MBCE UV can signal FLAME ON The adjustment can be made at the front faceplate potentiometer with the aid of a small flat blade sc...

Страница 7: ...it Table 1 NOTE power cycling the unit should reset some system faults If problem persists please contact local distributor or factory FIGURE 2 FLAME SIGNAL STRENGTH vs 4 20mA OUTPUT LED COLOR DEVICE...

Страница 8: ...CLOSED N C OUTPUT 110 VAC 1A max 230 VAC 1A max 30 VDC 1A max NOTICE The 4 20mA output on the faceplate wiring base is not evaluated for its isolation from to the 4 20mA current loops shall be insulat...

Страница 9: ...e mounting spacing and segregation requirements of the ultimate application to protect the user against electric shock and the equipment against ingress of water and dust 2 Line voltage and extra low...

Страница 10: ...s found defective in material or workmanship or which otherwise fails to conform to the description of the product on the face of its sales order THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES AND F...

Отзывы: