background image

 

ORDERING INFORMATION

PRODUCT SPECIFICATIONS

Supply Voltage

:

MBCE-110UV

 - 110 VAC (+20%, -15%), 50/60 Hz 

 

(@ 0.02 Amp consumption)

MBCE-230UV

 - 230 VAC (+10%, -15%), 50/60 Hz 

 

(@ 0.01 Amp consumption)

Flame Relay Output:

SPDT 1 Amp Resistive @ 110VAC, 1 Amp @ 30VDC
SPDT 1 Amp Resistive @ 230VAC, 1 Amp @ 30VDC 

Flame Failure Response Time:

1 or 3 seconds-depending on part number (-1, -3) for CE
1, 2, 3, or 4 seconds-depending on part number (-1, -2, -3, -4) for UL

 

Operating Temperature

:

-  40

°

 F to 150

°

 F (- 40

°

 C to 65

°

 C)

Storage Temperature:

- 58

°

 F to 185

°

 F (- 50

°

 C to 85

°

 C)

Humidity:

85% RH (max), non-condensing.

Agency Approvals:

MBCE-110UV

UL

MBCE-230UV 

CE / EN298:2012

Shipping Weight:

1 lb (.5 Kg)

UV Scanner:

S1 = Terminal 4
S2 = Terminal 8 

 

UV tube excitation Terminals 4 and 8, +300 VDC (max)

 

IP-Rating

 IP-20 

Test Jacks:

Standby/No flame

4mA

Flame signal (Min)

5.5mA

Flame signal (Max)

20mA

PART NUMBER

DESCRIPTION

BULLETIN

Flame Sensor

MBCE-110UV-1

Single channel module, 110 VAC 50/60 Hz, use with UV scanner, 1 sec. FFRT.

MBCE-1002

MBCE-110UV-2

Single channel module, 110 VAC 50/60 Hz, use with UV scanner, 2 sec. FFRT.

MBCE-1002

MBCE-110UV-3

Single channel module, 110 VAC 50/60 Hz, use with UV scanner, 3 sec. FFRT.

MBCE-1002

MBCE-110UV-4

Single channel module, 110 VAC 50/60 Hz, use with UV scanner, 4 sec. FFRT.

MBCE-1002

MBCE-230UV-1

Single channel module, 230 VAC 50/60 Hz, use with UV scanner, 1 sec. FFRT.

MBCE-1002

MBCE-230UV-3

Single channel module, 230 VAC 50/60 Hz, use with UV scanner, 3 sec. FFRT.

MBCE-1002

Wiring Base

60-2886

Plug in wiring base, DIN rail or panel surface mount complete with retaining kit.

MBCE-1002

Mounting Rails

60-2539-12

DIN style mounting rail, 12 inches, mounts up to 4 modules.

60-2539-24

DIN style mounting rail, 24 inches, mounts up to 8 modules.

60-2539-36

DIN style mounting rail, 36 inches, mounts up to 12 modules.

UV Scanner

UV90L-1

UV scanner, front and side viewing.

SC-108

UV5-1

UV scanner, front and side viewing.

SC-108

UV1AL-3

UV scanner, 1/2” NPT, 36” (915mm) shielded leads.

SC-108

UV1AL-6

UV scanner, 1/2” NPT, 72” (1830mm) shielded leads.

SC-108

4-742-1

Replacement tube for UV90L-1.

NOTICE:

 MBCE-UV module does not have any user serviceable parts. If the unit has a problem, 

return the unit to your local distributor, or contact Fireye directly.

Adequate disconnect means and overload protection is required. A 1 amp external fuse is 
recommended on terminal 10 for over-current protection.

Содержание MBCE-110UV Series

Страница 1: ...UV is ideally suited for flame detection in nat ural gas applications however it can be used for flame detection in propane and light fuel oil applications Check with Fireye for more details by conta...

Страница 2: ...ngle channel module 110 VAC 50 60 Hz use with UV scanner 3 sec FFRT MBCE 1002 MBCE 110UV 4 Single channel module 110 VAC 50 60 Hz use with UV scanner 4 sec FFRT MBCE 1002 MBCE 230UV 1 Single channel m...

Страница 3: ...CE 110 230UV to socket use retaining kit P N 60 2886 NOTICE The MBCE UV is designed to be used with a compatible UV scanner in order to sense the flame activity in a combustion chamber The MBCE UV is...

Страница 4: ...ed 60 302 for UV1AL The sight pipe must permit an unobstructed view of the pilot and or main flame Both pilot and main flames must completely cover the scanner field of view FIGURE 1 AIMING YOUR SCANN...

Страница 5: ...estos insulated wire should be avoided c Multiconductor cable is not recommended without prior factory approval 2 High voltage ignition wiring should not be installed in the same conduit with flame de...

Страница 6: ...he flame signal strength must be greater than the threshold before the MBCE UV can signal FLAME ON The adjustment can be made at the front faceplate potentiometer with the aid of a small flat blade sc...

Страница 7: ...it Table 1 NOTE power cycling the unit should reset some system faults If problem persists please contact local distributor or factory FIGURE 2 FLAME SIGNAL STRENGTH vs 4 20mA OUTPUT LED COLOR DEVICE...

Страница 8: ...CLOSED N C OUTPUT 110 VAC 1A max 230 VAC 1A max 30 VDC 1A max NOTICE The 4 20mA output on the faceplate wiring base is not evaluated for its isolation from to the 4 20mA current loops shall be insulat...

Страница 9: ...e mounting spacing and segregation requirements of the ultimate application to protect the user against electric shock and the equipment against ingress of water and dust 2 Line voltage and extra low...

Страница 10: ...s found defective in material or workmanship or which otherwise fails to conform to the description of the product on the face of its sales order THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES AND F...

Отзывы: