background image

7

£

4.

Installation of Extended Scanner Wiring:

— For extended scanner wiring up to 500 feet (150M), and for shorter lengths to reduce signal

loss, use a shielded wire (Belden 8254-RG62 coaxial cable, or equal)

 for each scanner wire

of UV1, UV2. The ends of the shielding must be taped and not grounded.

5.

Multiple Scanner Installations:

— The wiring from multiple UV scanners may be installed in a common metallic conduit.
— Multi-conductor cable is not recommended without prior factory approval.

INSTALLATION - 69ND1 FLAME ROD

The 69ND1 flame rod proves a gas pilot flame and/or main gas flame. It is a 

spark plug

 type unit

consisting of 

1

/

2

s

 NPT mount, a KANTHAL flame rod, a glazed porcelain insulating rod holder and

a spark plug connector for making electrical connections. The 69ND1 is available in 12

s

 (304.8mm),

18

s

 (457.2mm) or 24

s

 (609.2mm) lengths.

The flame rod may be located to monitor only the gas pilot flame or both the gas pilot and main gas
flames. It is mounted on a  

1

/

2

s

NPT coupling.

The following instructions should be observed:

1.

Keep flame rod as short as possible.

2.

Keep flame rod at least 

1

/

2

s

(12.7mm)from any refractory.

3.

Flame rod should enter the pilot flame from the side so as to safely prove an adequate pilot

flame under all draft conditions.

4.

If the flame is nonluminous (air and gas mixed before burning), the electrode tip should extend

at least 

1

/

2

s

(12.7mm)

into the flame, but not more than halfway through 

5.

If the flame is partly luminous, the electrode tip should extend only to the edge of the flame. It is
not necessary to maintain absolutely uninterrupted contact with the flame.

6.

It is preferable to angle the rod downward to minimize the effect of sagging and to prevent it
from coming in contact with any object.

7.

An adequate grounding surface for the flame must be provided. The grounding surface in actual
contact with the flame must be at least four times greater than the area of the portion of the

flame rod in contact with the flame. It is essential to adjust the flame rod and ground area ratio

to provide a minimum signal reading of 6VDC.

Note: Interference from the ignition spark can alter the true signal reading by adding to, or sub-

tracting from it. This trend sometimes may be reversed by interchanging the primary wires (line volt-

age) to the ignition transformer. This interference can also be reduced by the addition of grounded

shielding between the flame rod and ignition spark.

WRONG POSITION

OF ROD

INADEQUATE FLAME

PILOT BURNER

CORRECT POSITION

OF PILOT FLAME

CORRECT
POSITION

OF ROD

Содержание M-SERIES II

Страница 1: ...e are deter mined by the programmer module Type of flame scanner UV or Flame Rod and Flame Failure Response Time F F R T are determined by the amplifier module LED indicator lights on all programmer m...

Страница 2: ...125 VA pilot duty solenoid valve plus 250 VA Transformer 5 Main Fuel Valve s 125 VA pilot duty solenoid or 25 VA pilot duty solenoid and 400 VA opening motorized 8 Motor or contactor Motor normally e...

Страница 3: ...TRAIGHT FEMALE PIPE THREAD 1 DIA 25 4 UV1A UV SCANNER 36 FLEXIBLE CABLE UV1A3 72 FLEXIBLE CABLE UV1A6 2 50 8 36 1m APPROX FLEXIBLE CABLE 3 8 PIPE THREAD 13 16 DIA 206 UV2 UV SCANNER 2 3 8 60 3 1 3 16...

Страница 4: ...he following Chassis UV Scanner or Flame Detector Programmer Module Wiring Base Amplifier Module WARNING Installer must be trained and qualified Follow the burner manufacturer s instructions if suppli...

Страница 5: ...b a window coupling Fireye part 60 1257 to seal off furnace or burner pressure c cooling air to reduce the scanner sight pipe temperature 3 Mount rigidly a short length 10 20cm of 1 2s or 3 4s black...

Страница 6: ...Scanner Installations Wiring of UV Scanners The UV1A scanner is supplied with 3 90cm or 6 180cm of flexible cable The UV 2 scanner is supplied with 3 90cm of flexible cable If it is necessary to exte...

Страница 7: ...e from the side so as to safely prove an adequate pilot flame under all draft conditions 4 If the flame is nonluminous air and gas mixed before burning the electrode tip should extend at least 1 2s 12...

Страница 8: ...30M Maximum wiring run not to exceed 400 feet 120M MAINTENANCE Type UV1 UV2 UV8A and 45UV3 Ultraviolet Scanners The viewing area of the scanner must be kept clean Even a small amount of contamination...

Страница 9: ...is energized only during the Ignition Safety Time Flame On This LED is energized whenever a flame signal is detected by the UV scanner or Flame detector Alarm this LED is energized whenever a safety...

Страница 10: ...ition is initiated PTFI LED lit 3 When main flame is detected Flame LED lit KF 1 closes energizing Terminal 5 which pow ers the secondary main fuel valve if used KF 2 opens de energizing Terminal 4 wh...

Страница 11: ...for flame rectification amplifiers 5 Inadequate flame signal may be improved by a Assuring that the flame detector and wiring installations have followed the instructions on Pages 5 through 9 b Assuri...

Страница 12: ...gnition and pilot valve to Terminal 3 2 Initiate a normal startup 3 Manually shut off all fuel and observe the loss of flame signal on the test meter 4 If flame signal does not reduce to zero within t...

Страница 13: ...clean Use a clean cloth with detergent as often as oper ating conditions require Remove any residual detergent ROTATION It is recommended that units purchased as spares be rotated periodically so tha...

Страница 14: ...NG SUCCESSFUL RESET REPLACE PROGRAMMER DID FLAME LED COME ON YES MP100 4 7 SECONDS MP230 PREPURGE DELAY TIME NO YES NORMAL LOCKOUT NO NO NO NO NO YES AMPLIFIER DEFECTIVE OR MC120 REPLACE SCANNER REPEA...

Страница 15: ...IN BURNER NO TROUBLESHOOTING TIPS 1 Verify that there is a solid earth ground wire brought to the panel that the Fireye base is mounted to 2 In a rectification system verify that terminal S1 is solidl...

Страница 16: ...ME ROD FUEL VALVE CHASSIS WITH MART3 OR MART1T AMPLIFIER MODULES IGNITION GAS VALVE CONNECTION TO TERMINAL 1 IS NOT REQUIRED WITH MART3 OR MART1T AMPLIFIER MODULE WITH MAUV3 AND MAUV1T KB ENERGIZED WH...

Страница 17: ...DDED TO REQUIRE OPERATOR START UP EACH TIME THE BURNER FIRES S2 3 5 4 1 IGNITION 7 8 2 A 6 PILOT S1 B MULTIPLE BURNER SYSTEMS S2 3 5 4 1 IGNITION 7 8 2 A 6 PILOT S1 LIMIT R MANUAL RESET MAIN GAS VALVE...

Страница 18: ...ted in these general terms and conditions of sale remedies with respect to any product or part number manufactured or sold by Fireye shall be limited exclusively to the right to replace ment or repair...

Отзывы: