FIGURE 1.

INSTALLATION AND MOUNTING DIAGRAM OF ED510 WITH 129-145

WIRING CONNECTIONS FOR ED610 AND ED510 REMOTE DISPLAY

See Figure 2. Use the ED610 multi-port connector to remote mount the ED510 display greater than
eight (8) feet away from the Flame-Monitor control. An eight (8) conductor, 18 gage, low capaci-
tance, overall shielded cable (Belden 9554 or equivalent) must be used between the ED610 at the
burner site and the ED610 at the remote site. An ED580 cable is required between the ED510 dis-
play module and the ED610 connector as well as the ED610 connector and FLAME-MONITOR
control. A ferrite core is provided on the ED580 cable to improve the electrical noise immunity of
the FLAME-MONITOR system.

The connector nearest to the ferrite core must be plugged into

the EP Programmer.

MAKE SURE THE FLAME-MONITOR SYSTEM IS PROPERLY GROUNDED. REFER
TO THE WARNING BOX ON PAGE 2 TO ENSURE THE SYSTEM IS PROPERLY
GROUNDED.

The position of the ferrite core is not critical on the ED580 cable connected between the ED510 dis-
play and ED610 adapter. The Flame-Monitor control will drive two (2) ED510 display modules.

The Belden cable 9554 has 4 twisted pairs with an overall shield. Conductor pairs are color coded
red and black and numbered at one (1) inch intervals (e.g. 1-black, 2-red). Maximum cable distance
of the ED510 from the Flame-Monitor control is 700 feet. Do not ground shield at both ED610's.

CAUTION: When the remote display or the remote reset is installed, make sure that the
remote location is within sight and sound of the fired equipment. Safety procedures require
that the operator be at the burner to reset the safety controls in order that any unsafe condi-
tions can be discovered and corrected prior to resetting the safety controls or devices. Fireye
does not recommend remote reset locations beyond sight and sound of the burner.

KEYPAD/DISPLAY

FRONT

GASKET

PEM NUT
INSIDE

MOUNTING
SCREW

MOUNTING
PLATE

MAXIMUM THICKNESS

CONNECTOR
CABLE (2’, 4’, or 8’)

TO EP/EPD PROGRAMMER

 5/64 INCH (2.0mm) PANEL

3.63

(92.0)

3.63

(92.0)

SUGGESTED PANEL CUTOUT DIMENSIONS

Содержание 129-145-1

Страница 1: ...splay module remote from the Flame Monitor control with EP programmers Engineering code 28 or later or EPD programmers Engineering code 02 or later ED512 REMOTE MOUNTING CABLES The ED512 remote mount cable is a cable in varying lengths 2 4 and 8 with an RJ12 4P4C con nector on each end of the cable The ED512 is used with the ED610 multi port connector for connect ing the Flame Monitor control with...

Страница 2: ... immunity of the FLAME MONITOR system The connector nearest to the ferrite core must be plugged into the EP Programmer TO ENSURE THE SYSTEM IS PROPERLY GROUNDED 1 Connect the back plane of the mounting cabinet to a proper earth ground 2 Ground the FLAME MONITOR wiring base to the mounting cabinet by using mounting screws with star washers to ensure proper electrical contact 3 Connect the green gro...

Страница 3: ...osition of the ferrite core is not critical on the ED580 cable connected between the ED510 dis play and ED610 adapter The Flame Monitor control will drive two 2 ED510 display modules The Belden cable 9554 has 4 twisted pairs with an overall shield Conductor pairs are color coded red and black and numbered at one 1 inch intervals e g 1 black 2 red Maximum cable distance of the ED510 from the Flame ...

Страница 4: ...ING BOX ON PAGE 2 TO ENSURE THE SYSTEM IS PROPERLY GROUNDED Ground the shield at one end only of each individual wiring run Total maximum cable distances shall not exceed 4 000 feet NOTE Cable should be routed within the cabinet so that it doesn t come in close proximity with ignition wires high energy contactors or solenoids ED610 10 9 8 7 6 5 4 3 2 1 J5 J1 ED510 REMOTE E110 FLAME MONITOR ED580 2...

Страница 5: ...d EPD programmers hav ing and engineering code of 4 or greater MAKE SURE THE FLAME MONITOR SYSTEM IS PROPERLY GROUNDED REFER TO THE WARNING BOX ON PAGE 2 TO ENSURE THE SYSTEM IS PROPERLY GROUNDED Ground the shield at one end only of each individual wiring run Total maximum cable distances shall not exceed 4 000 feet NOTE Cable should be routed within the cabinet so that it doesn t come in close pr...

Страница 6: ...nd ED510 as shown using the ED580 cables Wire a normally open momentary push button switch across termi nals 8 4 Jumper J4 on the ED611 must be in position 1 to 2 Refer to Figure 8 REFER TO CAUTION FOR REMOTE RESET ON PAGE 3 ED610 10 9 8 7 6 5 4 3 2 1 J5 J1 ED610 10 9 8 7 6 5 4 3 2 1 J5 J1 E110 OPTION 1 TO PC PLC ETC ED512 2 4 8 FLAME MONITOR BELDEN 8761 E110 ED512 2 4 8 FLAME MONITOR CLEAR BLACK ...

Страница 7: ...ication software program P N E720 running on an IBM compatible PC is required for communication with the E340 controls Fireye recommends using the E500 Communication interface when communicating with the E340 controls since the E500 provides communication with the Flame Monitor flame safeguard con trols as well However the EC485 converter can be used to communicate only with the E340 con trols FLA...

Страница 8: ... NO WARRANTY OF MERCHANTABILITY OR ANY OTHER WARRANTY EXPRESS OR IMPLIED Except as specifically stated in these general terms and conditions of sale remedies with respect to any product or part number manufactured or sold by Fireye shall be limited exclusively to the right to replace ment or repair as above provided In no event shall Fireye be liable for consequential or special dam ages of any na...

Отзывы: