background image

For best protection, install a smoke alarm in EVERY room. 

In addition, we recommend that all smoke alarms be interconnected.

Also, as required by the California State Fire Marshal:

“Early warning fire detection is best achieved by the installation of
fire detection equipment in all rooms and areas of the household as
follows: a smoke alarm installed in each separate sleeping area (in
the vicinity, but outside the bedrooms), and heat or smoke alarms in
the living rooms, dining rooms, bedrooms, kitchens, hallways, attics,
furnace rooms, closets, utility and storage rooms, basements and
attached garages.”

Model CCPB smoke alarms DO NOT meet NFPA minimum
requirements for new construction. Use this alarm only in
recommended smoke alarm locations.

Mobile Home Installation

• For minimum protection, smoke alarms should be installed in 

compliance with H.U.D. Manufactured Home Construction Safety
Standards Title 24 CFR, Section 3280.208 and Section 3282.

• For additional protection, see single-story residence smoke alarm

requirements and recommendations for existing homes and new
construction.

NOTE: For mobile homes built before 1978, install smoke alarms on
inside walls between 4 and 12 inches from the ceiling (older mobile
homes have little or no insulation in the ceiling). This is especially
important if the ceiling is unusually hot or cold.

Additional Smoke Alarm Placement Information

Install a smoke alarm as close to the center of the ceiling as 
possible. If this is not practical, mount no closer than 4 inches from 
a wall or corner. Also, if local codes allow wall mounting, install
smoke alarms on walls between 4 and 12 inches from ceiling/wall
intersections.
Install a smoke alarm in each room that is divided by a partial wall
(either coming down from the ceiling at least 24 inches, or coming 
up from the floor).
Install smoke alarms on peaked, cathedral, or gabled ceilings, at or
within 3 feet from the highest point (measured horizontally).
Install a smoke alarm in lived-in attics or attics which house electrical
equipment like furnaces, air conditioners, or heaters.

DO NOT Install Smoke Alarms:

In areas where combustion particles are present.

(Combustion

particles are the by-products of something that is burning.) Areas to
avoid include poorly ventilated kitchens, garages, near furnaces, or
near hot water heaters. Place smoke alarm as far from the source of
combustion particles as possible to prevent nuisance alarms.

In damp or very humid areas

such as bathrooms with showers

where normal humidity may rise above 93% relative humidity. Areas
above this humidity level can cause a false alarm.

In direct air flow nor within 3 feet of heating and cooling supply
vents.

Install at least 3 feet (0.9 meters) away from these areas. The

air could blow smoke away from the detector, interrupting its alarm.

In rooms where temperatures may fall below 40°F (4°C) or rise
above 100°F

(38°C).

In extremely dusty, dirty, or insect-infested areas.

Loose particles

interfere with smoke alarm operation.

KITCHEN

DINING 
ROOM

BEDROOM

BEDROOM

BEDROOM

LIVING ROOM

BEDROOM

BEDROOM

LIVING
ROOM

DINING
ROOM

BASEMENT

HALL

/

TV ROOM

DINING 
ROOM

KITCHEN

BEDROOM

BEDROOM

BEDROOM

LIVING ROOM

SMOKE ALARM

COMBO SMOKE/CARBON MONOXIDE ALARM 

Key

CARBON MONOXIDE ALARM 

WARNING

!

3

CEILING

ACCEPTABLE HERE

NEVER HERE

TOP OF DETECTOR
ACCEPTABLE HERE

SIDE 

WALL

4 IN.

(O.1M)

4 IN.

(O.1M)

MINIMUM

12 IN.

(O.3M)

MAXIMUM

3'0

ACCEPTABLE
HERE

SOFFIT

SUBWALL

24"

Содержание CCPB

Страница 1: ...e information it contains the easier you will find it to install operate and maintain your smoke alarm properly which ultimately means greater security and peace of mind for you and your family Invensys Controls The ionization type alarms are generally more effective at detecting fast flaming fires which consume combustible materials rapidly and spread quickly Sources of these fires may include fl...

Страница 2: ...er and about 0 1 m 4 in down the wall as shown in Figure A 11 8 3 Detectors should not be placed in this dead air space Smoke and heat detectors should be installed in those loca tions recommended by the manufacturer s published instructions except in those cases where the space above the ceiling is open to the outside and little or no insulation is present over the ceiling Such cases result in th...

Страница 3: ...s between 4 and 12 inches from ceiling wall intersections Install a smoke alarm in each room that is divided by a partial wall either coming down from the ceiling at least 24 inches or coming up from the floor Install smoke alarms on peaked cathedral or gabled ceilings at or within 3 feet from the highest point measured horizontally Install a smoke alarm in lived in attics or attics which house el...

Страница 4: ...move thin plastic from notch on smoke alarm edge 8 Position smoke alarm to mounting bracket and turn clockwise The smoke alarm will lock into place To engage tamper resist feature insert pin into notch on edge of smoke alarm and mounting plate NOTE Smoke alarm will not mount to bracket if battery is not installed 9 Test smoke alarm See TESTING your SMOKE ALARM DO NOT connect this smoke alarm to an...

Страница 5: ...racell MN 1604 and long life lithium battery Ultralife U9VL J DO NOT USE ANY OTHER TYPE OF BATTERY EXCEPT AS SPECI FIED IN THIS MANUAL DO NOT USE RECHARGEABLE BATTERIES 1 Turn smoke alarm counter clockwise to detach from mounting plate 2 Remove battery from pocket Disconnect and discard drained battery from battery connector 3 Connect a fresh 9 volt or 9 volt lithium battery to connector The batte...

Страница 6: ...ng smoke alarms that work from two different power sources can give extra protection in case of a dead battery or an AC power failure If you have repeated false alarms move the smoke alarm to a different location This smoke alarm is designed to be used inside a single family household In multi family buildings each individual living unit should have its own alarms It is not a substitute for a comp...

Страница 7: ...ollow predefined escape plans if possible 3 Meet at a pre arranged meeting place outside the building 4 Call the fire department from OUTSIDE the building 5 DO NOT GO BACK INSIDE A BURNING BUILDING Wait for the fire department to arrive These guidelines will assist you in the event of a fire However to reduce the chance that fires will start practice fire safety rules and prevent hazardous situati...

Страница 8: ...TE Some states do not allow limitations on how long an implied warranty lasts so the above limitations may not apply to you IN NO CASE SHALL INVENSYS CONTROLS BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY EXPRESS OR IMPLIED WHATSOEVER EVEN IF THE LOSS OR DAM AGE IS CAUSED BY ITS NEGLIGENCE OR FAULT Some states do not allow the exclusion or limitatio...

Отзывы: