background image

Agency Alarm Placement 
Recommendations

Invensys Controls Americas recommends complete coverage 
protection achieved by installing a smoke alarm in every room of
your home.

For your information, the National Fire Protection Association’s
Standard 72, reads as follows:

11.5.1*  Required Detection.
11.5.1.1*  Where required by applicable laws, codes, or standards for
a specific type of occupancy, approved single- and multiple-station
smoke alarms shall be installed as follows:

(1) *In all sleeping rooms and guest rooms
(2) *Outside of each separate dwelling unit sleeping area, within

6.4 m (21 ft) of any door to a sleeping room, the distance
measured along a path of travel

(3) On every level of a dwelling unit, including basements
(4) On every level of a residential board and care occupancy 

(small facility), including basement and excluding crawl spaces
and unfinished attics

(5) *In the living area(s) of a guest suite
(6) In the living area(s) of a residential board and care occupancy

(small facility)

A.11.8.3  One of the most critical factors of any fire alarm system 
is the location of the fire detecting devices.  This annex is not a 
technical study. It is an attempt to provide some fundamentals on
alarm or detector location.  For simplicity, only those types of alarms
or detectors recognized by Chapter 11 (e.g., smoke and heat alarms
or detectors) are discussed. In addition, special problems requiring
engineering judgment, such as locations in attics and in rooms with
high ceiling, are not covered.

Smoke Alarms or Smoke Detector Mounting – Dead Air Space.

The smoke from a fire generally rises to the ceiling, spreads out
across the ceiling surface, and begins to bank down from the ceiling.
The corner where the ceiling and wall meet is an air space into which
the smoke could have difficulty penetrating.  In most fires, this dead
air space measures about 0.1 m (4 in.) along the ceiling from the 
corner and about 0.1 m (4 in.) down the wall as shown in Figure
A.11.8.3 Detectors should not be placed in this dead air space.

Smoke and heat detectors should be installed in those loca-

tions recommended by the manufacturer’s published instructions,
except in those cases where the space above the ceiling is open 
to the outside and little or no insulation is present over the ceiling.
Such cases result in the ceiling being excessively cold in the winter
or excessively hot in the summer.  Where the ceiling is significantly
different in temperature from the air space below, smoke and heat
have difficulty reaching the ceiling and a detector that is located on
that ceiling.  In this situation, placement of the detector on a side-
wall, with the top 0.1 m to 0.3 m (4 in. to 12 in.) from the ceiling, is
recommended.
Figure A.11.8.3  Example of Proper Mounting for Detectors

The situation described previously

for uninsulated or poorly insulated 
ceilings can also exist, to a lesser extent,
in the case of outside walls.  The recom-
mendation is to place the smoke alarm or
smoke detector on a sidewall.  However,
where the sidewall is an exterior wall with
little or no insulation, an interior wall
should be selected.  It should be recog-
nized that the condition of inadequately insulated ceilings and walls
can exist in multifamily housing (apartments), single-family housing,
and mobile homes.

In those dwelling units employing radiant heating in the ceiling,

the wall location is the recommended location.  Radiant heating in
the ceiling can create a hot-air, boundary layer along the ceiling 
surface, which can seriously restrict the movement of smoke and
heat to a ceiling-mounted detector.
This equipment should be installed in accordance with the National
Fire Protection Association’s Standard 72, NFPA, Batterymarch Park,
Quincy, MA 02269.
THIS STANDARD MEANS YOU SHOULD INSTALL AND USE 
A SMOKE ALARM IN EVERY ROOM AND AREA OF YOUR 
HOUSEHOLD OR BUILDING FOR BEST PROTECTION.

4 IN

(0.1m )

4 IN

(0.1m )

MINIMUM

12 IN

(0.3 m )

MAXIMUM

CEILING

SIDE

WALL

ACCEPTABLE HERE

NEVER HERE

TOP OF ALARM

ACCEPTABLE HERE

2

Содержание CCPB

Страница 1: ...e information it contains the easier you will find it to install operate and maintain your smoke alarm properly which ultimately means greater security and peace of mind for you and your family Invensys Controls The ionization type alarms are generally more effective at detecting fast flaming fires which consume combustible materials rapidly and spread quickly Sources of these fires may include fl...

Страница 2: ...er and about 0 1 m 4 in down the wall as shown in Figure A 11 8 3 Detectors should not be placed in this dead air space Smoke and heat detectors should be installed in those loca tions recommended by the manufacturer s published instructions except in those cases where the space above the ceiling is open to the outside and little or no insulation is present over the ceiling Such cases result in th...

Страница 3: ...s between 4 and 12 inches from ceiling wall intersections Install a smoke alarm in each room that is divided by a partial wall either coming down from the ceiling at least 24 inches or coming up from the floor Install smoke alarms on peaked cathedral or gabled ceilings at or within 3 feet from the highest point measured horizontally Install a smoke alarm in lived in attics or attics which house el...

Страница 4: ...move thin plastic from notch on smoke alarm edge 8 Position smoke alarm to mounting bracket and turn clockwise The smoke alarm will lock into place To engage tamper resist feature insert pin into notch on edge of smoke alarm and mounting plate NOTE Smoke alarm will not mount to bracket if battery is not installed 9 Test smoke alarm See TESTING your SMOKE ALARM DO NOT connect this smoke alarm to an...

Страница 5: ...racell MN 1604 and long life lithium battery Ultralife U9VL J DO NOT USE ANY OTHER TYPE OF BATTERY EXCEPT AS SPECI FIED IN THIS MANUAL DO NOT USE RECHARGEABLE BATTERIES 1 Turn smoke alarm counter clockwise to detach from mounting plate 2 Remove battery from pocket Disconnect and discard drained battery from battery connector 3 Connect a fresh 9 volt or 9 volt lithium battery to connector The batte...

Страница 6: ...ng smoke alarms that work from two different power sources can give extra protection in case of a dead battery or an AC power failure If you have repeated false alarms move the smoke alarm to a different location This smoke alarm is designed to be used inside a single family household In multi family buildings each individual living unit should have its own alarms It is not a substitute for a comp...

Страница 7: ...ollow predefined escape plans if possible 3 Meet at a pre arranged meeting place outside the building 4 Call the fire department from OUTSIDE the building 5 DO NOT GO BACK INSIDE A BURNING BUILDING Wait for the fire department to arrive These guidelines will assist you in the event of a fire However to reduce the chance that fires will start practice fire safety rules and prevent hazardous situati...

Страница 8: ...TE Some states do not allow limitations on how long an implied warranty lasts so the above limitations may not apply to you IN NO CASE SHALL INVENSYS CONTROLS BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY EXPRESS OR IMPLIED WHATSOEVER EVEN IF THE LOSS OR DAM AGE IS CAUSED BY ITS NEGLIGENCE OR FAULT Some states do not allow the exclusion or limitatio...

Отзывы: