Mount the Amerex 22408 Control Panel in a dry, protected area (such as 

inside the vehicle cab).  It should be clearly visible and within reach of 
the vehicle operator. 

DIMENSIONS - 135H x 189W x 50D mm 

Connect  the  wiring  loom  to  the  panel.  
Note:  each cable uses a different plug to 

ensure  that  they  are  connected  to  the 
correct plug.  DO NOT force plugs. 

The panel should not be placed in 

environments where the temperature is outside the range of -40°C to 
+66°C.  
 
Mounting Bracket (FP-22408B) may be used.  This bracket 
will accommodate the control panel and a manual activation 
switch.  Made from 316 stainless steel. 

 

 

 
 
 
 
 

 

Connect Power Supply Assembly to the vehicle's battery terminals and connect to panel using the Power Supply 

lead coming from the panel (marked Red).  

Note:

  the Red cable goes to the battery's positive terminal and the 

black cable goes to the battery's negative terminal. 
 

 

 

 

Содержание FP-22408

Страница 1: ...tion Switches 4 Linear Heat Detection Cable 4 Installation of FirePro Units MAX 4 Units 5 Thermal Fuse 5 Relay Connections and Programming 6 Sounder circuit wiring 6 Extension Leads 6 Colour Coded Cab...

Страница 2: ...il the FirePro generators are replaced SYSTEM OK INDICATOR will indicate green when the system is receiving appropriate 24vDC supply and is operating normally If power is not supplied or a fault if de...

Страница 3: ...plug DO NOT force plugs The panel should not be placed in environments where the temperature is outside the range of 40 C to 66 C Mounting Bracket FP 22408B may be used This bracket will accommodate...

Страница 4: ...the cables coming out of the Internal Activation Switch if no External Activation Switch is to be used Switch mechanism with travel Pin Switch Shown in External Mount Mount the Linear Heat Detection...

Страница 5: ...he FirePro generator s to the panel using the Activation Circuit marked Yellow For risks that require two or more FirePro generators use the supplied splitter cable s USING Splitter Cables Using the s...

Страница 6: ...d this needs to be specified by the installer To create extension leads follow these steps 1 Cut cable to required length and strip outer insulation to approximately 50mm Remove shielding and for 2 Pi...

Страница 7: ...late the Model 17310 panel simply unplug the activation cable and this will put the panel into fault This should be done at the connection closest to the panel Control panels do not require any specif...

Страница 8: ...Pro Generators and brackets are free from debris and any corrosion Ensure brackets are tight and show no signs of fatigue 5 Inspect Linear Heat Detection Cable ensuring it maintains a closed connectio...

Страница 9: ...omes with installed Deutsch Plug for easy install FP 6200 Heavy Duty Bracket 316 SS Suits FP 100 200 500 FirePro Aerosol Generators FP 08960 Signage for the System A sheet of different size labels FP...

Страница 10: ...icle ID Number Date of Installation FirePro Units Installed Specify Size and No of units Manual Activation Specify Location of Manual Actuation Switches Shutdown Installation Specify Delay Time and Sh...

Отзывы: