Page 31/43
Firemiks AB
Instruction manual version: SPFA FM
P.O. Box 8155, 104 20 STOCKHOLM, Sweden
phone +46-8-551 196 10 - [email protected] - www.firemiks.com
7.3 Once a month
7.3.1 Check there are no leakages on the unit or in the connections or couplings
and that no fasteners on the unit and installation are loose.
7.3.2 Check the oil level in the concentrate pump. Use the dip stick or the oil level
window if available on your unit. Refill if necessary according to section 7.6.1
7.3.3 Dry pipe system. Rotate the water motor and the concentrate pump manually.
Remove the protection cap on the back gable and use a wrench to turn the
water motor rotor. Note! Do not forget to put back the protection cap.
If
initially there is much resistance to rotation which releases once there
is movement, increase the rotating interval to once every second week.
With salt water, rotation must also be done at least every second week.
7.3.4 Wet pipe system. Let a small water flow go through the unit for about 30
seconds (see also 4.3.13) and check rotation of the unit.
If initially there is
much resistance to rotation which releases suddenly, increase the
rotating interval to once every second week. With salt water, rotation
must also be done at least every second week or more often if
necessary
.