background image

Connect the programming cable to S1 and S2 terminals

Note

The "1" of the DIP switch must not be in the "ON" state, otherwise it will not code properly.

TX7932

1. Read

View Program 

2. Write

Write Address 

3. R/W Config

Sensitivity

Span

4. Set 

-

FG-BD100 Programming Devices

By Handheld

R/W Config
Sensitivity Parameter  

Level 1 Sensitivity: 2.6 dB 

[Default]

Level 2 Sensitivity: 3.8 dB

Level 3 Sensitivity: 5.8 dB

READ

Address: 001

Sensitivity: 001

ID: 123456789012

Span m: 70-100

R/W Config
Span Parameter  

Span 1: 8 to 20 meter [Limited Path]

Span 2: 20 to 40 meter [Short Path]

Span 3: 40 to 70 meter [Normal Path-Default]

Span 4: 70 to 100 meter [Long Path]

FIREGUARD UK Technology Copyright ©2021, All right reserved.

Содержание FG-BD100

Страница 1: ...FG BD100 Beam Detector Product Introduction FIREGUARD UK Technology Copyright 2021 All right reserved ...

Страница 2: ...th Span 3 40 to 70 meters Normal Path Span 4 70 to 100 meters Long Path Beam Path Angle 0 4º Directional This data takes the average of the left and right deflection angles Alignment Guide Laser Beam Pointer Digital Display Guide Nixie Tube LED Indicator Guide Red Fire Yellow Fault Green Alignment Reset Time Less than 2 Second Relay Capacity Fire Fault Normally Open Close 2 0 A 30 VDC Physical Mat...

Страница 3: ...Product Image Exterior and Interior FIREGUARD UK Technology Copyright 2021 All right reserved ...

Страница 4: ...3 Terminal HJ1 and HJ2 for connecting Fire signal relay output Normally Open 4 Terminal GZ1 and GZ2 for connecting Fault signal relay output Normally Close LED Indicators Colour Function Fire Red Illuminates when at least one fire alarm event occur Fault Yellow Illuminates when at least one fault alarm event occur in the Detector Alignment Green Illuminates during the commissioning FIREGUARD UK Te...

Страница 5: ...t adjust parameter by DIP Switch you should turn 1 to ON state first The DIP switch has a higher priority than the handheld encoding which means that if the DIP SWITHCH 1 is ON TX7932 connection to S1 and S2 cannot be used at this time 2 and 3 used to adjust span parameter 4 and 5 used to adjust sensitivity parameter 6 Reserved for future use FIREGUARD UK Technology Copyright 2021 All right reserv...

Страница 6: ...Programming Devices By Handheld R W Config Sensitivity Parameter Level 1 Sensitivity 2 6 dB Default Level 2 Sensitivity 3 8 dB Level 3 Sensitivity 5 8 dB READ Address 001 Sensitivity 001 ID 123456789012 Span m 70 100 R W Config Span Parameter Span 1 8 to 20 meter Limited Path Span 2 20 to 40 meter Short Path Span 3 40 to 70 meter Normal Path Default Span 4 70 to 100 meter Long Path FIREGUARD UK Te...

Страница 7: ... detector and mirror was moved Not properly commission at the start Conduct maintenance Re Commission the detector Unable to commission Transmit Receive diode is not working The reed switch is damaged Replace the component Fire signal can t be cleared There is obscuration on the optical pathway between the detector and the reflector The angle of optical pathway has changed and need to be aligned a...

Страница 8: ...r Mirrors 2 Twelve screws with plastice wall plugs 3 Two screws with washers 4 Mounting Bracket 5 Opaque Translucent Material Test board 6 Magnetic Tool 7 Operation Mauanul FG BD100 Supplied Accessories FIREGUARD UK Technology Copyright 2021 All right reserved ...

Страница 9: ...End of Slide FIREGUARD UK Technology Copyright 2021 All right reserved ...

Отзывы: