PARALLEL INSTALLATION
•
Ensure proper uniform current distribution with equal resistance cables on both sides of
the Battery Terminals are connected to common load/ charger busbars. No center-
tappings are allowed as it would cause differential drain on batteries in the battery bank.
SERIES INSTALLATION
4V L16 CONNECTION
The battery will be shipped with the connection bar shown on the left. This
connects the 2 cells inside the module in series making the battery 4V and
450Ah. For a 12V x 450Ah bank, connect 3 x 4V L16 in series (3S). For 24V x
450Ah, connect 6 in series (6S). For 900Ah x 12V, it can be either 2P (P = in
parallel) x 3S, or 3S x 2P. For 900Ah x 24V, it can be either 2P x 6S, or 6S x 2P