2.4

 

Connec ng  the  Cygnus  Portable  Solar  Generator

 

 

2.4.1

 

Earth  a achment:  Installing  the  Op onal  Earth  Rod:

 

 

1.

 

Find  a  suitable  place  to  drive  the  earth  rod  into  the  ground.  The  earth  rod  should  be  driven  down  at  least  

 

 

 

600mm  into  the  ground  using  a  mallet  and  placed  as  near  to  the  unit  as  possible.

 

 

2.

 

Check  the  earth  cable  is  securely  clamped  to  the  rod.  The  clamp  may  need  re ghtening  a er  driving  the  earth  

 

 

 

rod  down.

 

 

3.

 

On  the  control  panel,  locate  the  earth  bolt  (Fig.  1,  C5)  undo  the  earth  bolt  wing  nut  and  remove  one  of  the  

 

 

 

washers.  Then  slide  the  ring  terminal  at  the  end  of  the  earth  cable  onto  the  earth  bolt.  Replace  the  washer  and  

 

 

 

ghten  the  wing  nut.

 

 

2.4.2

 

Connect  the  Inputs:

 

There  are  a  number  of  means  available  to  charge  the  unit.  Instruc ons  on  how  to  connect  charging  inputs  (e.g.  solar  PV,  
wind  turbines,  Kinectrics  equipment)  are  available  as  appendices  to  this  manual  or  included  with  those  products  at  the  
point  of  purchase.  All  user  manuals  can  also  be  downloaded  from  the  manufacturer’s  website  at  www.fireflysolar.net

 

It  is  also  possible  to  operate  the  unit  only  using  the  internal  ba ery  bank,  without  external  inputs  connected.

 

 

 

When  Cygnus  is  connected  to  an  external  AC  supply,  the  output  voltage  is  transferred  from  its  input.  
In  this  case  the  unit  will  not  modify  the  AC  output:  Consumers  will  be  supplied  with  an  output  

 

iden cal  to  the  source.

 

                W  A  R  N  I  N  G

 

Care  must  be  taken  to  ensure  that  the  correct  connec ons  are  made  to  avoid  the  risk  of  electrocu on  
or  possible  damage  to  the  unit’s  internal  components.

 

                W  A  R  N  I  N  G

 

Ensure  that  the  cumula ve  power  of  connected  consumers  does  not  exceed  the  maximum  power  out-­‐
put  of  your  unit–  refer  to  the  ra ng  plate  to  ascertain  the  unit’s  maximum  power  output.

 

                W  A  R  N  I  N  G

 

All  connected  consumers  must  be  fit  for  purpose–  refer  to  their  ra ng  plates  and  manuals  to  ascertain  
the  required  input.

 

                W  A  R  N  I  N  G

 

A  protec ve  earth  must  be    connected  to  the  unit  in  compliance  with  applicable  local  standards  and  
regula ons.  This  can  be  done  either  by  connec ng  to  a  suitable  exis ng  electrical  earth,  or  by  using  an  
op onal  earth  rod  supplied  by  the  manufacturer.

 

Содержание Cygnus CYG2400/1380/24

Страница 1: ...ual v3 0 2011 Page 1 Cygnus Portable Solar Generator User Manual v3 0 2011 For use with the following models CYG2400 460 24 CYG2400 920 24 CYG2400 1380 24 CYG3500 920 24 CYG3500 1380 24 CYG5000 920 24...

Страница 2: ...8 2 4 3 Connect the Output Power Cables 9 3 General Opera on 10 3 1 Turning the Power On 10 3 2 Monitoring the Power 11 3 2 1 Displaying Real me Ba ery Bank Voltage 11 3 2 2 Displaying the Ba ery Bank...

Страница 3: ...nected to Single Cygnus 26 6 4 Appendix 4 Troubleshoo ng Guide 27 6 5 Appendix 5 Technical Data 28 6 6 Appendix 6 Further Reading 29 Figures Fig 1 Cygnus Control Panel Component Reference 7 Fig 2 RCC0...

Страница 4: ...will be referred to as The manufacturer The Cygnus Portable Solar Generator will be referred to as Cygnus or Unit Any items that consume power will be referred to as Consumers State of Charge of the b...

Страница 5: ...Fire y Solar generators harness energy supplied by the sun using photovoltaic PV cells storing it for when it s needed Addi onally mul charge inputs allows kine c and wind energy to be stored for conv...

Страница 6: ...t weights 3 It is recommended that the unit is secured using suitable straps when in transit to prevent it from moving 2 2 2 Loading Unloading 1 Cygnus must be loaded or unloaded using the correct equ...

Страница 7: ...OC C2 RCC 03 Displays real me informa on on inputs and outputs also allows their adjustment C3 Open Terminate Switch Used when mul ple Cygnus Portable Solar Generators are linked together C4 Power On...

Страница 8: ...r manuals can also be downloaded from the manufacturer s website at www re ysolar net It is also possible to operate the unit only using the internal ba ery bank without external inputs connected When...

Страница 9: ...ial CEEform socket for the connec on of AC power out to consumers requiring Fig 1 E2 1 Before any power connec ons are made ensure that both the RCD Fig 1 B1 and MCB Fig 1 B2 are switched O 2 Plug in...

Страница 10: ...p will be heard and the RCC 03 Fig 1 C2 backlight will illuminate 5 The unit is now in standby mode 6 Message 012 use of ba ery temperature sensor will be displayed for ve seconds 7 A er which the fol...

Страница 11: ...a ery life le in the unit E g C75 indicates that there is 75 ba ery capacity remaining If the 30 lower limit is reached the Smartgauge s internal alarm will be triggered and its display will ash betwe...

Страница 12: ...SC on the RCC 03 Fig 1 C2 Turn the System O will be displayed 2 Press SET to accept The unit will then go into standby mode 3 To fully shut down the unit press the On O Bu on Fig 1 C4 on the control p...

Страница 13: ...n the standard models The relays can ac vate external alarms and automa c start relays for second ary power systems and can be added as an op onal extra Please contact the manufacturer for further inf...

Страница 14: ...he control panel If using a second Fold Array parallel junc on box to connect mul ple arrays connect its output to the Solar Array 2 connectors 6 The LED indicator to the right of the connectors will...

Страница 15: ...connector from the unit Refer to Appendix 2 6 2 2 for further informa on on using the SPEC Pak connector 2 Disconnect the remaining cables and any junc on boxes 3 7 3 Charging with AC Grid Supply or S...

Страница 16: ...d be set as open Fig 1 C3 rotate switch an clockwise and Cygnus 2 as Termi nated Fig 1 C3 rotate switch clockwise 4 If using three units Cygnus 1 and Cygnus 2 should be set as Open Fig 1 C3 rotate swi...

Страница 17: ...and the third L3 Do not a empt to connect the units in series if this is not the case 3 Once the unit numbers have been determined posi on the three units with L1 on the le L2 in the centre and L3 on...

Страница 18: ...in the On posi on and none of them have tripped out 4 4 Turning O The Units 1 Using the RCC 03 Fig 1 C2 of Cygnus 1 Press Up then Down to wake up the control panel 2 Press the Esc bu on to choose to...

Страница 19: ...s can be obtained from the manufacturer 5 4 Tes ng It is recommend that the unit should be tested annually for safety by a quali ed electrician Local regula ons may require more frequent tes ng Please...

Страница 20: ...to adjust the se ng 4 Use the arrow keys to input the required voltage A maximum of 245V is available Press SET to accept 5 Press ESC to navigate back to the main menu and the arrow keys to return to...

Страница 21: ...e adapters and appliances 6 2 1 Connec ng the SPEC Pak Plug 1 The SPEC Pak socket is ed with a waterproof cover Fig 5 Step 1 2 Remove the cover by hinging up the retaining clip and pulling out Fig 5 S...

Страница 22: ...nected to the AC output socket The ba eries are kept at full capacity and are only used if there is a break in input voltage Fig 6 Example Showing A Single Unit Connected To An AC Feed and Powering Co...

Страница 23: ...sumers and any surplus power keeps the ba eries topped up Ba ery power is used when the consumers require more power than the solar arrays are genera ng Fig 7 Example Showing Arrays Directly Connected...

Страница 24: ...3 3 Three Phase Cygnus System Three pre con gured units are connected by means of data cables and a series junc on box available separately from the manufacturer Fig 9 Example Showing the Use of Thre...

Страница 25: ...11 Page 25 6 3 4 Two Unit Parallel Cygnus System Two units are connected by means of a data interlink cable and a parallel junc on box available separately Fig 10 Example Showing the use of Two Units...

Страница 26: ...al v3 0 2011 Page 26 6 3 5 Kinectrics PedGen Connected to Single Cygnus Fig 11 Example Showing the use of Two Kinectrics Units to Charge Cygnus Fig 12 Example Showing the use of Eight Kinectrics Units...

Страница 27: ...t s will automa cally switch out of this mode and the indi cators should stay on as long as power is being used Message on RCC 03 Ba ery Voltage Too Low This indicates that the voltage has reached its...

Страница 28: ...Solar Generator range To nd the relevant informa on for your unit please refer to the model number on its ra ng plate at the bo om of the le hand panel or the main graphics on each side of the unit T...

Страница 29: ...uso 20Xtender 20serie 20 It pdf RCC 03 English h p www studer innotec com upload temp RCC 02 03 20User 20manual pdf French h p www studer innotec com upload temp Manuel 20u lisateur 20RCC 02 03 pdf G...

Отзывы: