Cygnus User Manual
-
v3.0 2011
Page 20
6.1
Appendix 1
-
Addi onal RCC
-
03 Se ngs
The RCC
-
03 provides control over a number of Cygnus’ se ngs. Two useful se ngs including boos ng the voltage over dis-‐
tance and the language used in the display.
6.1.1 Boos ng the Voltage Over Distance
If the cable run between the unit and the AC consumers is more than 50m, a drop in voltage can occur. Failure to boost
the voltage can result in the consumers not receiving the required voltage.
To boost the voltage:
1.
Use the RCC
-
03 arrow keys (Fig. 1, C2) to navigate down to ‘Basic Se ngs’.
2.
Press SET to enter this sub
-
menu.
3.
Use the arrow keys to navigate down to ‘AC Voltage’. Press SET to adjust the se ng.
4.
Use the arrow keys to input the required voltage. A maximum of 245V is available. Press SET to accept.
5.
Press ESC to navigate back to the main menu and the arrow keys to return to the main screen.
6.1.2 Se ng the RCC
-
03 Language
1.
Press the down RCC
-
03 arrow key (Fig. 1, C2) to navigate to ‘Remote Controller Se ngs’.
2.
Press the SET key to enter the Remote Control Se ngs.
3.
The language choices menu is displayed.
4.
Press the SET key to modify the current language.
5.
Use the upwards and downwards arrow keys to select the required language.
6.
Confirm the selec on by means of the SET key (OK).
7.
Press ESC to leave the se ngs for the remote control.
When using the unit with cable runs of less than 50m a er boos ng the voltage, be sure to return the
unit to its default voltage se ng. Repeat the above steps and return the voltage to 230V in step 4.