WIRING & INSTALLATION NOTES
1)
There are no user-re quired set tings (switches, head ers) on the
FC410MIO.
2)
All con duc tors to be free of earths.
3)
All wir ing must con form to the ap pli ca ble standards.
4)
See Figs 3 and 4 for FC410MIO sim pli fied wir ing di a grams.
5)
For 24 Vdc pow ered ap pli ca tions, only use a reg u lated sup ply
suit able for fire pro tec tive sig nal ling ser vice.
6)
For pow ered cir cuit op er a tion, route the pos i tive con duc tor
through the FC410MIO to the ex ter nal de vice, while con nect -
ing the com mon (neu tral) con duc tor to the ex ter nal cir cuit.
7)
For dry con tact switch ing, con nect the ex ter nal cir cuit to the
COM and N/O or N/C ter mi nals for nor mally open or nor mally
closed op er a tion as re quired.
8)
Ver ify the cor rect po lar ity of wir ing be fore con nect ing the
FC410MIO to the ad dress able loop cir cuit.
9)
For con nec tion to HVR800s, re fer to doc u ment “HVR800 High
Volt age Re lay Mod ule - In stal la tion In struc tions” 17A-03-HVR,
Is sue 3 or later, or 120.415.528, Is sue 5 or later.
MOUNTING
To mount the FC410MIO to the elec tri cal hous ing, pro ceed as fol lows:
Ø
mount the FC410MIO PCB to the backbox us ing the screws
and stand-offs sup plied.
PORTA DI PROGRAMMAZIONE
PROGRAMMING PORT
CENTRALE FC
FC CONTROLLER
AL
D
IS
PO
SI
TI
VO
S
EG
UE
NT
E
TO
N
EX
T
DE
VI
CE
ZU
M
N
ÄC
HS
TE
N
EL
EM
EN
T
INGRESSI SPUR
SPUR INPUTS
EINGÄNGE
STICHLEITUNGEN
Ringleitung
HVR800-Treiber
HVR800-Drivers
FC410MIO
FC
L1
L1
LEFT
FIG. 3
SPUR cir cuits (Class B)
Nor mally Open
Con tacts,
Short Cir cuit = Fault.
Note:
1)
All SPUR in puts must be ter mi nated with a 330 ohm EOL
re sis tor.
2)
FireClass 500 con sole con fig u ra tion se lec tion - Style C
(Nor mally Open).
3)
One con tact for each SPUR cir cuit.
+
Notes:
1) For con
nec
tion of HVR800s, re
fer to doc
u
ment
HVR800 High Volt age Re lay Mod ule “In stal la tion
In
struc
tions” 17A-03-HVR, Is
sue 3 or later, or
120.415.528, Is sue 5 or later.
2) Re lay wir ing will be ap pli ca tion de pend ant; re fer to the
sys tem di a gram.
!
WARNING: THE FC410MIO MUST NOT BE USED TO
SWITCH MAINS VOLTAGES.
INGRESSI SPUR
SPUR INPUTS
EINGÄNGE
STICHLEITUNGEN
PORTA DI PROGRAMMAZIONE
PROGRAMMING PORT
CENTRALE FC
FC CONTROLLER
AL
D
IS
PO
SI
TI
VO
S
EG
UE
NT
E
TO
N
EX
T
DE
VI
CE
ZU
M
N
ÄC
HS
TE
N
EL
EM
EN
T
FC
FC410MIO
Ringleitung
HVR800-Treiber
HVR800-Drivers
L1
L1
LEFT
FIG. 4
SPUR cir cuits (Class B)
Nor mally Closed
Con tacts,
Short Cir cuit = Fault.
Note:
1)
All SPUR in puts must be ter mi nated with a 330 ohm EOL
re sis tor.
2)
FireClass 500 con sole con fig u ra tion se lec tion - Style C
(Nor mally Closed).
3)
One con tact for each SPUR cir cuit.
+
Notes:
1) For con
nec
tion of HVR800s, re
fer to doc
u
ment
HVR800 High Volt age Re lay Mod ule “In stal la tion
In
struc
tions” 17A-03-HVR, Is
sue 3 or later, or
120.415.528, Is sue 5 or later.
2) Re lay wir ing will be ap pli ca tion de pend ant; re fer to the
sys tem di a gram.
!
WARNING: THE FC410MIO MUST NOT BE USED TO