7
19
COMMISSIONING & BURNER
Enviromax
Model
Burner
Output
Blast
Tube
Steinen Nozzle
Pump
Pressure
Avg.
Fg ˚C
CO2
kW
BTU
Size
Angle
Type
Blue Flame
26
MHG RHE
1.26HG
26
89K
Standard
0.75
80˚
H
9 bar
60
13.5
BURNER
1. A 15micron filter must be fitted to the oil line.
2. All burners are supplied with a two pipe system.
3. Use Kerosene 28 Second Class C fuel only.
4. The minimum oil pump pressure for Kerosene 28 Second Class C fuel is 7 bar and the maximum is 10 bar.
5. The burner supplied with your Firebird Blue Flame condensing boiler has been factory set. For on-site commissioning,
only the pump pressure should be adjusted to achieve the correct CO
2
level (this is to allow for slight variations in caloric
value (cv) of the fuel).
The burner air setting should not be adjusted.
6. If the CO reading is greater than 40ppm when commissioning this boiler, contact the Firebird technical desk for
assistance before leaving the premises.
7. Use burner settings as indicated below.
These settings are specific to the Firebird Enviromax Blue Flame boilers.
HANDING OVER
The householder should receive:
•
A clear and concise demonstration of the boiler operation and any system controls.
•
This manual, the burner manufacturer's manual and any other instructions.
•
OFTEC forms CD10 and CD11.
•
The boiler passport.
The householder should be advised to:
•
Service the boiler annually and to ensure that the service records in the boiler passport are completed.
•
Read the terms and conditions of warranty.
•
Keep all boiler documentation in a safe place.
For burner technical details which are not covered in this manual, refer to the burner manufacturer’s manual.