LCD-80F Annunciator
Features of LCD-80F
7
Document 51338 Rev. B 08/24/05 P/N 51338:B
1.1
Features of LCD-80F
• 80-character LCD display (20 characters x 4 lines) is backlit
under normal and alarm conditions
• System Status LEDs for AC Power (green), Alarm (red), Trouble
(yellow), Supervisory (yellow) and Alarm Silenced (yellow)
• No programming necessary — duplicates messages at control
panel display.
Note: The FACP may require programming to function with the
LCD-80F. Refer to the specific FACP manual for programming
information
• Local piezo sounder with alarm and trouble resound
• Device type identifiers from the control panel
• Device & zone custom alpha labels from the control panel
• Time/date and device address from the control panel
• EIA-485 connects to control panel terminal port
• Plug-in terminal blocks for ease of installation and service
• DIP switches control piezo enable/disable, transmit/receive
mode, FACP selection, function switches and key-switch enable/
disable.
• Up to 32 LCD-80F Annunciators per FACP
• Mounting options:
Surface mounting in SBB-3 (2.75" depth) or three
electrical boxes ganged together
Semi-flush mounting in three-gang electrical box (P/N
10103) with a minimum depth of 2.187" or three electrical
boxes ganged together
Can be located up to 6,000 feet (1,800 m) from the panel
• Backlight turns off during AC loss to conserve battery power but
will turn back on if an alarm condition occurs.
• Enable/Disable key-switch
• Function switches for:
Acknowledge/Step
Alarm Silence
Drill
System Reset/Lamp Test