background image

PrecauSmall.PMD    01/10/2005

An automatic fire alarm system

–typically made up of

smoke detectors, heat detectors, manual pull stations,
audible warning devices, and a fire alarm control panel
with remote notification capability–can provide early
warning of a developing fire.  Such a system, how-
ever, does not assure protection against property dam-
age or loss of life resulting from a fire.

The Manufacturer recommends that smoke and/or heat
detectors be located throughout a protected premise
following the recommendations of the current edition of
the National Fire Protection Association Standard 72
(NFPA 72), manufacturer's recommendations, State
and local codes, and the recommendations contained in
the Guide for Proper Use of System Smoke Detectors,
which is made available at no charge to all installing
dealers.  A study by the Federal Emergency Manage-
ment Agency (an agency of the United States govern-
ment) indicated that smoke detectors may not go off
in as many as 35% of all fires.  While fire alarm sys-
tems are designed to provide early warning against
fire, they do not guarantee warning or protection
against fire.  A fire alarm system may not provide
timely or adequate warning, or simply may not func-
tion, for a variety of reasons:

Smoke detectors

 may not sense fire where smoke

cannot reach the detectors such as in chimneys, in or
behind walls, on roofs, or on the other side of closed
doors.  Smoke detectors also may not sense a fire on
another level or floor of a building.  A second-floor
detector, for example, may not sense a first-floor or
basement fire.

Particles of combustion or "smoke"

 from a develop-

ing fire may not reach the sensing chambers of smoke
detectors because:

• Barriers such as closed or partially closed doors,

walls, or chimneys may inhibit particle or smoke
flow.

• Smoke particles may become "cold," stratify, and

not reach the ceiling or upper walls where detectors
are located.

• Smoke particles may be blown away from detectors

by air outlets.

• Smoke detectors may be drawn into air returns be-

fore reaching the detector.

The amount of "smoke" present may be insufficient to
alarm smoke detectors.  Smoke detectors are designed
to alarm at various levels of smoke density.  If such
density levels are not created by a developing fire at
the location of detectors, the detectors will not go into
alarm.
Smoke detectors, even when working properly, have
sensing limitations.  Detectors that have photoelec-
tronic sensing chambers tend to detect smoldering
fires better than flaming fires, which have little visible
smoke.
Detectors that have ionizing-type sensing chambers
tend to detect fast-flaming fires better than smoldering
fires.  Because fires develop in different ways and are
often unpredictable in their growth, neither type of
detector is necessarily best and a given type of detec-
tor may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide
adequate warning of fires caused by arson, children
playing with matches (especially in bedrooms), smok-
ing in bed, and violent explosions (caused by escaping
gas, improper storage of flammable materials, etc.).

Heat detectors do not sense particles of combustion
and alarm only when heat on their sensors increases at
a predetermined rate or reaches a predetermined level.
Rate-of-rise heat detectors may be subject to reduced
sensitivity over time.  For this reason, the rate-of-rise
feature of each detector should be tested at least once
per year by a qualified fire protection specialist.  

Heat

detectors are designed to protect property, not life.

IMPORTANT! 

 Smoke detectors 

must be installed in

the same room as the control panel and in rooms used
by the system for the connection of alarm transmission
wiring, communications, signaling, and/or power.

  If

detectors are not so located, a developing fire may
damage the alarm system, crippling its ability to report
a fire.

Audible warning devices

 such as bells may not alert

people if these devices are located on the other side of
closed or partly open doors or are located on another
floor of a building.  Any warning device may fail to
alert people with a disability or those who have re-
cently consumed drugs, alcohol or medication.  Please
note that:

• Strobes can, under certain circumstances, cause

seizures in people with conditions such as epilepsy.

• Studies have shown that certain people, even when

they hear a fire alarm signal, do not respond or
comprehend the meaning of the signal.  It is the
property owner's responsibility to conduct fire drills
and other training exercise to make people aware of
fire alarm signals and instruct them on the proper
reaction to alarm signals.

• In rare instances, the sounding of a warning device

can cause temporary or permanent hearing loss.

A fire alarm system

 will not operate without any

electrical power.  If AC power fails, the system will
operate from standby batteries only for a specified
time and only if the batteries have been properly main-
tained and replaced regularly.

Equipment used in the system

 may not be techni-

cally compatible with the control.  It is essential to use
only equipment listed for service with your control
panel.

Telephone lines

 needed to transmit alarm signals

from a premise to a central monitoring station may be
out of service or temporarily disabled.  For added
protection against telephone line failure, backup radio
transmission systems are recommended.

The most common cause

 of fire alarm malfunction is

inadequate maintenance.  To keep the entire fire alarm
system in excellent working order, ongoing mainte-
nance is required per the manufacturer's recommenda-
tions, and UL and NFPA standards.  At a minimum, the
requirements of NFPA 72 shall be followed.  Environ-
ments with large amounts of dust, dirt or high air ve-
locity require more frequent maintenance.  A mainte-
nance agreement should be arranged through the local
manufacturer's representative.  Maintenance should be
scheduled monthly or as required by National and/or
local fire codes and should be performed by authorized
professional fire alarm installers only.  Adequate writ-
ten records of all inspections should be kept.

While a fire alarm system may lower insurance
rates, it is not a substitute for fire insurance!

Fire Alarm System Limitations

Содержание LCD-80F

Страница 1: ...Remote Fire Annunciator LCD 80F PN 51338 B ECN 06 297 Document 51338 08 24 05 Rev B...

Страница 2: ...and violent explosions caused by escaping gas improper storage of flammable materials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a...

Страница 3: ...hnical Services Department if any problems are anticipated or encountered Disconnect AC power and batteries prior to removing or inserting circuit boards Failure to do so can damage circuits Remove al...

Страница 4: ...ith the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems UL 864 9th Edition Operation of this product with products not tested for UL 864 9th Edition has not been...

Страница 5: ...ch 16 2 2 2 Acknowledge Step 16 2 2 3 Silence 17 2 2 4 Drill Hold 2 Sec 17 2 2 5 Reset 17 2 3 LED Indicators 18 2 3 1 AC Power 18 2 3 2 Alarm 18 2 3 3 Supervisory 18 2 3 4 Trouble 18 2 3 5 Alarm Silen...

Страница 6: ...Alarm Trouble Supervisory and Alarm Silenced conditions The LCD 80F is capable of performing system acknowledge silence drill and reset remotely Communication between the FACP and the LCD 80F is accom...

Страница 7: ...he control panel Time date and device address from the control panel EIA 485 connects to control panel terminal port Plug in terminal blocks for ease of installation and service DIP switches control p...

Страница 8: ...e DIP Switch Settings Example on page 13 The LCD 80F sounder if enabled will be activated when any new alarm or trouble is received from the panel It is silenced by an Acknowledge switch Piezo must no...

Страница 9: ...e Refer to illustrations on the following page for LCD 80F connections to the MS 9200UD and MS 9600 MS 9200UD TB8 MS 9600 TB7 LCD 80F P1 Connector Terminal 2 IN Terminal 5 IN Terminal 1 OUT Terminal 4...

Страница 10: ...08 24 05 P N 51338 B LCD 80F MS 9200UD Figure 1 3 FACP EIA 485 Wiring to LCD 80F EIA 485 Out to Next Device EIA 485 Out to Next Device or back to FACP EIA 485 EIA 485 Out to Next Device EIA 485 Out t...

Страница 11: ...Supervision Receive Transmit OFF Supervision Receive Only One Annunciator if a single LCD 80F is the only annunciator connected to the EIA 485 loop Switch 3 must be set to the ON position to allow th...

Страница 12: ...appropriate switch settings Programming Note Depending on the FACP which is connected to the LCD 80F it may be necessary to enable communication with the annunciator in the FACP programming Refer to...

Страница 13: ...r function 2 DIP switch 2 OFF piezo sounder disabled requires approval of LAHJ 3 DIP switch 3 OFF Receive Only This setting is used for all annunciators except the last or only LCD 80F Annunciator on...

Страница 14: ...he last LCD 80F back to the FACP 2 Up to 32 LCD 80F Annunciators may be used on the EIA 485 circuit Refer to the specific FACP manual to determine the maximum current available for powering the LCD 80...

Страница 15: ...a period of over 30 seconds it will activate its local sounder if so programmed and display the following message A Communication Fault may be due to one of the following conditions FACP has not been...

Страница 16: ...abled position fully counterclockwise with the key removed and access to the key restricted to authorized personnel only Do not leave the key unattended in the LCD 80F 2 2 2 Acknowledge Step When the...

Страница 17: ...or at least two seconds time required to prevent accidental activations the LCD 80F will transmit a drill command to the control panel This command causes the FACP to turn on all NAC outputs and all s...

Страница 18: ...or more supervi sory conditions occur such as a sprinkler valve tamper condition It turns off when the Reset switch is pressed 2 3 4 Trouble This is a yellow LED that turns on steady when one or more...

Страница 19: ...depending on the type of installation desired Be certain that power is not applied to the wiring during the installation procedure Note To ensure static protection all enclosures including the LCD 80F...

Страница 20: ...UNCIATOR Alm Silenced Supervisory Trouble Alarm AC Power Figure 3 2 Hardware and Backboxes LCD 80F flange LCD 80F Trim Ring replacement P N 23165 3 Gang Electrical Box P N 10103 semi flush mount 3 Gan...

Страница 21: ...place the trim ring and secure with the two screws which were previously loosened Adjust the plastic trim ring to the surface of the wall before tightening the screws Do not overtighten Ack Step Silen...

Страница 22: ...ur screws provided for this purpose Replace the trim ring and secure with the two screws which were previously loosened Adjust the plastic trim ring to the surface of the wall before tightening the sc...

Страница 23: ...on page 13 Carefully insert the LCD 80F into the three gang electrical box and attach it using the four mounting holes on the LCD 80F flange and the four screws provided for this purpose Replace the...

Страница 24: ...ator Maximum LCD 80F current draw from the power supply under normal and alarm conditions is 64 3 mA Maximum current draw from the control panel s secondary power source batteries under loss of AC pow...

Страница 25: ...er strongly recommended that the power and communication wires be separate whenever possible 5 Ferrite Core P N FBD 1 is required to meet FCC Part 15 require ments if the EIA 485 wiring is not in cond...

Страница 26: ...as 120 VAC service noisy elec trical circuits that are powering mechanical bells or horns audio circuits above 25 VRMS motor control circuits or SCR power circuits Note To ensure static ESD electrosta...

Страница 27: ...annunciator must be left floating The shield entering the second annunciator must be connected to the three gang box or Earth Ground terminal P2 7 on the second annunciator If additional annunciators...

Страница 28: ...nciator must be left floating and the shield entering the following unit must be connected to the Earth Ground terminal P2 7 on the annunciator Caution Do not allow the floating shield end no connecti...

Страница 29: ...r maximum 14 application see also typical configuration 14 B backboxes 7 19 backlit 6 7 C communication 6 11 communication failure 15 Communication Fault 15 components 8 configuration see also FACP se...

Страница 30: ...FACP selection 12 Fault 15 FCC Part 15 requirements 25 ferrite core 25 flange 21 23 function switches 7 11 see also switch functions 16 G grounding 19 26 28 K key switch 11 16 L LAHJ 8 11 LCD display...

Страница 31: ...communication 11 reset switch 6 7 16 17 resound piezo 7 S SBB 3 backbox 19 21 semi flush mounting 21 shield no conduit 27 see also EIA 485 26 silence switch 6 16 17 specifications 9 static protection...

Страница 32: ...P N 51338 B three ganged electrical boxes 22 trim ring 19 20 21 22 23 trouble LED 6 7 18 typical configuration 14 W wiring 8 9 conduit 28 distance 25 EIA 485 25 ferrite core 25 no conduit 27 power 24...

Страница 33: ...33 Document 51338 Rev B 08 24 05 P N 51338 B Notes...

Страница 34: ...Notes 34 Document 51338 Rev B 08 24 05 P N 51338 B...

Страница 35: ...ial Authorization form from our Return Authorization Department This writing constitutes the only warranty made by the manufacturer with respect to its products The manufacturer does not represent tha...

Страница 36: ...rters One Fire Lite Place Northford CT 06472 1653 USA 203 484 7161 Fax 203 484 7118 www firelite com 2005 by Honeywell International Inc All rights reserved Unauthorized use of this document is strict...

Отзывы: