background image

F300-11-00                                                                                                    4                                                                                              I56-0047-005R

F300-11-00                                                                                                    5                                                                                              I56-0047-005R

[4.2] Installation For Ducts More Than 8 Feet Wide

NOTE:

  To install sampling tubes in ducts more than 8 feet wide, work must be performed inside the air duct. Sampling 

of air in ducts wider than 8 feet is accomplished by using the ST-10 sampling tube. If the tube is shorter than 
the width of the air duct, install the end cap into the sampling tube as shown in Figure 4 and support the end 
opposite the duct smoke detector.

Install the sampling tube as follows:

1. Drill a 

3

⁄4

-inch hole in the duct directly opposite the hole already drilled for the sampling tube. Make sure the hole is 

1

 to 2

 below the inlet hole on the opposite side of the duct to allow for moisture drainage.

2. Slide the sampling tube with the flange into the housing bushing that meets the air flow first. Position the tube so that 

the arrow points into the air flow. Secure the tube flange to the housing bushing with two #6 self-tapping screws.

3. From inside the duct, couple the other sections of the sampling tube to the section already installed using the 

1

⁄2

-inch 

conduit fittings supplied. Make sure that the holes on both of the sampling tubes are lined up and facing into the air 
flow.

4. Trim the end of the tube protruding through the duct so that 1

 to 2

 of the tube extend outside the duct. Plug this end 

with the end cap and tape closed any holes in the protruding section of the tube. Be sure to seal the duct where the 
tube protrudes.

NOTE:

  An alternate method to using the ST-10 is to use two ST-5 sampling tubes. Remove the flange from one of the 

tubes and install as described above. After the installation, use electrical tape to close off some of the sampling 
holes so that there are a total of 10 to 12 holes spaced as evenly as possible across the width of the duct.

NOTE:

  Air currents inside the duct may cause excessive vibration, especially when the longer sampling tubes are used. 

In these cases a 3 inch floor flange (available at most plumbing supply stores) may be used to fasten the sam-
pling tube to the other side of the duct. When using the flange/connector mounting technique, drill a 1-inch to    
1

1

⁄4

-inch hole where the flange will be used.

Figure 6. Sampling tube filter installation:

Wiring connections are made by stripping about 

3/8

-inch of insulation from the end of the wire, sliding the bare end under 

the plate, and tightening the clamping plate screw. 

Two LEDs on each duct smoke detector may light, if programmed by the system control panel, to provide a local, visible 
indication.  Remote LED annunciator capability is available as an option. Each duct smoke detector can only be wired 
to one remote accessory.

Panels  offer  different  feature  sets  across  different  panel  models.    As  a  result,  certain  features  of  the  D350RP  may  be 
available on some control panels, but not on others.  The possible features available in the D350RP, if supported by the 
control panel are:  
1. Panel controls the LED operation on the duct smoke detector.  Operational modes are RED blink, RED continuous, 

GREEN blink, GREEN continuous, and off.  

2. The remote output may be synchronized to the LED operation or controlled independent of the LEDs. 

Please refer to the operation manual for the UL listed control panel for specific operation of the D350RP. 

Wiring Instructions

Disconnect power from the communication line before installing the D350RP duct smoke detectors.  

Wire the D350RP duct smoke detector per the Control Panel Installation Manual 
and Figures 8, 9 or 10. Set the desired address on the sensor board code wheel 
address switches.

NOTE:

  Some panels support extended addressing. In order to set the sensor above 

address number 99 on compatible systems, remove the breakaway stop 
on the left hand rotary switch. Using pliers, carefully twist and pull off 
stop as shown in Figure 7.

[7] Perform Detector Check 

1. Perform STANDBY AND TROUBLE TEST per Section [9.2.1].
2. Perform MAGNET TEST per Section [9.2.2.1]. The RTS451 test of Section [9.2.2.2] may substitute for this requirement. 
3. Perform AIR FLOW TEST per Section [9.1].
4. Perform SMOKE RESPONSE TEST per Section [9.1.1].

[8] Install The Cover

 

Install the cover using the six screws that are captured in the housing cover. Be certain filters are installed as specified in 
Section [5]. Make sure that the cover fits into the base groove and that all gaskets are in their proper positions. Tighten 
the six screws.

[9] Duct Smoke Detector Maintenance and Test Procedures

Test and maintain duct smoke detectors as recommended in NFPA 72. The tests contained in this manual were devised 
to assist maintenance personnel in verification of proper detector operation. 

Before conducting these tests, notify the proper authorities that the smoke detection system will be temporarily out of 
service. Disable the device or system under test to prevent unwanted alarms.

Smoke Entry Tests

[9.1] Air Flow

To verify sufficient sampling of ducted air, use a manometer to measure the differential pressure created from air flow 
across the sampling tubes. The pressure should measure no less than 0.03 inches of water and no greater than 1.4 inches 
of water. The air handler must be operating for this test.

[9.1.1] Smoke Response

To determine if smoke is capable of entering the sensing chamber, visually identify any obstructions. Plug the exhaust 
and sampling tube holes to prevent ducted air from carrying smoke away from the detector head, then blow smoke such 
as cigarette, cotton wick, or punk directly at the head to cause an alarm. REMEMBER TO REMOVE THESE PLUGS AFTER 
THIS TEST, OR THE DETECTOR WILL NOT FUNCTION PROPERLY.

[5] Install The Filters 

To install the sampling tube filters, simply push the filters 
into  the  sampling  and  exhaust  tube  holes,  as  shown  in 
Figure 6. If a metal sampling tube is used, install the filters 
over the tube end.

[6] Field Wiring Installation Guidelines

All  wiring  must  be  installed  in  compliance  with  the 
National Electrical Code and the local codes having juris-
diction. Proper wire gauges should be used. The conduc-
tors used to connect smoke detectors to control panels and 
accessory devices should be color-coded to prevent wiring 
mistakes. Improper connections can prevent a system from 

responding properly in the event of a fire.

CAUTION

Filters require periodic cleaning or replacement, depending on the amount of dust and dirt accumulated. Visually inspect 
the filters at least quarterly; inspect them more often if the dust accumulation warrants it. See Section [9.1.2] for more 
information. Replacement filters can be ordered (filter P/N F36-09-11).

For signal wiring, (the wiring between detectors or from detectors to auxiliary devices), it is usually recommended that 
single conductor wire be no smaller than 18 gauge. The duct smoke detector terminals accommodate wire sizes up to 12 
gauge. The last foot of conduit should be flexible conduit (available in electrical supply houses), which facilitates easier 
installation and puts less strain on the conduit holes in the housing. Solid conduit connections may be used if desired.

Smoke detectors and alarm system control panels have specifications for Signaling-Line Circuit (SLC) wiring. Consult the 
control panel manufacturer’s specifications for wiring requirements for the particular model control panel being used 
before wiring the detector loop.

The D350RP detector is designed for ease of wiring. The housing provides a terminal strip with clamping plates.

BREAKAWAY STOP

Figure 7. Rotary Address Switches

Содержание D350RP

Страница 1: ...53FL Replacement Power Board w relay A5060 Accessory Current Loads at 24 VDC Device Standby Alarm PA400 0 mA 15 mA Max RA400Z 0 mA 12 mA Max RTS451 RTS451KEY 0 mA 10 mA Max Contact Ratings Alarm auxiliary contacts DPDT 10 A 30 VDC 10 A 277 VAC 75 power factor 240 VA 249 VAC 0 4 power factor 1 8 HP 120 VAC 1 4 HP 240 VAC Supervisory contact SPST 2 0 A 30 VDC resistive Minimum switching current for ...

Страница 2: ...ED AS A SUBSTITUTE FOR OPEN AREA DETECTOR PROTECTION as a means of providing life safety Nor are they a substitute for early warning in a building s regular fire detection system It is strongly recommended that the user read NFPA Standards 90A 72 and 101 WARNING This device will not operate without electrical power Fire situations may cause an interruption of power The system safeguards should be ...

Страница 3: ...timal performance The exhaust tube is molded onto the base of the duct housing and the A2440 00 Exhaust Tube Extension is available as an accessory in those cases where the molded exhaust port does not extend at least 2 inches into the duct The sampling tube is always installed with the air inlet holes facing into the air flow To assist proper installation the tube s mounting flange is marked with...

Страница 4: ...r to set the sensor above address number 99 on compatible systems remove the breakaway stop on the left hand rotary switch Using pliers carefully twist and pull off stop as shown in Figure 7 7 Perform Detector Check 1 Perform STANDBY AND TROUBLE TEST per Section 9 2 1 2 Perform MAGNET TEST per Section 9 2 2 1 The RTS451 test of Section 9 2 2 2 may substitute for this requirement 3 Perform AIR FLOW...

Отзывы: