The JA-82ST wireless combined smoke and heat detector 

 

MZZ57300 

 

The JA-82ST wireless combined smoke and heat 

detector

  

The JA-82ST is a wireless component of the JABLOTRON ALARMS 

OASIS security system. It is used to detect fire hazards in the interior of 
residential or commercial buildings. It is not designed to be installed in 
industrial premises. The JA-82ST detector uses wireless communication 
and it is powered with three AA 1.5V alkaline batteries. 

The JA-82ST consists of two independent detectors – an optical 

smoke detector and a heat detector. The optical smoke detector works on 
the principle of scattered light and is very sensitive to large dust particles 
which are present in dense smoke. It is less sensitive to smaller particles 
generated by the combustion of liquids such as alcohol. That is why there 
is also a built-in heat detector which has a slower reaction but is much 
better at detecting fire which generates heat quickly with a small amount 
of smoke. The microprocessor performs digital analysis of these values 
which markedly increases false alarm immunity. 

Detector range 

The smoke detector must be installed so that any smoke easily drifts 

into the detector, e.g. on the ceiling. It is suitable for residential buildings 
but not suitable for free spaces, outdoor environments or interiors with 
extremely high ceilings (above 5 m) where fire by-products can disperse 
over a large area – the smoke would not reach the detector position. 

The detector must always be placed in the section leading to the exit 

of the building (escape route), see Figure 1. If the building has a floor 
area greater than 150 m2, installation of an additional detector in some 
other suitable place is required, see Fig.2.  

 

1

2

3

3

4

 

Fig 1 

2

1

3

3

4

3

 

Fig 2 

1-kitchen 
2-living room 
3-bedroom 
4-children’s bedroom 
 

- Basic security 

- For more security 

 

 

1

3

3

3

 

Fig 3 

For large buildings it is recommended to place additional detectors in 

rooms where people sleep and in rooms with an increased risk of fire - 
see Fig.3. 

Installation on level ceilings 

Place the detector in the centre of the room if possible. The detector 

must not be recessed into the ceiling due to the possible existence of a 
cool air layer on the ceiling. 

Never place the detector in the corner of 

the room though

 (always keep at least a 0.5 m distance from the corner) 

see Fig 4. 

Installation on sloping ceilings 

If the ceiling is not suitable for mounting on a level surface (e.g. a 

room under a roof ridge), the detector can be installed as in Fig. 5 

0.5m

TOP

 

Fig 4 

 

0,9 m

 

 

Fig 5 

 centre of the room, best location  

acceptable location 

Walls, partitions, barriers and lattice ceilings 

The JA-82ST detector must not be installed closer than 0.5 m 

from any wall or partition. 

A narrow room with a width of less than 1.2m 

requires the detector(s) to be placed at a distance of at least one third of 
the room’s width away. In the case of separating walls (partitions, 
warehouse objects) which do not reach the ceiling, 

the space is 

considered to be fully separated if the gap between the top of the 
separating wall and the ceiling does not exceed 0.3 m.

 A free space 

of at least 0.5m is required under the detector. Any irregularities of the 

ceiling (e.g. girders) exceeding 5 % of the ceiling height shall be 
considered a wall and the above mentioned limitations shall apply.  

Ventilation and air circulation 

The detectors must not be installed directly by a fresh air inlet 

(e.g. air conditioning vents).

 In the case of air being supplied through a 

perforated ceiling, each detector must be placed so that no perforation 
hole occurs within 0.6m of the detector. 

Avoid installing the detector in the following locations:

 

  places with poor air circulation (niches, corners, apexes of A-

shaped roofs, etc.) 

 

places exposed to dust, cigarette smoke or steam 

  places with over-intense air circulation (close to ventilators, heat 

sources, air conditioning outlets, etc.) 

 

in kitchens and other cooking places (because steam, smoke or oily 
fumes can reduce detector sensitivity). 

  beside fluorescent lights (electrical interference can cause a false 

alarm) 

 

in areas with lots of small insects 

 

Please note: Most false alarms are caused by improper 

detector location.

 

See CEN/TS 54-14 standards for detailed installation guidelines.

 

 

Installation 

The detector should be installed by a trained technician with a valid  

certificate issued by an authorized distributor. Abide by the procedures 
recommended in the previous paragraphs.  

 

1

2

3

1400- 00- 0000- 00 01

5

4

6

INS
MEM
SMOKE
TEMP

+

-

7

 

Fig 6: 1– detector cover opening; 2 – detector cover closing; 3 – optical status 

signalling; 4 – arrow showing where to insert the detector; 5 – enrollment code; 6 – 

configuration terminals; 7 – battery holders    

 

1. 

open the detector cover, by turning it anti-clockwise (1)

 

2. 

attach the removed plastic base

 to the desired place with screws (not 

shown above). 

3. 

set the configuration terminals (6) according to the table below.

 

4.  Proceed according to the control panel installation manual. Basic 

procedure: 

a.  Switch on the enrollment mode in the control panel.  
b.  When you insert all batteries into the detector, the enrollment code 

is sent to the system – its sending is confirmed with a short flash of 
the LED indicator (3). 

c.  The control panel confirms the enrollment with a flashing of the “A“ 

LED on the system keypad at the corresponding position.  

5.  Insert the detector into the plastic base. The detector can be inserted in 

the plastic base in one position only. It is marked with arrows (4) on both 
plastic parts. Close the detector cover by turning it clockwise (2).  

Note

: The detector can also be enrolled into the system by entering its 

enrollment code (5) in the O-Link program. (Enter the last 8 digits under 
the bar code). 

Detector setting 

The detector properties can be set in the 

Detectors

 window in the  

O-Link

 program and with the configuration terminals. 

 

ON 

Instant alarm

 

3 OFF 

1

OFF 

Fire alarm

 

4 OFF

 

smoke (EN 54-7) or 
heat (EN 54-5)

 

ON 

memory enabled

 

3 ON 

2

OFF 

memory disabled

 

4 OFF 

smoke only (EN 54-7) 
(not heat)

 

3 OFF 
4 ON 

heat only (EN 54-5) (not 
smoke)

 

3 ON 

1

2
3
4

INS
MEM
SMOKE
TEMP

 

ON

OFF

 

4 ON 

Both smoke and heat 
(both conditions at the 
same time)

 