[9.1.2] Filter Replacement

The filters do not substantially affect smoke performance even when up to 90% of the filter is clogged. Quarterly visual 
inspection usually suffices to determine whether the filters should be replaced because only a high percentage of con-
tamination affects performance. If further testing is required, compare differential pressure readings with and without 
the filters installed using a manometer. If the difference exceeds 10%, replace the filters. In no case should the pressure 
differential fall below 0.03 inches of water.

[9.2] Standby, Alarm, And Sensitivity Tests
[9.2.1] Standby And Trouble

Standby —    If programmed by the system control panel, look for the presence of the flashing LEDs through the transpar-

ent housing cover.  The LED will flash with each communication. 

Trouble —     If programmed by the system control panel and if the detector LEDs do not flash, then the detector lacks 

power (check wiring, panel programming, or power supply), the detector board is missing (replace), or the 
unit is defective (return for repair). Additionally, if the cover is removed for more than 20 minutes, the LEDs 
of the detector will not flash.

Test —          The trouble condition can be caused intentionally to verify correct operation of the system. Remove the 

detector board to cause a trouble condition locally and at the system control panel.

F300-11-00                                                                                                    6                                                                                              I56-0047-005R

Figure 8.  Wiring Diagram for D350RP Duct Smoke 
Detector using a UL listed control panel

Figure 10. System Wiring Diagram 
for D350RP Duct Smoke Detector 
with RTS451/RTS451KEY

Figure 9. Wiring Diagram for D350RP Duct Smoke 
Detector with optional RA400Z

+

COM (+)

COM (-)

COM (+)

COM (-)

COMMUNICATION

LINE

UL LISTED CONTROL

PANEL

1ST DETECTOR

IN LOOP

2ND DETECTOR

IN LOOP

1 2

1 2

J1 JUMPER

J1 JUMPER

COIL NOTE

Please  note  that  the  magnetic  coil  supplied  with  the  RTS451  and  RTS451KEY 

is not 

required 

when these accessories are used with the D350RP detectors. The functionality 

of the magnetic coil has been designed into the circuitry of the duct smoke detector.

5 7

RA400Z

5 = Alarm Signal
7 = Aux. Power (–)

DO NOT BREAK TAB ON RA400Z

NOTE:

    J1  jumper  must  be  removed  for 

power  board  supervision.  The  J1  jumper 
must be installed for 2W applications.

ALARM SIGNAL

AUX. POWER (–)

TEST +

TEST –

ALARM SIGNAL

NOT USED

NOT USED

CIRCUIT

REFERENCE

TEST

SWITCH

FOR RTS451, TERMINAL 3 IS NOT 

USED. (RTS451 DOES NOT HAVE 

A TERMINAL 6.) FOR RTS451KEY, 

TERMINALS 3 AND 6 ARE NOT USED.

RTS 451/RTS451KEY

5

7

4

3

1

3

6

2

4

5

[3] Secure The Detector Housing To The Duct

Slide the foam gaskets over the tube bushings as shown in 
Figure Use the two 1

1/4

” long sheet metal screws to screw 

the detector housing to the duct. 

CAUTION: Do not overtighten the screws.

[4] Sampling Tube Installation for Ducts Greater 
Than 1

1⁄2

 Feet Wide

The sampling tube is identified by a series of air inlet holes 
on the tube. A plastic tube is included for ducts up to 1

1

⁄2

  

feet wide. All other lengths must be purchased separately. 
Order the correct length, as specified in Table 1, for width 
of  the  duct  where  it  will  be  installed.  It  is  recommended 
that the sampling tube length extend at least 

2

⁄3

 across the 

duct  width  for  optimal  performance.  The  exhaust  tube  is 
molded onto the base of the duct housing, and the A2440-
00 Exhaust Tube Extension is available as an accessory in 
those cases where the molded exhaust port does not extend 
at least 2 inches into the duct. 

The  sampling  tube  is  always  installed  with  the  air  inlet 
holes facing into the air flow. To assist proper installation, 
the tube’s mounting flange is marked with an arrow. Make 
sure the sampling tube is mounted so that the arrow points 
into the air flow (see Figure 4). Figure 5 shows the various 
combinations of tube mounting configurations with respect 
to air flow. Mounting the detector housing in a vertical ori-
entation is acceptable, provided that a metal sampling tube 
is  used  and  the  air  flows  directly  into  the  sampling  tube 
holes as indicated in Figure 4.

[4.1] Installation For Ducts Greater Than 1

1⁄2

 Feet But 

Less Than 8 Feet Wide

1. 

If the tube is longer than the width of the air duct, drill a 

3

⁄4

 hole in the duct opposite the hole already cut for the 

sampling tube. Make sure the hole is 1

 to 2

 below the 

inlet hole on the opposite side of the duct to allow mois-
ture drainage away from the detector. 

If the tube is shorter 

than the width of the air duct,

 install the end cap into the 

sampling tube as shown in Figure 4. Sampling tubes over 
3 ft. long must be supported at the end opposite the duct 
smoke detector.

2. Slide the tube into the housing bushing that meets the 

air flow first. Position the tube so that the arrow 

    points into the air flow, as shown in Figure 4. 
3. Secure the tube flange to the housing bushing with two 

#6 self-tapping screws.

4. For tubes longer than the width of the air duct, the tube 

should  extend  out  of  the  opposite  side  of  the  duct.  If 
there  are  more  than  2  holes  in  the  section  of  the  tube 
extending out of the duct, select a different length using 
Table 1. Otherwise, trim the end of the tube protruding 
through the duct so that 1

 to 2

 of the tube extend out-

side the duct. Plug this end with the end cap and tape 
closed any holes in the protruding section of the tube. 
Be sure to seal the duct where the tube protrudes.

F300-11-00                                                                                                    3                                                                                              I56-0047-005R

SCREW HOLES FOR
ATTACHING HOUSING
TO DUCT WORK.

Figure 3. Installation of foam gaskets over sampling 
tube bushings:

Figure 5. Tube mounting configurations with varying 
air flow direction:

Table 1. Sampling tubes recommended for different 
Duct Widths:

  Outside Duct Width      Sampling Tube Recommended*

1 to 2 ft. (0.3 to 0.6 m)                  ST-1.5
2 to 4 ft. (0.6 to 1.2 m)                    ST-3
4 to 8 ft. (1.2 to 2.4 m)                    ST-5

8 to 12 ft. (2.4 to 3.7 m)                  ST-10

*Must extend a minimum of 

2

3

 the duct width

SAMPLING

TUBE

END CAP

AIR HOLES

ARROW

MUST FACE

INTO AIR FLOW

AIR FLOW DIRECTION

FLANGE

Figure 4. Air duct detector sampling tube:

AIR FLOW

DIRECTION

DETECTOR

HOUSING

DOTS INDICATE POSITION OF

SAMPLING TUBE HOLES

AIR FLOW

DIRECTION

DETECTOR

HOUSING

SAMPLING

TUBE

EXHAUST

TUBE

AIR FLOW

DIRECTION

EXHAUST

TUBE

SAMPLING

TUBE

SAMPLING

TUBE

EXHAUST

TUBE

DETECTOR

HOUSING

AIR FLOW

DIRECTION

DETECTOR

HOUSING

A.

B.

C.

D.

HORIZONTAL MOUNTING OF HOUSING

VERTICAL MOUNTING OF HOUSING

NOTE: Only metal sampling tubes can be installed in 
orientations C and D.

NOTE: 

The sampling tube end cap is critical to the proper 

operation  of  the  duct  smoke  detectors.  The  end  cap  is 
needed to create the proper air flow to the sensor of the 
duct smoke detector.

Содержание D350RP

Страница 1: ...53FL Replacement Power Board w relay A5060 Accessory Current Loads at 24 VDC Device Standby Alarm PA400 0 mA 15 mA Max RA400Z 0 mA 12 mA Max RTS451 RTS451KEY 0 mA 10 mA Max Contact Ratings Alarm auxiliary contacts DPDT 10 A 30 VDC 10 A 277 VAC 75 power factor 240 VA 249 VAC 0 4 power factor 1 8 HP 120 VAC 1 4 HP 240 VAC Supervisory contact SPST 2 0 A 30 VDC resistive Minimum switching current for ...

Страница 2: ...ED AS A SUBSTITUTE FOR OPEN AREA DETECTOR PROTECTION as a means of providing life safety Nor are they a substitute for early warning in a building s regular fire detection system It is strongly recommended that the user read NFPA Standards 90A 72 and 101 WARNING This device will not operate without electrical power Fire situations may cause an interruption of power The system safeguards should be ...

Страница 3: ...timal performance The exhaust tube is molded onto the base of the duct housing and the A2440 00 Exhaust Tube Extension is available as an accessory in those cases where the molded exhaust port does not extend at least 2 inches into the duct The sampling tube is always installed with the air inlet holes facing into the air flow To assist proper installation the tube s mounting flange is marked with...

Страница 4: ...r to set the sensor above address number 99 on compatible systems remove the breakaway stop on the left hand rotary switch Using pliers carefully twist and pull off stop as shown in Figure 7 7 Perform Detector Check 1 Perform STANDBY AND TROUBLE TEST per Section 9 2 1 2 Perform MAGNET TEST per Section 9 2 2 1 The RTS451 test of Section 9 2 2 2 may substitute for this requirement 3 Perform AIR FLOW...

Отзывы: