![Fire-Lite APS-6RF Скачать руководство пользователя страница 20](http://html.mh-extra.com/html/fire-lite/aps-6rf/aps-6rf_instruction-manual_2291040020.webp)
Appendix B: Sensiscan 2000
Connecting the APS-6RF to an MPS-24AF
20
APS-6RF Instruction PN 50893:B 7/20/00
Connecting the APS-6RF to an MPS-24AF
Make the following connections as shown in the figure below.
• Connect primary power from
TB1
to MPS-24AF terminal block
TB1
, Pin
5
(
NEUT
) and Pin
7
(
HOT
)
• Connect secondary power from
TB3
to MPS-24AF terminal block
TB2
, Pin
1
(+) and Pin
2
(–)
• Connect trouble input from
J3
to MPS-24AF terminal block
P5
Figure 12 Wiring to MPS-24AF
P4
P3
JP5
TB1
TB2
F1
CB1
P5
R27
P2
EA RT H G ND A C NE U T RA L A C HOT
+ 24 R CO MM ON +24 COMMON
POW ER L IM IT E D
BAT + BAT -
J2
J9
J3
J1
TB2
JP3
JP2
APS
-6
R t
o
M
P
S-
2
4
A
.c
d
r