Fire-Lite APS-6RF Скачать руководство пользователя страница 2

LimWarSm.p65    01/10/2000

An automatic fire alarm system

–typically made up of

smoke detectors, heat detectors, manual pull stations,
audible warning devices, and a fire alarm control with
remote notification capability–can provide early warning
of a developing fire.  Such a system, however, does not
assure protection against property damage or loss of life
resulting from a fire.

The Manufacturer recommends that smoke and/or heat
detectors be located throughout a protected premise
following the recommendations of the current edition of
the National Fire Protection Association Standard 72
(NFPA 72), manufacturer's recommendations, State and
local codes, and the recommendations contained in the
Guide for Proper Use of System Smoke Detectors, which
is made available at no charge to all installing dealers.
A study by the Federal Emergency Management Agency
(an agency of the United States government) indicated
that smoke detectors may not go off in as many as 35%
of all fires.  While fire alarm systems are designed to
provide early warning against fire, they do not guarantee
warning or protection against fire.  A fire alarm system
may not  provide timely or adequate  warning,  or  simply
may not function, for a variety of reasons:

Smoke detectors

 may not sense fire where smoke

cannot reach the detectors such as in chimneys, in or
behind walls, on roofs, or on the other side of closed
doors.  Smoke detectors also may not sense a fire on
another level or floor of a building.  A second-floor
detector, for example, may not sense a first-floor or
basement fire.

Particles of combustion or "smoke"

 from a developing

fire may not reach the sensing chambers of smoke
detectors because:

Barriers such as closed or partially closed doors,
walls, or chimneys may inhibit particle or smoke flow.

Smoke particles may become "cold," stratify, and not
reach the ceiling or upper walls where detectors are
located.

Smoke particles may be blown away from detectors
by air outlets.

Smoke detectors may be drawn into air returns before
reaching the detector.

The amount of "smoke" present may be insufficient to
alarm smoke detectors.  Smoke detectors are designed
to alarm at various levels of smoke density.  If such
density levels are not created by a developing fire at the
location of detectors, the detectors will not go into alarm.

Smoke detectors, even when working properly, have
sensing limitations.  Detectors that have photoelectronic
sensing chambers tend to detect smoldering fires better
than flaming fires, which have little visible smoke.
Detectors that have ionizing-type sensing chambers
tend to detect fast-flaming fires better than smoldering
fires.  Because fires develop in different ways and are
often unpredictable in their growth, neither type of detec-
tor is necessarily best and a given type of detector may
not provide adequate warning of a fire.

Smoke detectors cannot be expected to provide
adequate warning of fires caused by arson, children
playing with matches (especially in bedrooms), smoking
in bed, and violent explosions (caused by escaping gas,
improper storage of flammable materials, etc.).

Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a
predetermined rate or reaches a predetermined level.
Rate-of-rise heat detectors may be subject to reduced
sensitivity over time.  For this reason, the rate-of-rise
feature of each detector should be tested at least once
per year by a qualified fire protection specialist.  

Heat

detectors are designed to protect property, not life.

IMPORTANT! 

 Smoke detectors 

must be installed in

the same room as the control panel and in rooms used
by the system for the connection of alarm transmission
wiring, communications, signaling, and/or power.  If
detectors are not so located, a developing fire may dam-
age the alarm system, crippling its ability to report a fire.

Audible warning devices

 such as bells may not alert

people if these devices are located on the other side of
closed or partly open doors or are located on another
floor of a building.  Any warning device may fail to alert
people with a disability or those who have recently con-
sumed drugs, alcohol or medication.  Please note that:

Strobes can, under certain circumstances, cause
seizures in people with conditions such as epilepsy.

Studies have shown that certain people, even when
they hear a fire alarm signal, do not respond or
comprehend the meaning of the signal.  It is the
property owner's responsibility to conduct fire drills
and other training exercise to make people aware of
fire alarm signals and instruct them on the proper
reaction to alarm signals.

In rare instances, the sounding of a warning device
can cause temporary or permanent hearing loss.

A fire alarm system

 will not operate without any

electrical power.  If AC power fails, the system will
operate from standby batteries only for a specified time
and only if the batteries have been properly maintained
and replaced regularly.

Equipment used in the system

 may not be technically

compatible with the control.  It is essential to use only
equipment listed for service with your control panel.

Telephone lines

 needed to transmit alarm signals from

a premise to a central monitoring station may be out of
service or temporarily disabled.  For added protection
against telephone line failure, backup radio transmission
systems are recommended.

The most common cause

 of fire alarm malfunction is

inadequate maintenance.  To keep the entire fire alarm
system in excellent working order, ongoing maintenance
is required per the manufacturer's recommendations,
and UL and NFPA standards.  At a minimum, the
requirements of Chapter 7 of NFPA 72 shall be followed.
Environments with large amounts of dust, dirt or high air
velocity require more frequent maintenance.  A mainte-
nance agreement should be arranged through the local
manufacturer's representative.  Maintenance should be
scheduled monthly or as required by National and/or
local fire codes and should be performed by authorized
professional fire alarm installers only.  Adequate written
records of all inspections should be kept.

While a fire alarm system may lower insurance

rates, it is not a substitute for fire insurance!

Fire Alarm System Limitations

Содержание APS-6RF

Страница 1: ...Auxiliary Power Supply APS 6RF Instruction Manual Document 50893 07 20 2000 Rev B PN 50893 B ECN 00 317 ...

Страница 2: ...explosions caused by escaping gas improper storage of flammable materials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level Rate of rise heat detectors may be subject to reduced sensitivity over time For this reason the rate of rise feature of each detector should be tested at least o...

Страница 3: ...ipated or encountered Disconnect AC power and batteries prior to removing or inserting circuit boards Failure to do so can damage circuits Remove all electronic assemblies prior to any drilling filing reaming or punching of the enclosure When possible make all cable entries from the sides or rear Before making modifications verify that they will not interfere with battery transformer and printed c...

Страница 4: ...4 APS 6RF Instruction PN 50893 B 7 20 00 This Page Intentionally Left Blank ...

Страница 5: ...S 6RF 12 Connecting Multiple APS 6RF Power Supplies 13 Connecting the APS 6RF to an IC 4F ICE 4F Module 14 Configuring the APS 6RF 15 Servicing the APS 6RF 16 Appendix A Sensiscan 200 Mounting in a CAB 200 Backbox 17 Connecting the APS 6RF to an MPS 24BF 18 Appendix B Sensiscan 2000 Mounting in CAB A3F or CAB B3F Cabinet 19 Connecting the APS 6RF to an MPS 24AF 20 Connecting the APS 6RF to an MPS ...

Страница 6: ...6 APS 6RF Instruction PN 50893 B 7 20 00 This Page Intentionally Left Blank ...

Страница 7: ...scription The APS 6RF Auxiliary Power Supply is a 150W cabinet mounted power supply designed to power devices that require filtered regulated non resettable power such as Notification Appliance Circuit Modules The APS 6RF provides three 24 VDC filtered output circuits Figure 1 APS 6RF Auxilliary Power Supply Control Panels Refer to Part Number Sensiscan 2000 Sensiscan 2000 Manual 15017 Sensiscan 2...

Страница 8: ... circuits Two 2 power limited One 1 non power limited Trouble In J4 Trouble Out J3 P style connectors for internal cabinet connections LED Status Indicators Green LED Indicates AC power on Yellow LED Indicates loss of AC or battery Fuse F2 for battery protection 10A 3AG slow blow Jumpers JP2 and JP3 for selecting 8 hour or 16 hour delay for AC loss reporting default is immediate APS 6Rsidebrd cdr ...

Страница 9: ...ged by the system power supply 24 VDC output power Circuit 1 Circuit 2 Circuit 3 Total 6 A 4 A continuous 3 A 24 VDC power limited 10 15 3 A 24 VDC power limited 10 15 6 A 24 VDC non power limited 10 15 Fuses F1 AC supervision F2 battery supervision 250 VAC 4A 3 AG slow blow 32 VAC 10 A 3 AG slow blow Trouble supervision bus J3 output J4 input Note J3 and J4 can be interchanged Form A contact open...

Страница 10: ...10 APS 6RF Instruction PN 50893 B 7 20 00 NOTES ...

Страница 11: ... instructions for common wiring configuring and servicing the APS 6RF For mounting and specific wiring instructions refer to the appendix concerning your system Installation topics covered in detail Topic Refer to Field Wiring Field Wiring an APS 6RF on page 12 Wiring Multiple APS 6RFs Connecting Multiple APS 6RF Power Supplies on page 13 Connecting to an IC 4F ICE 4F Connecting the APS 6RF to an ...

Страница 12: ...s See appendix for your specific system information Caution When finished wiring AC connections install the press fit terminal block cover over TB1 AC connections Figure 4 Typical Wiring for an APS 6RF J2 J9 J3 J1 TB2 JP3 JP2 Output Circuit 1 Power limited 3 A 24 VDC 10 15 Primary Power 120 VAC or 240 VAC Output Circuit 1 24 VDC Output Circuit 2 24 VDC Secondary Power 24 VDC batteries Trouble Bus ...

Страница 13: ...nd J4 Use Cable 71033 or 75098 same cables different lengths for all wiring See appendix on your system for specific Trouble Input connection Note J3 and J4 can be interchanged Figure 5 Trouble Bus Connections for Multiple APS 6RF Configurations J2 J9 J3 J1 TB2 JP3 JP2 J2 J9 J3 J1 TB2 JP3 JP2 J2 J9 J3 J1 TB2 JP3 JP2 To trouble input on main power supply or control panel First APS 6RF Last APS 6RF ...

Страница 14: ... the APS 6RF output circuit 2 J2 and the four 4 NACs on the ICE 4F are powered from circuit 1 J1 The NACs share the total 3A available from each circuit Typical connections for wiring Figure 6 Typical APS 6RF Wiring to an IC 4F ICE 4F Module J 6 5 J J 6 5 J J2 J9 J3 J1 TB2 JP3 JP2 IC 4F ICE 4F Auxiliary Power Harness PN 71091 Black Blue Blue Black APS 6RF APS 6Ricm cdr ...

Страница 15: ...configured for the following 8 hour delay for reporting loss of AC cut jumper JP2 16 hour delay for reporting loss of AC cut jumper JP2 and JP3 240 VAC operation cut jumper JP1 The figure below illustrates the location of the jumpers Figure 7 Configuring the APS 6RF J P 1 J2 J9 J3 J1 TB2 JP3 JP2 JP3 JP2 JP1 APS 6Rconfig cdr ...

Страница 16: ...remove the vertical PC board as follows 1 Turn off and remove all power sources 2 Remove plastic cover 3 Remove the two retaining screws securing vertical board 4 Unplug the vertical PC board from the connectors 5 Replace fuses as required 6 Reinstall board in reverse order install plastic cover and connect all power The figure below illustrates the location of the fuses Figure 8 Servicing the APS...

Страница 17: ...er from APS 6RF 2 If 240 VAC is to be used cut JP1 jumper at this time See Configuring the APS 6RF on page 15 3 Place the APS 6RF onto the mounting studs in the backbox 4 Insert a standoff through each of the printed circuit board mounting holes threading each standoff to the mounting studs 5 Tighten the standoffs until the APS 6RF is securely fastened to the backbox 6 Reinstall the plastic chassi...

Страница 18: ...F terminal block TB1 Pin 3 NEUT and Pin 4 HOT Connect secondary power from TB3 to MPS 24BF terminal block TB3 Pin 1 and Pin 2 Connect trouble input from J3 to MPS 24BF terminal block P4 Figure 10 Wiring to MPS 24BF J2 J9 J3 J1 TB2 JP3 JP2 JP3 P3 P4 TB3 P1 TB2 TB1 CB1 P2 R55 1 2 3 4 6 7 8 7 5 3 2 1 EARTH AC NEUT COMMON COMMON BATT 24 VRESET AC HOT MPS 24BPCC REV ___ 24 VPOWER BATT TROUBLES AC BATT ...

Страница 19: ...S 4F Chassis Step Action 1 Remove plastic cover from APS 6RF 2 If 240 VAC is to be used cut JP1 jumper at this time See Configuring the APS 6RF on page 15 3 Place the APS 6RF onto the mounting studs of the chassis 4 Insert a standoff through each of the printed circuit board mounting holes threading each standoff to the mounting studs on the chassis 5 Tighten the standoffs until the APS 6RF is sec...

Страница 20: ...nect primary power from TB1 to MPS 24AF terminal block TB1 Pin 5 NEUT and Pin 7 HOT Connect secondary power from TB3 to MPS 24AF terminal block TB2 Pin 1 and Pin 2 Connect trouble input from J3 to MPS 24AF terminal block P5 Figure 12 Wiring to MPS 24AF P4 P3 JP5 TB1 TB2 F1 CB1 P5 R27 P2 EARTH G ND AC NEU TRAL AC HOT 24R CO MMON 24 COMMON POW ER LIMITE D BAT BAT J2 J9 J3 J1 TB2 JP3 JP2 APS 6R to MP...

Страница 21: ...BF terminal block TB1 Pin 3 NEUT and Pin 4 HOT Connect secondary power from TB3 to MPS 24BF terminal block TB3 Pin 1 and Pin 2 Connect trouble input from J3 to MPS 24BF terminal block P4 Figure 13 Wiring to MPS 24BF J2 J9 J3 J1 TB2 JP3 JP2 JP3 P3 P4 TB3 P1 TB2 TB1 CB1 P2 R55 1 2 3 4 6 7 8 7 5 3 2 1 EARTH AC NEUT COMMON COMMON BATT 24 VRESET AC HOT MPS 24BPCC REV ___ 24 VPOWER BATT TROUBLES AC BATT...

Страница 22: ...22 APS 6RF Instruction PN 50893 B 7 20 00 NOTES ...

Страница 23: ... wiring 12 fuses 16 H High Voltage Warning 11 I IC 4F ICE 4F 12 14 connections to 14 Installation topics 11 internal modules 12 J J1 connection 12 J2 connection 12 J3 connection 13 J4 connection 13 JP1 jumper 15 17 19 JP2 jumper 15 JP3 jumper 15 jumpers location of 15 M Mechanical Specifications 9 MPS 24AF 20 MPS 24BF 18 21 multiple power supplies 13 N NAC Modules 7 NACs 14 Non power limited circu...

Страница 24: ...tion PN 50893 B 7 20 00 serviceable components 16 Specifications 9 standoff 17 19 T TB2 12 TC 2F TC 4F 12 terminal block cover 12 Trouble Bus 12 trouble connectors 13 trouble input 18 20 21 W Warning High Voltage 11 wiring 12 ...

Страница 25: ...APS 6RF Instruction PN 50893 B 7 20 00 25 ...

Страница 26: ...26 APS 6RF Instruction PN 50893 B 7 20 00 ...

Страница 27: ...ransportation prepaid to the manufacturer This writing constitutes the only warranty made by this manufacturer with respect to its products The manufacturer does not represent that its products will prevent any loss by fire or otherwise or that its products will in all cases provide the protection for which they are installed or intended Buyer acknowledges that the manufacturer is not an insurer a...

Страница 28: ...World Headquarters One Fire Lite Place Northford CT 06472 1653 USA 203 484 7161 Fax 203 484 7118 www firelite com ...

Отзывы: