![Fire-Lite APS-6RF Скачать руководство пользователя страница 17](http://html.mh-extra.com/html/fire-lite/aps-6rf/aps-6rf_instruction-manual_2291040017.webp)
APS-6RF Instruction PN 50893:B 7/20/00
17
Appendix A: Sensiscan 200
Mounting in a CAB-200 Backbox
The Auxiliary Power Supply is mounted as shown in the figure below.
To mount the APS-6RF, follow these instructions:
Figure 9 Mounting an APS-6RF to a CAB-200 Backbox
Step
Action
1
Remove plastic cover from APS-6RF.
2
If 240 VAC is to be used, cut JP1 jumper at this time. See "Configuring the
APS-6RF" on page 15.
3
Place the APS-6RF onto the mounting studs in the backbox.
4
Insert a standoff through each of the printed circuit board mounting holes,
threading each standoff to the mounting studs.
5
Tighten the standoffs until the APS-6RF is securely fastened to the
backbox.
6
Reinstall the plastic chassis cover.
Standoff
(2 places)
APS-6RF
Assembly
CAB-200
Backbox
Mounting