Document 50400 Rev A 5/15/96 P/N 50400:A
Mounting to Backbox
Mounting to Backbox
Mounting to Backbox
Mounting to Backbox
Mounting to Backbox
Remove the plug-in terminal blocks from the LED-10 circuit board. Connect the EIA-485
and power wiring into the terminal block positions illustrated in Figures 1-1, 4-1 and 4-2.
Plug the terminal blocks back into the TB1 and TB2 connectors on the back of the LED-
10.
Set DIP switches SW1 and SW2 for the desired options (refer to Figures 1-1 and 1-2
and Table 1-1).
Mount the LED-10 to the three-gang electrical box using the four mounting holes on the
LED-10 flange and the four screws provided for this purpose. Replace the trim ring and
secure with the two screws which were previously removed. Adjust the plastic trim ring
to the surface of the wall before tightening the screws.
Do not overtighten.
Figure 3-2: LED-10 Mounting
Figure 3-2: LED-10 Mounting
Figure 3-2: LED-10 Mounting
Figure 3-2: LED-10 Mounting
Figure 3-2: LED-10 Mounting
LED-10 flange
Mounting Holes (4)
Three-gang electrical
box, 2.5" minimum depth
(Fire•Lite P/N 10103 or
equivalent).
flange
Three-gang electrical box, 2.5"
minimum depth (Fire•Lite P/N
10103 or equivalent).
EIA-485 and power wiring
LED-10
MountingMountingMountingMountingMounting