9.5.8 OPT failure protection
For the OPT sensor, it is used for the defrost function in heating mode. If OPT sensor works well,
the unit will check the data from OPT sensor, then decide if go to defrost function. Please refer to
11.3.4.
If there is failure with OPT sensor, the unit would work with automatic defrost function. See as below:
Automatic defrost function start condition:
Heating mode, and compressor continuously works for 25 minutes, if IPT-RT
18
ć
, the unit would go
to defrost function.
Automatic defrost function stop condition:
When the compressor works for 12 minutes, unit would stop defrost function.
9.5.9 Fan speed
Indoor fan speed in cooling mode: Hi/Med/Low: 1250rpm/1100rpm/900rpm
Indoor fan speed in heating mode: Hi/Med/Low: 920rpm/850rpm/800rpm
10. Precaution
When using electrical appliances, basic safety precaution should always be followed:
• Do not place objects on the product or allow objects to obstruct the inlet or outlet openings. Extreme
care should be taken when any product is used by or near children and pets and whenever the
Indoor fan speed in heating mode: Hi/Med/Low: 920rpm/850rpm/800rpm
Outdoor fan speed: Hi/Low: 2350rpm/1800rpm/
care should be taken when any product is used by, or near children and pets, and whenever the
product is left operating and unattended.
Please note:
Before operating the product, remove the air conditioner from its package and check it is in good
condition.
• Do not let children play with the packaging, for example plastic bags.
• Do not operate any product with a damaged cord or plug, or after the air conditioner malfunctions,
has been dropped, or damaged in any manner.
• Always operate the product from a power source of the same voltage, frequency and rating as
indicated on the product identification plate.
• This air conditioner is not intended for use in wet or damp locations.
• Do not place the air conditioner near an open flame, cooking or heating appliance, or hot surface.
• Do not let the power cord hang over the edge of a table or counter. Arrange the power cord away
from an area where it may be tripped over
from an area where it may be tripped over.
• Never place the power cord under a carpet or rug. Do not operate the air conditioner in areas where
petrol, paint, or other flammable liquids are used or stored.
• Do not carry out any cleaning or maintenance or access internal parts until the air conditioner has
been disconnected from the mains electricity supply.
• Avoid prolonged direct contact with the flow of the air from the air conditioner and the room being
closed with no ventilating for a long period of time.
Содержание iCOOL
Страница 4: ...3 Overall Dimensions Note The external pipes are same Ø197mm ...
Страница 5: ...4 Explosion view and parts list 4 1 iCOOL Explosion view ...
Страница 8: ...4 2 iWARM Explosion view ...
Страница 12: ......
Страница 13: ...7 Installation ...
Страница 14: ......
Страница 15: ......
Страница 19: ...8 ICOOL IWARM Electric wiring ...
Страница 28: ...R25 5 0K 1 7HPSe 5HVLVWDQFH YDOXH 7HPSe 5HVLVWDQFH YDOXH 7HPSe 5HVLVWDQFH YDOXH 7HPSe 5HVLVWDQFH YDOXH 23 7103 ...