2
optional;
⑶
Alarm
:
‘
0
’
:
no set alarm
;
‘
1
’:
one alarm ( alarm mode optional)
;
⑷
Input signal
:
“8”: Free exchange of the input signal
⑸
Main control mode
:
‘
space
’
:
relay normally-open contact output;
‘
A
’
:
Single phase zero trigger control;
‘
G
’
:
Solid state relay control output
(6) Suffix
:‘
K
’
:
with 485 or RS232 Communication module interface
;
‘
WT
’
:
With an external mini printer module interface
Ⅴ
、
Code setting mode
Serie
s
Code
Name
Setting range
Manual
Ex-Factory
First
Menu
0
LOCK
Electronics
lock
0
~
50
LOCK=18, all the parameter can be
revised;
LOCK
≠
18 all the parameter can
not be revised
18
1
Sn
Input type
、
、
、 、
CU50(
)
-50.0~150.0℃
Pt100(
)-199.9~600.0℃
K( )
、 -30.0~1300℃
E( )
、 -30.0~700.0℃
J( ) -30.0~900.0℃
2
ALP
Alarm output
definition
0
~
6
‘0’no alarm; ‘1’upper limit alarm;
‘2’lower limit alarm;
‘3’positive deviation alarm
‘4’negative deviation alarm.
‘5’outside the interval alarm
‘6’inside the interval alarm
1
3
t
Output cycle
0
~
120 S
relay control action cycle setting
10 S
4
dp
Display
accuracy
0~1
1: have radix point,
0: have not radix point
0
5
P-SH
The max. value
of temperature
range
P-SH
≥
P-SL
They are used to reset proper
temperature range as per user’s
application.
As for the Max. temperature range for
different inputs, please refer to
Sn,
1300
6
P-SL
The min. value of
temperature
range
0
7
OPB
Assistant
output method
0~2
0
:
no Assistant output
;
1
:
RS485 communication
2
:
Mini printer
0
8
Add
Address
1
~
64
(
1
~
9999min
)
The meter’s number in the control system
(in mini type as print times)
1
9
bt
Baud rate
——
1200
;
2400
;
4800
;
9600
Four optional
9600
In the following parameters, N represents the corresponding channel number 1 ~ 4.
10
SP
+
N(1~4)
N channels
control setting
Rang decide by
P-SL, P-SH,
deviation alarm
Setting value of temperature
50
www.finglai.com