1. Labels and Symbols
The labels on the inverter show the conformity marking, main technical
data and identification of the equipment and manufacturer.
The below labels are intended as an example only; in fact, other models
of inverter are available
Regulatory Label
Identification label
Inverter Model
Inverter Part Number
Inverter Serial Number
consisting of:
YY = Year of manufacture
WW = Week of manufacture
SSSSSS = sequential number
Week/Year of manufacture
Manufacturer
SN WLAN: SSSSSSSSSS
PN WLAN: PPP.PPPPP.PP
Mac Address:
XX:XX:XX:XX:XX:XX
SN WLAN: SSSSSSSSSS
SN Inverter: SSSSSSSSSS
MAC: XX:XX:XX:XX:XX:XX
PK: KKKK-KKKK-KKKK-KKKK
Remove and apply on the Quick installation guid
e
Wireless
Identification Label
WLAN embedded board Serial Number
WLAN embedded board Part Number
MAC address:
To be used to obtain the SSID of the wireless access
point created by the inverter: ABB-XX-XX-XX-XX-
XX-XX (where “X” is a hex digit of the MAC address).
To be used to obtain the “Host Name”: http://ABB-
XX-XX-XX-XX-XX-XX.local (where “X” is a hex digit
of the MAC address).
MAC address it’s the only required information to
register the inverter with Aurora Vision.
Inverter Serial Number
Product Key:
To be used as wireless access point password, or to
be used to access to the Web UI as username and
password in case of lost credentials, and to commission
inverter using ABB Installer for Solar Inverters.
ATTENTION –
A
The labels placed on the equipment absolutely
MUST NOT be removed, damaged, dirtied, hidden, etc.
In the manual and/or in some cases on the equipment, the danger
or caution areas are indicated with signs, labels, symbols, icons.
Always refer to instruction manual
General warning - Important safety information
Dangerous voltage
Hot surfaces
,3;;
Protection rating of equipment
Temperature range
Without insulation transformer
Direct and alternating current, respectively
Positive and negative pole of the input voltage (DC)
Obligation to use protective clothing and/or personal
protective equipment
Point of connection of the protective ground
Risk of electric shock.The discharge time (quantified in the
figure by the number XX) of the stored energy after de-
energizing of the Inverter from both DC side and AC side.
2. Installation site and position
• Consult technical data to confirm the environmental specifications will
be met.
• Installation of the unit in a location exposed to direct sunlight is acceptable.
Except for the version equipped with a display.
• Do not install in closed spaces where air does not freely circulate.
• Always ensure that the flow of air around the inverter is not blocked, so as
to prevent overheating.
• Do not install near flammable substances (minimum distance: 3 m).
• Do not install near on wooden walls or near flammable surfaces.
• Do not install in rooms where the people live or where the prolonged
presence of people or animals is expected.
• Installation of these models can be carried out vertically or horizontally
with a maximum inclination as indicated in the figures.
• Hardware and software maintenance on device entails opening the front
door. Check that the correct installation safety distances are observed in
order to allow routine check and maintenance operations.
• Install on a wall or strong structure suitable to bear the weight.
• If possible, install at eye-level so that the status LEDS can be seen easily.
• Install at a height which takes into consideration the weight of the
appliance and in a position which is suitable for servicing, unless suitable
means are provided to carry out the operation.
• Final installation of the device must not compromise access to any
disconnection devices that may be located externally.
• Respect the minimum distances from objects around the inverter that
could prevent the inverter installation and restrict or block the air flow.
• Provide sufficient working space in front of the inverter that allows to
make connections on the wiring box.
• In case of multiple installation position the inverters side by side keeping
the minimum distances (measured from the outer edge of the inverter)
for each inverter. If the space available does not allow this arrangement,
position the inverters in a staggered arrangement as shown in the figure
so that heat dissipation is not affected by other inverters below.
• The vertical installation in also permitted on a structure which must be
composed of a support for the attachment of the bracket and one for the
support of the rear pins.
• The vertical installation of two inverters positioned back to back in also
permitted on a structure which must be composed of 2 supports for the
attachment of the brackets.
• The inverter operates normally up to 2000 meters; between 2000 and
4000 meters the inverter works in derating (to verify curve derating),
above 4000 meters the installations are forbidden.
• Never open the inverter in the case of rain, snow or a level of humidity
>95%.
PVS-6
0
PVS-60
PVS-60
OPE
N
LOC
K
OPE
N
LOC
K
OPE
N
LOC
K
PVS-60
PVS-60
PVS-60
PVS-60
PVS-60
PVS-60
PVS-60
PVS-60
PVS-60
PVS-60
50 cm
01
02
50 cm
5̊ max
20 cm
30 cm
ok
ok
ok
ok
ok
no
ok
ok
ok
ok
03
05
06
04
ATTENTION –
A
Do not block access to the external AC and DC
disconnect switches.
ATTENTION –
A
Please refer to the warranty terms and conditions
and avoid voiding the warranty with improper installation.