• Pass the AC cable 

through the AC 

cable gland 

(23).

• Strip the AC cable 

and wires

• Install ferrule with plastic collar on the wires.

• Install the wires (based on the AC connection type) respecting the 

connections as indicated on the screw terminal block (L1=R ; L2=S ; 

L3=T):

A.Five-cores cable (L1, L2, L3, N and PE).

B.Four-cores cable (L1, L2, L3 and N).

C.Four-cores cable (L1, L2, L3 and PE).

D.Three-cores cable (L1, L2, L3).

M4

1.5Nm

L1 N PE

L2

L3

T S R

 ATTENTION – 

A

In case of a wrong phase sequence the inverter will 

not connect to the grid and it will provide an error state.

• Re-install the screw terminal block inside the AC quick fit connector.

 ATTENTION – 

A

Push  the screw terminal block till a double “click” 

will be heared.

• Tighten the cable gland ring (7.5Nm).

 ATTENTION – 

A

Make sure the cable glands are properly sealed to 

ensure to keep IP65 protection degree.

7.5.1  Connection of AC quick fit connector to the inverter

• Pull out the protective cap from the AC output connector 

(17)

.

• Connect the AC quick fit connector 

(09)

 to the AC output connector 

(17)

.

Click 

Click 

 ATTENTION – 

A

Push the connector till a double “click” will be heared.

• Secure the AC quick fit connector. Install and screw the holding clip.

 ATTENTION – 

A

The AC quick fit connector must not be subject to 

tensile forces (examples: do not connect weights to the AC cable, do 

not leave excess cable windings hanging, etc).

8.  Input connection (DC)

For the strings connections it is necessary to use the DC input quick fit 

connectors 

(13)

, located on the bottom side of the inverter.

13

The input connectors are divided into 2 groups (one group for each input 

MPPT). For each MPPT 2 pairs of quick fit connectors are available.

Respect the Maximum DC input power for each MPPT as follow:

MPPT

PVS-10-TL

PVS-12.5-TL

PVS-15-TL

IN1

17A / 7.8kW

18A / 8.3kW

22A / 10kW

IN2

17A / 7.8kW

18A / 8.3kW

22A / 10kW

8.1  Preliminary operations to the connection of 

the PV generator

• Checking the correct polarity of the strings

• Checking of leakage to ground of the photovoltaic generator

• Checking of strings voltage

• Installation of quick-fit connectors

8.2  Connection of the input strings

 WARNING – 

B

When the photovoltaic panels are exposed to sunlight 

they provide continuous DC voltage to the inverter. To avoid risks of 

electrical shock, all wiring operations must be carried out with the DC 

disconnect switches (internal 

(07)

 and external to the inverter) and 

external AC disconnect switches OFF.

• Connect all the strings required by the system by pushing the quick fit 

connectors in the right position.

 ATTENTION – 

A

Using coupling parts that are not compliant with 

the quick fit connector models on the inverter could cause serious 

damage to the unit and lead to invalidation of the warranty.

X

X

Y

12...16 mm

0.47...0.63 ”

Y

75...80 mm

2.95...3.15 ”

Содержание PVS-10-TL

Страница 1: ...tion information provided in the product manual must be read and followed The technical documentation for the product is available at the website The device must be used in the manner described in the manual If this is not the case the safety devices guaranteed by the inverter might be ineffective APPLY HERE THE COMMUNICATION IDENTIFICATION LABEL ...

Страница 2: ...who has a good knowledge of the installation conditions the devices that will be installed externally and whether it will eventually be integrated into an existing system 1 1 Main inverter components Inverter external view 01 Inverter 10 USB connector for accessories board 18 Side bracket screws 02 Heatsink 11 Ethernet 1 2 connectors 19 Padlock hole 03 Synoptic LED icons 12 Digital input and RS485...

Страница 3: ...g and transporting Transportation and relocation The transportation of the device in particular via land transportation must be made with adequate means and ways to protect the parts from violent impacts humidity vibrations etc ATTENTION A If the package is stored correctly it can withstand a maximum load of 5 stacked pallet 2 units each pallet Lifting The means used for lifting must be suitable t...

Страница 4: ...clearance distances H of 100cm 39 and I of 30cm 12 G I I H H H G G ATTENTION A Please check the product manual for Wireless signal environmental checks Installations at high altitudes and Installations with a high level of humidity NOTE D The final installation of the inverter must not compromise the access to any disconnection devices located outside NOTE D Refer to the warranty conditions to eva...

Страница 5: ...g the specific AC quick fit connector 09 supplied AC conductor cable Cable diameter range 11 19 mm or 19 26mm based on the type of seals installed Conductor cross section 6mm2 16mm2 with plastic collar ferrule accepted by the AC quick fit connector Conductor material copper 7 3 Protection switch under load AC switch and differential protection To protect the AC connection line of the inverter it i...

Страница 6: ...o not connect weights to the AC cable do not leave excess cable windings hanging etc 8 Input connection DC For the strings connections it is necessary to use the DC input quick fit connectors 13 located on the bottom side of the inverter 13 The input connectors are divided into 2 groups one group for each input MPPT For each MPPT 2 pairs of quick fit connectors are available Respect the Maximum DC...

Страница 7: ...ioning procedure to be completed Open the Installer for solar inverters APP Login or Sign In to Aurora vision account Tap on Commissioning wizard A QR code scanner will be opened Scan the QR code on the Communication identification label and connect to inverter network NOTE D The name of the Wi Fi network created by the inverter will be FIMER YYWWSSSSSS 10 digit Inverter SN NOTE D After this step ...

Страница 8: ... A 32 A 32 A Output overvoltage protection SPD Type 2 Operating performance Maximum Efficiency ηmax 98 4 98 5 98 5 Weighted Efficiency EURO 98 1 98 2 98 2 Environmental Operating ambient temperature range 25 60 C 13 140 F with derating above 45 C 113 F Storage temperature 40 C 85 C 40 F 185 F Relative Humidity 4 100 with condensation Sound pressure level typical 40 dB A 1m 45 dB A 1m 45 dB A 1m Ma...

Отзывы: